Document 15Gj8LBBe08OgO1Z2rEMjXeMd

25A-3 ELECTRIC LIGHT 1 POWER rtAR 1 9 8 2 CUPPtD BT BACON'S What would you do if a resident in your service territory called- you* irate because she had just discovered her back-yard garden is the site of a. former PCB spill? Baltimore Gas St Electric's Carl Manger solved such a problem by go ing to the house, sitting down in the kitchen and eating a tomato from the garden. Manger's story was part of a panel session at the EPRI PCB seminar de voted exclusively to relating utility experiences with PCB spills. Repre sentatives from four utilities told how they handle spills, analyze and dis pose of contaminated soil, deal with the local press, and soothe property owners. Survey data released at the meet ing by EE I shows that PCB spills are not rare. Each year, on average, 0.09 percent of PCB capacitors, for exam ple, fail in such a way aa to cause a spill. In addition 0.77 percent of PCB capacitors will experience "moder ate" leaks of insulating fluid with at least 50 ppm PCB, and 2.3 percent will develop small leaks each year. For a utility with 10,000 pole-mount ed distribution PCB capacitors, for example, that means there will likely be 9 PCB spills yearly. The utility in dustry has a total of 2.8 million PCB capacitors. That suggests 2500 PCB spills yearly. The EE1 survey also showed that contaminated mineral oil transform ers can have PCB spills (0.007 per cent a year), as well as voltage regu lators (0.024 percent a year), oil-filled circuit breakers (0.008 percent), oilfilled reclosers (0.004 percent), and oil-filled switches and sectionalizers (0.007 percent.) Most problems are caused by ca pacitors, however, which can rupture somewhat violently, spraying PCB liquids over neighboring property, passing cars, houses, etc. Federal regulations require that the spill be cleaned up and all contaminated ma terial removed and disposed in ap proved landfills or incinerators. Lo cal regulations are often strietac One of the immediate problems in a capacitor spill, related LAPWD's 'Earl Morrison, ia to determine the boundaries of the spill, meaning gen erally the radius of soil with 50 ppm PCB or more. Soil samples are taken and sent to a lab for analysis, "We like to take a whole shovelful," Morrison said, smiling, "but that's not right." The top y in. or V* in. should be sam pled, he explained. Results can be back in 2 or 3 hours, he added. Overhead line crews are typically the first utility people on the scene, said the manager. They are trained and equipped to deal with spills. The area is cordoned off and absorbent material is spread to prevent runoff. Visibly contaminated soil is removed and put in drums while lab people sample to find the 50 ppm radius. Visibly contaminated shrubbery ia pruned. Once, Morrison recalled, crews had to get a sod cutterand roll up a lawn-- the soil beneath waa OK. Asphalt poses a tough problem, the manager explained, because the PCB can penetrate deeply. LAPWD policy is to bring in a backhoe and dig up the asphalt for removaL Some problems are almost unsolvable, however. Morrison told how one capacitor rupture- covered the front; porch of a house and the residents,.in. the normal course of entering and leaving the house , tracked PCBs all over the house. "I don't find any place in books where it tells you how to find out if a rug is contaminated," said Morrison. Northeast Utilities's Bill Renfro said his company keeps PCB spill cleanup kits, in 55-gallon drums, in strategic locations throughout the service territory. For large spills the company sends a 4000-gallon capacity tanker truck to drain the PCB con taminated transformer, Renfro add ed. If people are sprayed by a failed capacitor, they are advised to wash immediately and change clothes. Harry Onishi of Commonwealth Edison reported concern on the part of utility workers who maintain PCB contaminated equipment. The utility measured the concentration of PCBs inthe air inthe maintenanceshop and found the level waa less than-1 per cent of the OSHA limit. Several members of the audience asked how the panel members han dled reporting of spills. LADWP's Morrison said oil spills don't have tobe reported to EPA unless the oil con tains more than 10 lb of PCB. BG&E'a Manger said such reporting ia re quired by the federal "superfund" legislation. Regarding public notification. Com Ed's Onishi said that the whole area ia "kind of fuzzy" He said that his com pany's policy is to report a PCB spill to all the people directly affected, but not to local news media. When public questions arise about PCB spills, ad vised Northeast Utilities'a Renfro, the best policy is to answer them forthrightly. If people don't get the answers from you, he added, they'll go to the press or politicians. The panelists advised utility work ersto be ready forunusual situations. For example, a capacitor can fail by opening a seam, spraying PCB liquid into the wind, and contaminating a large area or a distant spot like a backyard across the street. On the PCB spray can hit a passing can the panelists related. When the car can be identified -- a contaminat ed parked car, for example, -- the policy at Northeast Utilities is to wash the surface and notify the own er. If the owner isn't present, the company leaves a form on the car "Von can imagine what kind of re sponse we get to that." said Bill Ren fro. Earl Morrison said policy at Los Angeles is to ask the car owner to bring his car to the company service center and put it on the wash racks used for company vehicles. (He noted that the wash water can't be dis charged to a sewer under California law. It goes to a sump where the or ganic material is separated for dis posal.) BGAE's Manger recalled that one customer's nearly new Datsun 210 was sprayed by a failing PCB capaci tor. When the resident complained, the company bought the car Manger, in turn, bought the car from the com pany and now drives it, with license plate number PCB-l. Several of the panelists noted that there are no comprehensive stan dards or guidelines for cleaning up PCB spills. Procedures have to be de veloped by each company using com mon sense and sensitivity to the deli cate nature of the problem. They seemed to agree that EPA waa gener ally reasonable about utility cleanup practices, but one noted that prob lems can arise--forexample, when an agresaive new EPA inspector locks horns with relatively inexperienced cleanup crew foreman. The foreman, the managers noted, is the key man. He must make a number of on-the- spot judgments and deal with the im mediate reactions. Baltimore G&E's Manger said his company has put together a movie on the utility's PCB spill cleanup prac tices which is available to anyone. He added that a spill cleanup guide is be ing prepared for EPA that may be useful to utilities. One nagging problem mentioned by all the panelists was the difficulty en countered in analyzing samples to de termine what's contaminated and what isn't. All complained about the cumbersome nature and expense of getting accurate laboratory analysis, and the inaccuracy of many of the available methods. Even when PCBs are measured, their source is not necessarily clear. LADWP's Earl Morrison described a case with PCB-spattered deck paint for which a detailed analysis finally showed the paint had 80 ppm of the PCB_ AroclMJ261Lirnntth^ capacitor and an additional 300 ppm Aroclor 1254, a slightly different PCB materi al that was used as a plasticizer in the paint used on the deck. ELECTRIC LIGHT ANO POWER MARCH 1962 PCB-ARCH-EXT0378151