The most feasible site for an injection installation of the Sudbury Aqueduct is at the Farm Pond outlet in the vicinity of Dudley Rd. in Framingham where the Metropolitan District Com. owns approxi mately 5.3 acres of land. The Sudbury Aqueduct bisects this parcel of land and abuts property that is owned by the town of Framingham. Furthermore, water drawn from the South Sudbury supply could be fluoridated by facilities located at Farm Pond.
In view of the need to provide complete treatment of the Sudbury supply in the near future, it is recommended that the fluoridation facilities be suitably designed for relocation to the treatment plant when constructed. Consideration should also be given to the relocation of the Leland St. chlorination facilities when a treatment plant is constructed. An analysis-and-control station is also required to monitor flu oride ion concentration in the Sudbury supply. The existing brick structure on the west side of Leland St. is not presently utilized and could be repaired and used to house sampling pumps and analysis-andcontrol equipment. The location of this facility is a sufficient distance downstream from the point of injection (approximately 10 000 ft) to ensure complete mixing and diffusion of the chemical solution.
Comparison of Alternatives
Evaluation of the alternatives indicates that the most feasible method to fluori date the Metropolitan District water sup ply is to utilize chemical storage and feed facilities at the locations proposed in alter native II, shown on Fig. 3. This selection is based on the following comparison of the two alternatives.
1. Alternative II requires one less chemical storage and feed building and monitoring station.
2. Alternative II offers better centraliza tion of facilities for chemical delivery and system operation, control, and mainte nance.
3. Alternative II provides the best op portunity for diffusion and mixing of the fluoride solution.
Conclusion
It was decided that two sites be utilized for the location of fluoridation installation. Both sites proposed are centrally located in Framingham and are separated by a distance approximately 3 mi. Figure 2 shows the approximate location of both the injection facilities and monitoring sta tions for each proposed site. The installa tion at shaft 4 of the Southborough Tun nel would fluoridate all water entering the Hultman and Weston aqueducts. Facili ties at Farm Pond would fluoridate water entering the Sudbury Aqueduct. Collec tively, these three aqueducts furnish the Metropolitan Water District with its entire water supply.
AWWA C402-75
AWWA STANDARD
for
ASBESTOS-CEMENT TRANSMISSION PIPE, 18 IN. THROUGH 42 IN., FOR WATER AND OTHER LIQUIDS
First approved by AWWA Board of Directors Jan. 26, 1975.
Prepared by AWWA Standards Committee on Asbestos-Cement Pressure Pipe
F. Gordon Denson, Chairman
Consumer Members
P. J. Brady, Director of Utilities, Portsmouth, Va. F. G. Denson, Engineering Department, Winnipeg, Man. J. R. FlENDRrcK, Water Department, Fort Worth, Tex. R. W. King, Water Utilities, San Diego, Calif. J. L. Warden, US Bureau of Reclamation, Denver, Colo. J. E. Johnson,* US Bureau of Reclamation, Denver, Colo.
General Interest Members
Gordon C. Anderson,* Insurance Services Office, New York, N.Y.
R. A. Barrows, C. E. Maguire, Inc., Waltham, Mass. S. L. Bishop,* Metcalf & Eddy, Boston, Mass. V. R. Bickel, Department of Environmental Health,
Albuquerque, N.M. Robert S. Bryant, Department of Water & Power,
Los Angeles, Calif. K. J. Carl, Insurance Services Office, New York, N.Y. R. S. Holmgren Jr., James M. Montgomery, La Jolla, Calif. F. A. Obert, Metcalf & Eddy, Boston, Mass. J. S. Slicer, Factory Mutual Research, Norwood, Mass. William Taggart, Wright-McLaughlin Engineers,
Denver, Colo.
Producer Members
Robert D. Baker, Cement Asbestos Products Co., Ragland, Ala.
T. R. Gillen, Johns-Manville Sales Corp., Denver, Colo. Joseph C. Jackson, A/C Pipe Producers Assoc.,
Washington, D.C. A. I. Leff,* Certain-Teed Products Co., Valley Forge, Pa. W. R. Seipt, Certain-Teed Products Co., Valley Forge, Pa. D. W. Sullivan, The Flintkote Co., Ravenna, Ohio
(AWWA) (AWWA) (AWWA) (AWWA) (USBR) (USBR)
(ISO) (NEWWA) (NEWWA)
(APWA)
(ASCE) (ISO)
(AWWA.) (WPCF)
(FMR)
(ASCE)
(AWWA) (AWWA)
(A/C PPA) (AWWA) (AWWA) (AWWA)
* Alternate
462 WATER TECHNOLOGY/DISTRIBUTION
JOURNAL AWWA
Table of Contents
SEC.
Foreword I History of Standard II Information Regarding Use
of This Standard
Standard 1 General 1.1 Scope 1.2 Definitions 1.3 Affidavit of Compliance
2 Physical and Chemical Re quirements
2.1 Composition 2.2 Physical Requirements 2.3 Chemical Requirements
3 Design 3.1 Classification of Pipe 3.2 Pipe Diameters 3.3 Pipe Lengths 3.4 Couplings 3.5 Joints 3.6 Wall Thickness
4 Workmanship and Finish 4.1 Imperfections
5 Inspection, Testing, and Re jection
5.1 Inspection 5.2 Physical Test Require
ments 5.3 Retests (Physical) and
Rejection 5.4 Test for Uncombined Cal
cium Hydroxide 5.5 Test Records
6 Marking and Delivery 6.1 Marking 6.2 Preparation for Shipment
Tables 1 Pipe Classification
AUGUST 1975
2 External Test Load (3-Edge Bearing)
3 Wall Thickness Tolerances 4 Hydrostatic Tests
Figures 1 Crushing Test Assembly
Foreword
This foreword is for information only and is not a part of C402-75.
I--History of Standard
A new pipe material consisting of an intimate mixture of Portland cement and asbestos fibers was introduced to the North American market in 1931 following a number of years of usage in other countries, particularly Italy.
In the ensuing years, this type of pipe gained popularity, and in 1949 AWWA established a committee on standard specifications for asbestos-ce ment pipe under the chairmanship of S. M. Clarke of Greeley and Hanson, Chicago.
The committee developed a standard for asbestos-cement water pipe, which was approved by the AWWA Board of Directors as a tentative standard, AWWA C400-53T, on May 15, 1953. In 1958, the committee was reactivated as Committee 8340D on Asbestos-Ce ment Pipe under the chairmanship of Roy H. Ritter, Whitman, Requardt and Assocs., Baltimore, to review sev eral suggested changes and to recom mend revisions to the standard. The committee produced a revised standard adopted by AWWA as C400-64T on Jan. 27, 1964. It was advanced to "standard" without revision on Jul. 2, 1965.
In early 1968, the committee was re activated as the Standards Committee on Asbestos-Cement Pipe to review and revise all of the AWWA stan dards on asbestos-cement pipe. The committee produced a revised standard approved by the Board of Directors on Jan. 31, 1972, designated as "AWWA Standard for Asbestos-Cement Pres sure Pipe for Water and Other Liq uids, C400-72."
During the past five years, the as bestos-cement pipe manufacturers de veloped a large new range of pipe classifications, designed to give wider freedom of selection to design engi neers. This is of particular signifi cance for large pipeline projects where
the possible savings in material cost can exceed the increased cost of more detailed design, better control of meth ods of installation, and provision of surge controls when justified.
This standard was developed to pro vide the user with a ready reference and specification for this type of pipe known as transmission pipe. The user should not confuse this standard with, or use it in place of, C400-75, "AWWA Standard for Asbestos-Cement Pres sure Pipe for Water and Other Liq uids." Detailed engineering study of the factors listed in Sec. II regarding local installation and operating condi tions, is required to ensure adequate performance of transmission pipe.
The possibility of confusion between this standard and AWWA Standard C400-75, "Asbestos-Cement Pressure Pipe," was carefully reviewed. To re duce this possibility, the pressure pipe designation was revised to an upper limit of 24-in. diameter, and transmis sion pipe ranges were limited to a min imum diameter of 18 in. The overlap ping sizes of 18-24 in. are not anal ogous.
II--Information Regarding Use of This Standard
When ordering pipe covered by this standard, local installation and operat ing conditions should be considered to determine the classification and type of pipe to specify. Also, certain other items must be specified to describe completely the pipe required.
The following criteria are presented for determining the type of pipe to be used under various soil and water con ditions. Each condition should be con sidered separately, even though each may exist in combination with others.
These criteria are based on expo sures within the temperature range of 40-80F (5-28C). For pipe exposures to temperatures beyond these limits, consult the manufacturer.
1. Water transported through the pipe:
(a) Use either Type I or Type II where pH + log (AH) 1> 12.0
(b) Use Type II where pH + log (AH') ^ 10.0
where
pH = index of acidity or alkalin ity of the water in standard pH units
A = the total alkalinity in parts per million as CaCCL
C 402-75 463
H = the calcium hardness in parts per million as CaC03.
2. Water within the soil surround ing the pipe:
Water Conditions Within the Soil
Minimum pH of the
Soil Type Type
I II
(a) Essentially quiescent (b) Mildly fluctuating (c) Rapidly moving or
grossly cyclic
5.0 5.5
6.3
4.0 5.0
5.5
3. Waters and soils with soluble al kali sulfates:
Water Alkali Sulfate ppm
Soil Nonacid Sulfate
ppm
Type I will be attacked to varying degrees by concentrations
>150
>1 000
Type II is resistant to
all levels all levels
Note: Acid sulfate soils and waters, whether the acid is inorganic or or ganic, must be evaluated independently of the preceding criteria, taking into consideration soil permeability and other factors.
by AWWA Standard C400-75, "As
bestos-Cement Pressure Pipe, 4 in. Through 24 in., for Water and Other Liquids," not to transmission pipe cov ered by this standard.
The purchaser is referred to AWWA Standard C603-65 "Installation of As bestos-Cement Water Pipe," for guid ance in the laying of the pipe.
The following information summa rizes the conditions and items that the purchaser should consider when pre paring his supplementary specifications and lists the sections in the standard and other references where they may be found:
1. The standard used; that is. AWWA C402-75
2. Affidavit of compliance (Sec. 1.3), if required
3. Type of pipe to be furnished (Sec. 2.3 and second paragraph in "Foreword," Sec. II)
4. Classification of pipe (Sec. 3.1) 5. Nominal inside diameter (Sec. 3.2)
6. Lineal feet to be furnished in standard and random lengths (Sec. 3.3)
7. Number, size, classification, lengths, and extent of machining of special short lengths (Sec. 3.3.3)
8. Whether inspection by the pur chaser (Sec. 5.1) and special markings (Sec. 6.1.4) are required.
purtenances, which permit reasonable hydraulic analysis, including that for surge.
Sec. 1.2--Definitions
Under this standard, the following definitions shall apply:
1.2.1 Inspection. Inspection of the pipe and the tests by the inspector.
1.2.2 Inspector. The authorized representative of the purchaser, en trusted with the duty of inspecting pipe produced and tests performed under this standard.
1.2.3 Lot. Pipe of the same size, class, and type manufactured during a shift.
1.2.4 Manufacturer. The person, firm, or corporation that manufactures the pipe.
1.2.5 Purchaser. The person, firm, corporation, or government agency en tering into a contract or agreement to purchase pipe according to this stan dard.
Sec. 1.3--Affidavit of Compliance
The purchaser's supplemental spec ifications may require an affidavit of compliance from the manufacturer, whether factory inspection has been required or not, to the effect that the materials furnished under the purchas er's order comply with all applicable requirements of this standard.
For any service outside of these cri teria, consult the manufacturer.
These criteria just previously given for sulfate "resistance" of Type I pipe were taken from Concrete Manual (8th edition), Bureau of Reclamation (pend ing printing as of Mar. 1975).
It is recommended that, for large pipeline projects, the purchaser eval uate local installation and operating conditions, operating pressures and surge pressures, trench loads, and sur face loads as well as corrosive soils and corrosiveness of the liquids to be trans ported when determining the strength classification to be used.
The purchaser is referred-to AWWA C401-64 (formerly AWWA H2) "Standard Practice for the Selection of Asbestos-Cement Water Pipe" for guidance in designing transmission pipe to fit his installation and operating conditions. Attention is directed to the fact that selection curves and related data in the current edition of AWWA C401-64 are applicable to pipe covered
AWWA C402-75
AWWA Standard lor
Asbestos-Cement Transmission Pipe, 18 in. Through 42 in., for Water and Other Liquids
Section 1--General
Sec. 1.1--Scope
This standard pertains to asbestoscement transmission pipe of two chem ical types, each in nine strength classi fications of 18-in. through 42-in.-diam eter pipe, intended to be used for the transmission of water or other liquids under pressure and to be laid under ground in public and private rights-ofway. Asbestos-cement transmission pipe is to be used in pipe systems hav ing relatively steady flows and few ap
Section 2--Physical and
Chemical Requirements
Sec. 2.1--Composition
Asbestos-cement pipe shall be com posed of an intimate mixture of (1) Portland cement or portland blast fur nace slag cement and asbestos fiber with or without silica; (2) or portland pozzolana cement and asbestos fiber-- both (1) and (2) with or without the addition of curing agents. The mix ture shall be free from organic addi tives and the pipe shall be formed under pressure and cured.
Sec. 2.2--Physical Requirements
2.2.1 Bursting strength. Each length of pipe and each coupling shall have sufficient strength to withstand the minimum internal bursting pressures indicated for the classifications in Ta ble 1.
464 WATER TECHNOLOGY
JOURNAL AWWA
TABLE 1 Pipe Classification
Classification
30 35 40 45 50 60 70 80 90
Minimum Internal Bursting Pressure
psi
300 350 400 450 500 600 700 800 900
2.2.2 Crushing strength. Each length of pipe shall have sufficient strength to support the external test load indi cated for its class in Table 2 when subjected to the crushing test proce dure specified in Sec. 5.2.3.
Sec. 2.3--Chemical Requirements
Pipe shall be designated as either Type I or Type II according to its content of uncombined calcium hy droxide as determined by the test pro cedures in this standard for uncom bined calcium hydroxide. The require ments for each type are
Type I--no limit on uncombined cal cium hydroxide
Type II--1.0 per cent or less un combined calcium hydroxide.
Section 3--Design
Sec. 3.1--Classification of Pipe
Sec. 3.2--Pipe Diameters
Pipe shall be made with nominal in side diameters of 18, 20, 21, 24, 27, 30, 33, 36, 39, and 42 in., as specified by the purchaser. The average inside diameter of a standard or random pipe length shall not be less than the nom inal diameter by more than 1.5 per cent.
Sec. 3.3--Pipe Lengths
Pipe shall be produced in standard, random, and short lengths. At least 90 per cent of the total footage of pipe of any classification and size, excluding short lengths, shall be furnished in standard lengths. The remaining 10 per cent may be in random lengths.
3.3.1 Standard length shall be 13 ft 1 in. Coupling areas shall be ma chined or otherwise rendered suitable for making a tight joint with the coupling.
3.3.2 Random lengths shall be cut from standard lengths and shall be not less than 7 ft long. The coupling area of all random lengths shall be ma chined or otherwise rendered suitable for making a tight joint with the coupling.
3.3.3 Short lengths for making con nections to valves, fittings, or struc tures, and for making closures shall be furnished as specified by the pur chaser. They shall be properly ma chined at ends or over their entire length to serve their intended purpose, as specified by the purchaser.
equal or better bonding characteristics, strength, and serviceability as that of an asbestos-cement coupling. The man ufacturer shall submit to the purchaser for approval, prior to manufacturing, specifications and drawings of alternate couplings.
3.4.1 One coupling of the same size and classification as the pipe shall be furnished with each standard and ran dom length of pipe.
3.4.2 Rubber rings shall conform to the requirements of the latest edition of ASTM D1869, "Rubber Rings for As bestos-Cement Pipe."
Sec. 3.5--Joints
Joints shall be capable of withstand ing, without leakage, a hydrostatic pressure test as defined in Section 5.2.2.I.
Sec. 3.6--Wall Thickness
The wall thickness of the machined portion of any length of pipe shall not be less than the manufacturer's stan dard by an amount in inches exceeding that listed for the various sizes of pipe in Table 3.
TABLE 3 Wall Thickness Tolerances
Size of Pipe
in.
18 20-24 27-30 33-36 39-42
Wall Thickness Tolerance
in.
-0.12 -0.14 -0.17 -0.20 -0.23
Pipe supplied under this standard shall be made in one or more of the classifications shown in Table 1. (The numerical value for each classification is equivalent to one tenth of the hy drostatic lot test pressure.
Sec. 3.4--Couplings
A coupling shall consist of an as bestos-cement sleeve of the same type and composition as the pipe and two rubber rings or a device that has
TABLE 2 External Test Load (Three-Edge Bearing)*--lb/lineal ft
Pipe
Classification
Size
in.
30 35 40 45
50
60
70
80
90
18 2 500 3 000 4 000 5 000 6 500 8 500 11 000 14 000 18 000
20 2 500 3 500 4 500 5 500 7 100 9 500 12 000 15 000 20 000
21 2 500 3 500 4 500 5 800 7 300 9 700 12 500 16 000 21 000
24 2 800 3 800 5 000 6 200 8 100 11 000 15 000 19 000 24 000
27
3 500 4 200 5 500
7 000 8 800 12 500 16 500 20 500 27 000
30
3 500 4 500 6 000
7 500 9 700 13 500 18 000 22 500 30 000
33 3 500 5 000 6 500 8 000 10 500 14 500 19 500 24 500 33 000
36 4 000 5 000 7 000 9 000 11 200 16 000 21 000 26 000 36 000
39 4 200 5 300 7 500 9 700 12 000 17 200 22 500 28 000 39 000
42 4 300 5 700 8 000 10 500 13 000 18 500 24 000 30 000 42 000
* It is necessary to apply a load factor to the above three-edge bearing loads in order to correlate them to the field loads. (See AWWA Standard C401-64.)
Section 4--Workmanship
and Finish
Sec. 4.1--Imperfections
4.1.1 Interior surfaces. The inside surface of each length of pipe shall be free from bulges, dents, and tears that result in a variation in diameter of more than 0.20 in. from the diameter of adjacent unaffected portions of the surface.
4.1.2 Coupling areas. The coupling areas of the barrel of each length of pipe shall be free from dents and gouges that can cause leakage from the joint.
4.1.3 Exterior surfaces. Flaking on the exterior surface and edge of ma chined ends shall not extend back by more than 0.500 in. from the end, have
AUGUST 1975
C 402-75 465
a depth of more than 0.125 in., and shall not extend around the perimeter for more than 0.500 in. at any one location.
4.1.4 Straightness. Each length of pipe shall not vary in straightness by more than 0.05 in./ft of length when the variation is measured as follows:
Measure the maximum ordinate from the exterior surface of the pipe by plac ing a straight edge that exceeds the pipe length against the exterior sur face and measure the maximum dis tance from the exterior pipe surface to the straight edge.
Section 5--Inspection, Testing, and Rejection
Sec. 5.1--Inspection
5.1.1 General. Inspection by the pur chaser shall not relieve the manufac turer of the responsibility to furnish material conforming in all respects to the requirements of this standard.
5.1.2 Notification. If inspection is specified by the purchaser, the manu facturer shall notify the purchaser, in advance, of the date, time, and place of testing of the pipe, so that the pur chaser may be represented at the test.
5.1.3 Access. The inspector shall have free access to those parts of the manufacturer's plant that are involved in work performed under this standard. The manufacturer shall afford the in spector, without charge, all reasonable facilities for determining whether the pipe meets the requirements of this standard.
Sec. 5.2--Physical Test Requirements
5.2.1 Test specimens. All pipes and couplings tested under this standard shall be in a normal, air-dried condi tion when tested.
5.2.2 Hydrostatic tests'5.2.2.1 Each standard, random, or short length of pipe and each coupling sleeve shall be tested under an internal hydrostatic pressure as shown for the routine proof test in Table 4. All air shall be expelled and the water pres sure shall be increased to the test pres sure at a uniform rate of not less than 100 psi/s. The test pressure shall be maintained for at least 5 s. Any pipe length or coupling sleeve that shows leakage, sweating, or other defects shall be rejected.
466 WATER TECHNOLOGY
TABLE 4 Hydrostatic Tests
Classification
Routine Proof Test
psi
30 225 35 263
40 300 45 338 50 375 60 450 70 525 80 600 90 675
Lot Test
psi
300 350 400 450 500 600 700 800 900
P
-12 in-
Fig. 1. Crushing Test Assembly
The diagram at the left shows a side view of the test assembly; that at the right, an end view. P represents load; R, approximately 0.5 in.--the radius of the bearings; D, the nominal diameter of the pipe; and C, the clear space between supports. C should be approximately 1 in./ft of internal pipe diameter, but in
no case less than 1 in.
5.2.22 From each 300 standard lengths of pipe or fraction thereof of each size and classification, one 1-ft length of pipe, or longer, shall be cut from an unmachined portion of a pipe length. Each such length shall with stand the hydrostatic lot test shown in Table 4 in the manner specified in Sec. 5.2.2.1 except that the test pressure need not be held for 5 s. If inspection by the purchaser is specified, the in spector shall be permitted to select the length of pipe to be tested. Each length of pipe so tested shall be re tested in the manner and at the pres sure specified in Sec. 5.2.2.1.
5.2.3 Crushing tests. On lots con taining more than 100 lengths of each size and classification, one length from each 300 lengths or fraction thereof shall be tested for crushing strength. If inspection by the purchaser has been specified, the length of pipe to be tested may be selected by the inspector. From each selected length, one unmachined length of pipe 1 ft long shall be cut.
This section shall be tested by the crushing-test method shown in Fig. 1. After 75 per cent of the specified load has been reached, the loading shall be applied at a uniform rate of approxi mately 2 000 lb/min. The test section shall not fail until the total load applied meets or exceeds the applicable value shown in Table 2.
For this test, the two lower bearings shall consist of two straight strips with vertical sides, each strip having its in terior top edge rounded to a radius of approximately 0.5 in. The strips shall be of hardwood or metal; if metal, a piece of leather belting 3/16 in. in thickness shall be laid over them. The strips shall be securely fastened to a rigid block, with the interior vertical faces parallel and a distance apart of approximately 1 in./ft of internal pipe diameter, but in no case less than 1 in. The upper bearing shall be a rigid wooden block, straight and true from end to end. The upper and lower bearings shall extend the full length of the test section.
For those sizes and classifications where the specified crushing load ex ceeds 30 000 lb/linear ft, the test length may be less than 1 ft long. In those cases, the test load shall be such as to
produce an equivalent specified loading per linear foot.
5.2.4 Machines for testing. The machine used for the hydrostatic test shall be such that in no way is the hydrostatic test pressure counteracted.
The machines used for the crushing test shall be substantial and rigid throughout, so that the distribution of the load will not be appreciably af fected by the deformation or yielding of any part of the machine.
Sec. 5.3--Retests (Physical) and Rejection
The failure of any specimen tested for crushing strength to support 75 per cent of the crushing load required in Table 2 shall be cause for rejection of the entire lot of that size and classifi cation manufactured during the same shift as the test specimen. If any spec imen tested for crushing strength sup ports more than 75 per cent but less than 100 per cent of the crushing load, two additional pipe sections of the same size and classification, manufac tured during the same shift, shall be subjected to the crushing test. The additional lengths may be selected by the inspector, if inspection bv the pur
JOURNAL AWWA
chaser has been specified. The failure of one of these additional specimens to meet the full crushing strength require ment shall be cause for rejection of the entire lot of that size and classification manufactured during the same shift as the test specimen.
If any pipe subjected to the hydro static tests specified in Sec. 5.2.2.2 fails to withstand the pressure specified in Table 4, two additional lengths of the same size and classification, manufac tured during the same shift, shall be subjected to the same hydrostatic test. The additional lengths may be selected by the inspector, if inspection by the purchaser has been specified. The fail ure of one of these additional lengths to withstand the specified pressure shall be cause for rejection of the en tire lot of that size and classification manufactured during the same shift as the test lengths.
Sec. 5.4--Test for Uncombined Calcium Hydroxide
The manufacturer shall perform this test as often as necessary to ensure compliance with the requirements for uncombined calcium hydroxide in Type II pipe.
5.4.1 Reagents. Phenolphthalein indicator. Dissolve 1.0 g of phenolphthalein in 100.0 ml of absolute ethanol.* Glycerol-ethanol solvent. Prepare a solution consisting of glycerol and an hydrous or absolute ethanol,* 1:2 by volume. To each litre of this solution, add 2.0 ml phenolphthalein indicator. Adjust the solvent to slightly basic with either dilute NaOH in absolute ethanol* or standard ammonium ac etate, depending upon the original pH. Strontium nitrate [Sr(N03)2], Standard, ammonium acetate solu tion. Dissolve 16.0 g dry crystalline ammonium acetate in 1 1 of absolute, or anhydrous, ethanol.* Standardize the ammonium acetate solution by titrating against pure CaO that has been freshly prepared by cal cining pure calcium carbonate or cal cium oxalate to constant weight in a platinum crucible at 1650-1830F (900 1 000C). When the calcined CaO has cooled in a desiccator, perform the following op
* Specially denatured alcohol No. 30, 3a, or 2b, of the US Bureau of Internal Rev enue, or alcohol consisting of 95 per cent specially denatured alcohol No. 3a plus 5 per cent isopropanol, may be substituted.
erations in rapid succession. Grind it in an agate mortar. Then weigh out 0.05-0.06 g CaO into a clean, dry 250 ml Erlenmeyer flask and add 60 ml of the glycerol-ethanol solvent and 2.0 g of anhydrous strontium nitrate to the flask. Place a TFE encapsulated mag netic stirring bar into the flask and attach a reflux condenser. Adjust the heating rate and stirring speed to ob tain a vigorous boiling and complete agitation. Titrate the hot solution with standardized ammonium acetate solu tion every 5 min. The endpoint is reached when no further color appears in the solution after 10 min of boiling. Titration is to be carried out only on a hot solution. Good titration proce dure is evidenced by a change to pink color upon cooling.
Step 1. Brush representative pieces of the pipe free of dust and drill with a clean, sharp 0.25-in. carbide-tipped drill inward from the outer surface at a rate of penetration of approximately 1 ipm until the drill point emerges from the inside wall. Catch the drill ings on a dean sheet of glazed paper. Use a soft brush to collect all drillings. Screen through a 20-mesh screen im mediately, and place in a weighing bottle.
Step 2. Place the bottle with top removed into a drying oven at 217F (105C) for 2 hr and then cool to room temperature in a desiccator.
Step 3. Weigh out 1 0.010 g of the dried sample to the nearest 0.001 g and place in a clean, dry 250-ml Erlen meyer flask, to which a TFE-encapsulated stirring bar, 60 ml of the glycerolethanol solvent, and 2.0 g Sr(N03)2 have been added. Attach the flask to a water-cooled condenser (with a stan dard 24/40 glass joint) and place on a hot plate with a magnetic stirrer. Boil the solution gently for 30 min, stirring slowly. Then, remove the flask and filter the mixture, under vacuum, through a Buchner funnel. Bring the filtrate to a boil and titrate to a colorless endpoint with the stan dardized ammonium acetate reagent. Determine the endpoint by comparing with a similar mixture containing no phenolphthalein indicator.
5.4.2 Calculations:
, where
^ WCaO X 1.32 A ^-------
WCaO = the weight in grams of CaO in the standardized ammonium acetate solution
Va~ the volume in millilitres of standardized ammonium acetate used in titration of the solution.
Percentage uncombined Ca(OHi) = ---- X 100 w
where
V = the volume of standardized ammonium acetate solution required by the sample, in millilitres
W = the weight of the sample in grams.
Sec. 5.5--Test Records
The results of all tests shall be re corded and retained for one year, and shall be available to the purchaser at the place of manufacture.
Section 6--Marking and Delivery
Sec. 6.1--Marking
6.1.1 Standard and random lengths. Each standard or random length of pipe shall be clearly marked on the outside surface with the trade name, nominal inside diameter, classification, type, date, and shift of manufacture, and the word "Transmission."
6.1.2 Short lengths. Each short length of pipe shall be clearly marked on the outside surface with the nom inal inside diameter, the classification, the letter T to indicate that it has been hydrostatically tested, and the word "Transmission."
6.1.3 Couplings. All component parts of each coupling shall be clearly marked for use with the pipe for which they are intended. Each coupling shall also be marked with the letter T to indicate that it has been hydrostatically tested.
6.1.4 Special markings. If factory inspection is made by the purchaser or his authorized inspector, each pipe and each coupling shall receive an addi tional special marking of no more than three letters, as specified by the pur chaser.
Sec. 6.2--Preparation for Shipment
E -- the weight in grams of Ca- All pipe and couplings, unless other
(OH)2 per millilitre of standardized wise specified, shall be prepared for
ammonium acetate solution
standard commercial shipment.
AUGUST 1975
C 402-75 467