Document 1QQNzOvM1mKedxZXBM3e4ad5K

400 CHAPTER 35 K, -- 0.38 <aT)*m for top horizontal surface " 0.20 (&T)*** for bottom horizontal surface heat gain ------- 1S02 X 60----------- 38,300 Bluh -----i-----+ _1_ 12 X 0.12 1.73 Equivalent temperature rise per day 38,300 X 24 3.5 P deg per day 31,000 X 8.5 _ ,. . 6S,6W Tons refrigeration - - -- 3.2 6 12,000 However, the performance of typical coolers at 15 F may be as little as 20 percent of rated value, ao some 15 rated tons of ca pacity could be needed. 2a. Same conditions as for Example 1 except for concrete tank, 20X20X20 ft, with 12 in. walls, capacity approximately 49,500 gal, consisting of 4 exposed walls and exposed top, exposed area 2000 sq ft. Thermal conductivity, k, for dense concrete, 0.7. ,, . 2000 X 60 Heat gain - -j-------- -- - 60,000 Btuh Temp rise per day 60,000 X 24 * 3.4 P deg per day 49,500 X 8.5 2b. Saving possible with 4 in. of corkboard insulation, k 0.025 Heat gain 2000 X 60 1,1, 4 0.7 + 1.73 + 12 X 0.025 7820 Btuh Saving -- 87 percent. Equipping the storage cellar with a refrigeration room of large capacity containing a considerable number of tanka ia a convenient but relatively costly method of chilling wines. In practice, it is used principally by the smaller wineries where a large number of wines can be chill-proofed simultaneously. As already indicated, the rate of precipitation of cream of tartar is a time-temperature relationship, the tima necessary to effect adequate precipitation being markedly dependent upon the temperature. While a period of 15 days or more may be adequate for most wines held to within a degree of their congealing points, this time ia markedly prolonged by a tem perature rise of only a few degrees (Fig. 5). This is one of the chief disadvantages of Hie previous two systems. In operation Hie wine may be allowed to fall to the tempera ture of the room through simple placement in storage. More frequently, however, the system is supplemented by use of an external chilling apparatus. The wine from the outside storage cellar is chilled almost to refrigerated storage temperature by circulation through the sheO-and-tube cooler before entering Hie refrigerated cellar. It is then held at constant temperature for the time required to effect adequate cream of tartar sep aration. In France, Italy and North Africa, a type of direct expan sion ammonia cooler incorporating mechanical agitation msfrfa the tube or liquid side has been employed for chill-proofing of wines and for concentration of wines by freering out water.7 Advantages claimed are more rapid stabilisation owing to the close approach to congelation possible and more rapid tar trate deposition resulting from agitation. At present, con centration of wines by freezing is not legally permitted in the United States. However, it would appear to offer considerable promise in production of better quality high alcohol type wines to supplant, perhaps in part, the practice of adding wine spirits. Concentration by freezing would increase acidity and soluble solids as well as alcohol which are generally too low in many dessert type wines made with added wine spirits. 1962 Guide And Data Boofc The wine ride of heat interchange surfaces frequently come coated with a deposit of tartrate material which rednepo their efficiency. This is easily removed by circulation of a dilute lye solution through the system. All systems should be constructed of non-corrosive metals and the refrigerant used should be noninjurious to the wine or health, in caap 0f feab in the systems. Refrigeration Requirements for Cooling Heated Must Short-time heating of crushed red grapes (rowf) to tempera, tures of 190 F destroys the eeJlnUr structure and liberates Hie red coloring matter into the juice. The change in physical structure also permits easy separation of juice and cellular materials by pressing. When heating and cooling cycles are carried out in heat transfer units designed for rapid heat ex change, little or no change in flavor occurs. Red grapes can thus be fermented as juice and the pomace need never enter the fermenting cellar. Present units are for Hie most part of the tube-in-tube type. They consist of 20 ft lengths of 4 in. pipe inaiHa of which ia mounted a single length of 3 in. pipe, connected by suitable return bends and banked together in a variety of ways. Sev eral sections are used for heating, more for regeneration and others for cooling. It now appears that reducing the crashed mass to much below 120 F by regenerative heat transfer is im practical. Cooling from 120 to 70 F or the removal of from 85,000 to 100,000 Btu per ton of grapes passed through the units must be provided. Very few wineries have the required amount of refrigeration to successfully complete the cycle. Water as a secondary refrigerant appears most ftriupfoblg to the process at present. Refrigeration Requirements for ChillProofing Brandy A relatively minor application of refrigeration in the wine industry is chill-proofing of brandy just prior to bottling. Dis tilled spirits, including brandy, are aged in oak barrels at alcoholic strength somewhat higher than that at which they are usually marketed. For brandy, the proof during aging in wood is 102 to 115. During processing for bottling, the proof is generally reduced to 84 by addition of water. The reduction of alcoholic strength results in a partial precipitation of the alcohol-soluble, water-insoluble wood ex tractives. These ill-defined wood-extract substances are much less soluble at low than at higher temperatures. Consequently, in order to insure continued bottle stability, producers subject brandies to a low temperature holding period of 1 to 14 days. The temperatures used vary from about 15 to 25 F. Experience has indicated that the insoluble ma terials separate almost immediately upon shilling It tends to rapidly redissolve with rising temperatures. Therefore, it is essential that the brandy be filtered at the low temperature to which it has been stabilized. Apparently the only advantage of holding at a low tempera ture for several days is to allow the suspended material to settle to the bottom of the holding tank which thereby fa cilitates the filtration. Filter rates are slow at best, owing to the high viscosities of water-alcohol mixtures at low tempera tures. For example, the viscosity at 32 F of 40 percent (by weight) ethanol is 7.2 centipoises, or more than four times as much as either pure ethyl alcohol or water at this temperature. In the range of temperatures used for chill-proofing the vis cosity is markedly greater, which has a marked adverse ef fect on heat transfer coefficients. The procedures employed by brandy producers vary. Gen- Beverage Processes Table 3 .... Volume of COj Gas Absorbed in One Volume of Water Pressure, in botile, psig 0 10 20 30 40 SO 60 70 SO 32 1.71 2.5 4.0 5.2 6.3 7.4 8.6 9.7 10.9 40 1.45 2.4 3.4 4.3 5.3 6.3 7.3 8.3 9.2 50 1.19 2.0 2.8 3.6 4.4 5.2 6.0 6.8 7.6 60 1.00 1.7 2.3 3.0 3.7 4.3 5.0 5.7 6.3 70 085 1.4 2.0 2.5 3.1 3.7 4.2 4.8 5.4 80 0.73 1.2 1.7 2.2 2.7 3.2 3-6 4.1 4.6 90 0.63 1.0 1.5 1.9 2.3 2.7 3.2 3.6 4.0 100 0.56 0.9 1.3 1.7 2.0 2.4 2.8 3.2 3-5 90 12.2 10.3 8.5 7.1 6.1 5.2 4.5 3.9 401 100 13.4 11.3 9.5 7.8 6-6 5.7 4.9 4.3 gafly insulated stainless steel tanks of 1000 to 5000 gal capac ity are used for processing tanks. Some use direct expansion of refrigerant into coils installed inside the tanks while others tfrppnrf on circulating Hie brandy through external heat ex changers with direct expansion of refrigerant, much in the manner as the wine coolers described earlier. Holding temperatures used have been reported as tow at 10 F but 18 to 20 F is more usual. Present information indicates that the temperature of the brandy as it passes the filter is that to which the brandy can be regarded as cold stable. Brandy can be considered to have the same specific heat and density values as ethyl alcohol-water mixtures at equiv alent concentrations. PART III: CARBONATED BEVERAGES Refrigeration equipment is required in most, carbonated brar&ge bottling plants to cool the water used in Hie prod uct, the sirup or the finished beverage. The refrigeration load varies with production conditions, and whereas small plants may utilize only about four tons of refrigeration, a large plant will require over 300 tons. Cooling the water, sirup or finished beverage serves to: (1) obtain maximum stability of the carbonated beverage during bottle filling, which becomes very critical under present day high speed operations; (2) promote uniformity of the finished beverage; and (3) permit reducing the pressure at which the beverage is filled into the bottle. In order to prepare carbonated water that will have Hie proper life and will show the desired sparkle and release of carbon dioxide gas when the finished beverage is served, Hie water is supersaturated by carbon dioxide gas under pressure in an apparatus known as a carbemaior. The amount of gas dissolved varies direcUy with the temperature of the water and the carbon dioxide gas pressure. It is found that the lower the temperature of the water, the less the gas pressure needed for a given carbonation of the water, for cold car bonated water shows less tendency to lose its gas while going through Hie bottle filling machines, meaning it is more stable. For example, at 60 F and atmospheric pressure, a given TOhmie of water will absorb an equal volume of carbon di oxide gas. If the carbon dioxide gas is supplied to the water nnder a pressure of two atmospheres (approximately 15 psig), the water will absorb two volumes. For each additional 15 Psig, one additional volume of gas is absorbed by the water. Reducing Hie temperature of the water to 32 F increases the nbeorption by the water to 1.7 volumes. Therefore, each 15 psig additional at 32 F water temperature, gives an additional 1.7 volumes, instead of one volume, as is the case when Hie water temperature is 60 F. The commonly used data on the relationship of pressure and temperature to the volumes of carbon dioxide dissolved per volume of water is presented in Table 3. Beverages of low carbonation fall below 3.5 volumes of carbon dioxide per volume of water, while the higher carbonation may run up to 5.0 volumes, depending on the product. Types of Water Coolers Although there is a variety of nrprhanWl designs for water coolers, they are to be considered first as to function, namely, instantaneous or storage type based upon the rate of cooling and the volume of water hold-up. The storage type has lost position in recent years because the instantaneous cooler has better sanitation facilities, operating economy, requires less space and inherently must be soundly engineered to the actual refrigeration demands of the plant. The cooling of water is carried out in one of a number of water cooling units of several designs: Baudelot, tank unit, cascade tray, shell-ond-coil, sheU-and-tube and carbonatorcooler. The Baudelot or descending film type of cooler consists of stamped, corrugated, stainless steel sheets which resemble a washboard and in which the corrugations form channels for the refrigerant flow. The water to be cooled trickles down in a thin film from an overhead pan containing distributing holes. The tank type cooler has the refrigerant expansion coils im mersed in a tAiik of water. Other arrangements baffle the water for long flow. The cascade tray type has a series of inclined trays in which the expansion coils are laid, over which Hie water passes in flowing by gravity from the* highest tray on down to the lowest, usually in a zig-zag path. The internal-coil or sheU-andr-coil type of unit is usually de scribed in the beverage business as a closed system cooler. Water goes through a dosed pipe coil immersed in Hie re frigerant. This form of cooler, since it will operate under pres*' sure, can also be used to cool water further after it has been carbonated. All of the above types of coolers have direct expansion or direct heat interchange between the evaporating refrigerant and the water to be cooled. Differing from these is the brine circulation system which is used either for special design or as precaution against the possibility of refrigerant leakage into