Heating Ventilating Air Conditioning Guide 1938
Table 4. Heat Loss from Horizontal Tarnished Copper Pipe
Expressed in Btu per linear foot per degree Fahrenheit between the pipe and surrounding still air at 70 F
Nominal Peps Size
(Inches)
x
M i iK \X 2 2X. 3 IX 4 4H 5 6 8
Hot Water (Type K Copper Tube)
Steam (Standard Pipe Sue Pipe)
120 F
150 F
180 F
210 F
1
227.1 F (5 Lb)
297.7 F (50 Lb)
337.9 F (100 Lb)
Temperature Difference
50 F'
0.250 0.340 0.440 0.500 ' 0.580 0.730 0.880 1.040 1.180 1.460
80F
0.287 0.381 0.475 0.559 0.656 0.825 1.000 1.175 1.350 1.500
1.600 1.840 2.400
1.812 2.125 2.685
110 F
0.300 0.409 0.S09 0.618 0.710 0.890 1.091 1.272 1.454 1.635
1.980 2.270 2.910
140 F 1
0.321 0.429 0.536 0.622 0.750 0.957 1.143 1.343 1.535 1.715
2.071 2.430 3.110
157.1 F
0.433 0.533 0.636 0.764 0.904 1.101 1.305 1.560 1.750 1.941 2.131 2.387 2.740 3.310
227.7 F
0.500 0.543 0.746 0.878 1.053 1.273 1.490 1.800 2.020 2.240 2.465 2.770 3.210 4.050
267.9 F
0.530 0.654 0.803 0.934 1.120 1.364 1.605 1.940 2.170 2.430 2.650 2.990 3.440
4.370
linear foot of pipe. Table 5 gives these areas for various standard pipe sizes, and Table 6 for copper tubing, while Table 7 gives the area in square feet for flanges and fittings for various standard pipe sizes.
Very often, when pipes are insulated, flanges and fittings are left bare due to the belief that the losses from these parts are not large. However, the fact that a pair of 8 in, standard flanges having an area of 2.41 sq ft
Table 5. Radiating. Surface per Linear Foot of Pipe
Nominal
, Pipe Sue
(Inches)
"X
Vt,
l
W \x
Surface ` Area (Sq Ft)
0.22 0.275 0.344' 0.435. 0.498
Y Nominal Pipe Size (Inches)
2 2X 3 3^ 4
.
Surface Area (Sq Ft)
0.622 0\753 0.917 1.047 1.178
Nominal Pipe Size (Inches)
5 6 8 10 12
Surface Area (Sq Ft)
1.456 1.734 2.257 2.817 3.338
Table 6: Radiating Surface per Linear Foot of Copper Tubing
(Inches) '
w
Vi.
1
. mix
(Sq Ft)
0.164 0.229 0.295 .. .0.360. 0.426
Tube Size (Inches)
2 2X 3 3X 4
Surface Area (Sq Ft)
0.556 0.687 0.818 0.949 1.080
'
Tube Size (Inches)
5 6. 8
Surface Area (Sq Ft)
1.342 .. 1.604 2.128
722
Chapter 39. Piping and Duct Insulation
Table 7. Areas of Flanged Fittings, Square Feet3
Nominal Pipe Size (Inches)
i
imx
2 2X 3 m 4 iX 5 6. 8` 10 . 12
Flanged Coupling
90 Deg Ell
Long Radiub Rij,
Tee
Cross
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
0.320 0.383 0.477 0.672 0.841
0.945 1.122
1.344 1.474 1.622 1.82 2.41
3.43 4.41
0.438 0.795 1.015 0.892 1.083 1.235 1.575 1.622 2.07 0.510 0.957 1.098 1.084 1.340 lt.481 1.925 1.943 2.53 0.727 1.174 1.332 1.337 1.874 11.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28, 4.28 4.48 6.04 5.83 7.89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97 2.78 5.13 6.99 5.99 7.76 ' 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 5.20 10.18 13.58 12.35 15.60 15.41 20.41 19.58 26.26 6.71 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11
^Including areas of accompanying flanges bolted to the fitting.
would lose, at 100 lb steam pressure, an amount of heat equivalent to more than a ton of coal per year shows the necessity for insulating such surfaces.
HEAT LOSSES FROM INSULATED PIPES
The conductivities of various materials used for insulating steam and hot water pipes are given in Table 8. In this table the conductivities are given as functions of the mean temperatures'or the mean of the inner and outer surface temperatures of the insulations. This method of stating conductivities makes it possible to readily calculate the heat loss through single or compound sections. It should be emphasized that the conduc tivities given in Table 8 for the various insulations are the average of
kTable 8. Conductivities ( ) of Various Types of Insulating Materials
for Medium and. High Temperature Pipes3
Ttprs of Insulating Material*
85 oer cent Magnesia Type Corrugated Asbestos Type.-.............
(4 Plies per 1 in. thick) Corrugated Asbestos Type--.............
(8 Plies per 1 in. thick) Laminated Asbestos Type
(30-40 Laminations per 1 in. thick) Laminated Asbestos Type
(20 Laminations per 1 in. thick) kock Wool IvDe....................... High Temperature Type..........................
(Diatomaceous Earth'and Asbestos) Brown Asbestos Type
(Felted Fibre)
Mean Temperature
100 F 200 F 0.425 0.465 0.530' 0.650
300 F
0.505 0.770
0.480 0.555 0.630
0.360 0.415 0.470
0.545 0.605 0.665
0.350 0.410 0.470 0.515. 0.545 0.575
0.600 0.640' 0.675
400 F
0.550 0.890
0.705
0.525
0.725
0.530 0.605
0.715
500 F
0.590
0.585 0.785 0.590 0.635 0.750
R. H. Heilman. Mechanical Engineering, VoL 46 (1924), p. 593. 723
./