Document 1Q7v1Y5KdmqR0N3dejkN89kXZ
________________________________________________________________ BULL=~iN NC C. = - S
TRANSFORMER
Askarel Inspection & Maintenance Guide Monsanto
0
TOWOLDMON0024014 WATER_PCB-00008483
TM ff (Dmteffite
SECTION A TRANSFORMER ASKARELS.......................................... 1 I. Introduction............................................................1 II. History of Trade Name Types.............................. 1
Table l - The Composition of
Transformer Askarels ........................................... 2 III. Interchangeability ................................................. 2 IV. Table II - Official Transformer Askarel
Shipping Specifications.........................................3 V. Ordering Instructions ........................................... 2
VI. Stability................................................................... 2 VII. Precautions When Handling Drums, Tank Cars
VIII.
and When Opening Transformers.........................4 A Keep Dry During Handling ........................... 4
Table III - Handling and Pumping Temperatures ....................................4 B. Use Ordinary Personal Precautions .............. 4
C. Precautions on Opening an Askarel Transformer.........................................5
Avoid Environmental Pollution............................5
1. Labeling Askarel Transformers...................... 6 2 Disposal of Liquid and Solid Wastes ........... 6 3. Conditioning of New or Recycled Askarel .6
IX. X. XI. XII. XIII.
XIV. XV.
4. Teardown of Transformers for Repair or Scrap ......................................... 7
5. Transformer Disposal ...................................... 7 Expected Service Life............................................7 General Characteristics of Transformer Askarel Fluid............................................................7 Sampling Transformer Askarel Fluid .................3 Evaluation of Askarel Received in New Equipment................................................ 3 Dielectric Breakdown Voltage -- Moisture Relationship........................................... 9 Table IV - Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil.........................................9 Table V - Approximate Solubility of Water in Transformer Askarel and Mineral Oil ... .10 Turbidity ...............................................................10 Check Points for Maintaining Askarel Insulation ............................................... 10 A. General Considerations..................................10 B. Modern Sealing Procedures ..........................11 C. The Older Sealing Arrangements..................12
XVI. Periodic Fluid Inspection and What Checkpoints Mean .................................... 12
A. Visual Inspection............................................13
B. Dielectric Breakdown Voltage ....................13
XVII. Inspection Checklist..............................................13 XVIII. Contamination in Transformers........................... 14
Table VI - Effect of Common Insulation
Materials on Power Factor and Dielectric Strength.............................................. 14 Table VII -- Effect of Common Insulation
Materials on Volume Resistivity of Askarel.......................................................... 14
XIX. ASTM Method for Investigating the
Compatibility of Transformer Insulation
and Construction Materials in Askarels............15 XX. Refining Askarel for Re-Use.............................. 15
A. Filtering Through Dry Blotter Paper
to Remove Moisture and Extraneous Particles...................................... 15 Table VI11 - Water Removal by Filtering
Askarel Through a Paper Press ..........................16
B. Disposal of Solid Wastes ...............................16
C. Solid Insulation Requiring Drying...............16
D. Earth Treatment for Maximum Improvement of Power Factor and
Volume Resistivity .......................
16
Table IX Effect of Power
Factor and Volume Resistivity......................... 17
XXI. Cleaning Arced Transformers............................ 17 XXII. Sampling Askarel................................................. 17
SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS ............................... 19 I. Introduction..................................................... 19 II. Sources of Contamination................................. 19 III. Sealing Switches and Terminal Chambers .20 IV. Askarel Used Under Mild Arcing Conditions 20 V. Maintenance for Askarel Filled Switches . . 20 VI. Askarel Under Excessive Temperature
or Fault Conditions ........................................... 21
SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO ................................ 22 Types of Analyses Available: .......................................... 22
1) Routine Maintenance Check......................................22 2) Complete Analysis......................................................22 3) Analysis After Earth Refinement ............................22 Appendix A - Askarel Stability and Composition of Arc Formed Gas................................... 23 Appendix B -- Solubility of Gas in Transformer Askarels ......................................................23 Appendix C -- Effect of Temperature on Dielectric Breakdown Voltage of Askarel ................ 23 Appendix D -- Comparison of the Approximate Viscosity in Saybolt Universal Seconds of Transformer Askarels and Mineral Oil....................... 24 Appendix E - The Density of Inerieen 54201 KA 7336-9 and Transformer Pyranol A13B3B-3........................................................... 24 Appendix F - Thermal Conductivity Values of Transformer Pyrarol A13B3B-3.......................... 24 Appendix G -- Heat Capacity .................................. 24 Appendix H -- Coefficient of Expansion..................... 24 Appendix I - Fire Resistance....................................... 24 Appendix J - Seals, Properties and Procurement ..................................................... 25 Appendix K -- Caution Label....................................... 25
0156847
j
TOWOLDMON0024015 WATER_PCB-00008484
TOWOLDMON0024016 WATER_PCB-00008485
TOWOLDMON0024017 WATER_PCB-00008486
0156851
I
TOWOLDMON0024019 WATER_PCB-00008488
TOWOLDMON0024020 WATER_PCB-00008489
0156854
TOWOLDMON0024021 WATER PCB-00008490
TOWOLDMON0024022 WATER_PCB-00008491
TOWOLDMON0024023 WATER PCB-00008492
TOWOLDMON0024024 WATER_PCB-00008493
TOWOLDMON0024025 WATER_PCB-00008494
TOWOLDMON0024026 WATER_PCB-00008495
TOWOLDMON0024027 WATER_PCB-00008496
i tnfltfftfnwi.
nkanl filled transformers, due,, to soluble polar materials. This increate Table VI has no adverse effect on di '
Table VI
,,
Effect of Common InwIatlon MatarUit on^ower
Factor and Dtetectric Strength \ .
(Heat Aged 96Houra in Al^epdl M
Material Immersed
. Alkanl A*t
*Power Factor,;
Percent at SCf '
eye., 100*C
sec.
None (control) Black varnished cloth Copper Pressboard Manila paper phenol formaldehyde r
Shaded Iron Synthetic rubber
1.0 85.0
1.5 2.0 1.6
- 1-! .
36 KV 42 40 37
;
Similarly, trace contaminant!* from materials can lower the vOlume-reifttvity Of its dielectric breakdown voltage* Thirfelhowh-
Effect of Common Inaal on Volume Realttiv{ty<
Sample
1. New askarel before heat 2. New askarel after heat aging 3. After heat aging with \ sq.
a. Phenolic resin tap changer b. Paper c. Grade A pressboard ltan) d. Grade A pressboard (gray) e. Grade A pressboard, laminated strip. f. Cotton wrapping g. Glyptal 1276 cement, cured 48 hrs. at 110^C-
While trace contamination easily lowefii levels, it is important to note that h< does not lower the resistivity. belQJfllj
The different behavior of askarel vs.'rttineretollriivj
summarized as follows:
'
High power factor and li ....._*........ v
.,,
mineral oils are commdnly regarded*'** ',d#o9ef;*!iiN
oil has deteriorated and broken down
moisture is present.
This is NOT TRUE of askarel liquid insulation uplastLttWclleiMh'iC: breakdown voltage is low or the moisture con&Rt4ifcllgttifir <
114
0156861
TOWOLDMON0024028 WATER PCB-00008497
TT\
TOWOLDMON0024029 WATER PCB-00008498
TOWOLDMON0024030 WATER_PCB-00008499
TOWOLDMON0024031 WATER_PCB-00008500
TOWOLDMON0024032 WATER_PCB-00008501
TOWOLDMON0024033 WATER_PCB-00008502
TOWOLDMON0024034 WATER_PCB-00008503
TABLE OF CONTENTS
SECTION A TRANSFORMER ASKAREL
Page
I. Introduction....................*......................................................................................
II. History of Trade Name Types............................................................................... Tabic 1 -- The Composition of Transformer Askarels
I 1
III. Tabic II -- Official Transformer Askarel Shipping Specifications................... A. General Electric Company's Transformer Pyranol A13B3B B. Westinghouse Transformer Inerteen PPO (7336-9)
2-3
IV. Interchangeability and Stability............................................................................ 4
V. Directions For Handling and Personal Precautions............................................ 4
VI. Expected Service Life............................................................................................. 5
VII. Dielectric Strength -- Moisture Relationship................................................... A. Table III -- Dielectric Strength vs. Amount of Dissolved Water in Askarel and Mineral oil B. Table IV -- Approximate Solubility of Water in Askarel and Mineral Oil.
VIII. Table V --Typical Values Found in Askarel Fluid Under Various Con ditions of Use..........................................................................................................
IX. Check Points For Maintaining Askarel Insulation........................................... A. General Considerations B. Modern Sealing Procedures C. The Older Sealing Arrangements
5
6 9
X. Periodic Fluid Inspection...................................................................................... A. Visual Inspection B. Dielectric Strength
11
XI. Inspection Check List............................................................................................ 12
XII. Contamination in Transformers........................................................................... A. Table VI -- Effect of Common Insulation Materials on Power Factor and Dielectric Strength B. Table VII -- Effect of Common Insulation Materials on VolumeResistivity
12
XIII.
Refining Askarel For Re-Use.............................................................................. A. Filtering Through Dry Blotter Paper To Remove Moisture and Extraneous Particles. Table VIII -- Guide to Rate of Dissolved Water Removal By Filtration. B. Earth Treatment for Maximum Improvement of Power Factor and Volume-Resistivity 1. Procedure 2. Effect of Earth on Removal of Scavengers 3. Table IX -- Approximate Relationship Between Power Factor, Volume-Resistivity and Dielectric Strength of Transformer Askarel
14
XIV. Cleaning Arced Transformers............................................................................. 15
XV. Sampling ASKAREL............................................................................................ 17
0156876
|
TOWOLDMON0024035 WATER_PCB-00008504
TOWOLDMON0024036 WATER_PCB-00008505
APPENDIX J
Seals, Properties and Procurement Dow Corning Corporation, Midland, Michigan with Districts at Atlanta, Boston. Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D.C, and Toronto has available Bulletin 09-019. August 1962 entitled ''Silastic Design Oata". This lists the gasket fabricators throughout the country from whom the "Silastic 60" gasketing can be purchased in sheet, extrusions or molded shapes.
Genet ally. Silastic 50 sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers.
Where the gasket is extruded for fitting into a machined groove or between gasket stops. Dow Corning advises use of a scarved joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure.
Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480F.
SPECIFICATIONS4
ASTM D676 ASTM D412 ASTM 0412 ASTM D395
Color Specific Gravity at 77*F Hardness, Shore A. Scale Tensile Strength, psi, min Elongation, percent, min Compression Set after 22 hrs
at 300F, percent, max
White 1.20 + 0.02 45 to 60 800 250
30
*AII physical properties measured on 0.075 inch thick samples molded 5 minutes at 240F, and oven cured 24 hours at 480F.
APPENDIX K_____________________________________________________________________________________
Caution Label The following or equivalent caution statements should be fixed on all containers of transformer askarels and the transformers themselves:
This product contains Polychlorinated Biphenyls (PC8$). Care should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin contact occurs, remove by washing with soap and water. Following eye contact, flush with water. In case of spillage onto clothing, the clothing should be removed as soon as practical, skin washed, and clothing laundered.
Monsanto
MONSANTO INDUSTRIAL CHEMICALS COMPANY SPECIALTY PRODUCTS GROUP 600 N. LINDBERGH BLVD. ST. LOUIS. MISSOURI 63166
The information herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over 40 years from the experience of makers and users of askarel transformers and it is believed will be Helpful. Nothing herein shall be construed as applying to other than askarel insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufacturer of the transformer should also be carefully followed. Because these maintenance directions apply only to the askarel insulation, Monsanto disclaims any liability lor damage to property or miury to ixjrsons arising Irom transformer operation.
UlShH?^
TOWOLDMON0024037 WATER_PCB-00008506
r
CUSTOMER SERVICE CENTERS
AKRON, OHIO 44313 260 Springtide Drive Montrose Development Perk 'it 216/ 666-4111
ATLANTA. GEORGIA 30339 J2C 'rtArsrjie North Perkway -.'O Tel. ,404, 432-7111
BOSTON. MASSACHUSETTS 02149 Everett Station Tel. (617) 337 5010
CHICAGO. ILLINOIS 3158 Des Plaintt Ave. Dos Plaines. H/inott 60018 "et. '312) 296-8833
CINCINNATI. CH/O 45236 1041 -Hoso/oor Road rei. 513) 384-1 tOO
DETROIT. MICHIGAN 500 Northland Towert West Southfield. Michigan 48075 Tel <313) 357 0910
HOUSTON. TEXAS 77027 1301 Post Oak Towat 5051 Weathermen Road Jet. (713) 621-9SSO
LOS ANGELES. CALIFORNIA 90022 6670 Flotilla St. Tel. (213) 723-2492
NEW YORK. NEW YORK 10036 1114 A venue of the Americas Tel. (212) 764-5000
ST. LOUIS. MISSOURI 63166 900 N. Lindbergh Slvd. Tel. (314) 694-1000
SAN FRANCISCO BAY AREA 2710 Lafayette (ante Clare. California 96062 Hi. , 408) 243-0414
SEATTLE. WASHINGTON 98121 2112 ''iird Avenue Nf 206) 522-4203
WILMINGTON. DELAWARE 19810 Suite 204, Bancroft Bldg. J411 Sitvers/da Road HI. 302) 478-4600
Monsanto Industrial Chemicals Co. A Unit of Monsanto Company 300 N. Lindbergh 8lvd., St Louis. Mo. 53164
V. J
Monsanto
0156S?3
TOWOLDMON0024038 WATER_PCB-00008507