Document 159GJGQdGjgjoVVjLomByaOR5

WATER DISCHARGE TO SEWER AROCLOR DEPARTMENT LOCATION APPROX. AMOUNT SUGGESTED ACTION DISCHARGE TO 1, ill Still Jet ' 20 GFM 1. Use the minimum water to con- New Sump Fit dense the steam. No, I, 2, 3. Run water hot. Reinstall thernio- meters in tails water line to allow operator to adjust. 2. No. 4, No. 5 Jet. a) Adjust water to minimum with rotometer. Eliminate water to one condenser by b) Operating No. 5 jet without the after condenser. Save 7 GPM. Allow Steam to discharge to atmosphere (per '7.E.Voss) 2. <}2 Still Jet 20 GPM Same as #1 above New Sump Pit 3. #3 Still Jet 20 GPM Same as 1 above New Sump Pit 4. U Still Jet 20 GPM Same as #1 above New Sump Pit 5. #5 Still Jet 70 GPM Same as #1 above New Sump Pit 6. Sprinkler Valve 15 GPM Issue MRO to repair water leak. 7. S&K Jets at Blow Tanks (2) 20 GFM Operate with minimum water. Suggest 10 psig and tag valves. New Sump Pit 8. Apoclor 1238 Flaker 2 GPM Issue MRO to repair leak in water lirie at union. Floor-ther to New Sump Pit 9. Aroclor-Cooling Tower Water 30 GPM Miller/E.C. Wright Make up water now tied open. Repair fan it overflow float. Acid Sever 10. Sink in Aroclor Control Room -- Keep water valve closed when not using# Sump Pit 11. Chlorinator Cooling Coils when cooler plugged Shut down & repair cooler Sump Pit 12. Cooling Water on -Pumps Use minimum water. < Sump Pit HONS 09359? WATER DISCHARGE TO SEWER MURIATIC ACID DEPT. .LOCATION APPROX. AMOUNT 1. East Aci.cl Loading Dock .2 West Acid Loading Dock A Gl'M vjLen water Is on 4 GPM SUGGESTED ACTION Keep water valve at sink closed when not using. Same ns above DISCHARGES 'j0 Phosphoric Acid Sewer Phosphoric Acid Sewer 3. Sink at AcicI Plant 7 GPM when water is on .4 Drowning Jets 100 GPM 2 Tici 1(by-pass HCl line from chloTS. f< line from tails tower. These jets arc in series. Enters large jet then to small jet.) Replace bad water valve and keep closed when not using. Issue MRO to relocate pressure gauges in rater line to.downstream side of valves. Also chain operator for valves so that operator'may adjust flow. (If by-pass is not used one jet can handle HC1 from tails tower.) If by-pcss must be used then open weter to second jet. HC1 Sevier HCl Sever 5. SfK Drowning Jet 40 GPM (Fumes from stg. tanks)' Issue M&0 to replace bad water valve, also replace & relocate pressure gauge. Believe this may possibly be cut completely off when not air blowing,(See TSD section for piping alter ation to reduce HCl released when air blowing tank. .6 Acid leak at flang e 10 GFM when Issue >!?.0 to repair leak so under South carbon water is on that water hose can be re tower. . moved. HCl Sever HCl Sever 7. Surge Tank Pump leaking at seal 10 GPM when water is on .8 Proposed Fume 10 GPM Collection System (Long-Range Load ing docks and-st$. tanks. Issue.MR0 to repair leak so that water hose can be re moved . TSD Proposal - Dale' and Etheredge HCl Sewer HCl Sewer 9. Underground Spring 20 + GPM Phos.Acid Sewer Note: City water is metered to acid de pt. 200 (3FM at tine of survey. (20 GPM for acid make water, 1A0 GPU for jets, AO GPM waste.) . HONS 093598 WAREHOUSE b PACKAGING AREA 1, The water from this area now running into sanitary sever is estimated at 100 GPM. It is suggested that this water be piped into return line to cooling tower to save city water. (This is all city water from compressors, biphenyl flaker tank and pumps.) 2. Surface water running off bank, from Aroclor storage tank area, to railroad track at Aroclor loading dock enters a perforated underground pipe, Aroclor from spillage around docks can enter this pipe which drains into neutralisation pit. Viator also enters this underground pipe through two open drains along railroad track. A steel separator tank located west of neutralization pit has been installed to separate solids. MOWS 093599 BIPHENYL DEPARTMENT LOCATION APPROX. AMOUNT Benzene Storage Tank Pump Dost Tank Most surface water also goes to Acid sewer. 2 GPM ' Conversion Sampler 1 GPM . ir1 Decoking Pit Condensate Viator 6 GPM Hydrogen Compressor Cooling Water Tank 5 GPM SUGGESTED ACTION Faulkner Faulkner Faulkner Faulkner Descale compressor to eliminate waste voter. DISCHARGE TO Acid Sower Acid Sewer Acid Sewer Acid Sever Many steer,\ leaks in i?l & v2 Biphenyl still rooms. Cooling -water to sewer when operating. Repair before next Oil? run. HONS 093600 LOCATION 1. Cut oil steam and vatcr W-R PLANT APPROX, AMOUNT 2 GPM SUGGESTED ACTION Faulkner PISCII/.M LJO Flioa. Acid Sever HONS 09360 I I. Loading docks and.storage tanks fume collection system A. Net change - 15 to 25 gprn to acid sewer 100% of the time, plus 120 ppm 15% of the time,- instead of existing flow of 180 gpm 100% of the time. H, The job is being done by J. EtUcrcdgc TSJJ Job #10/(5 K. Hale Premise out by 9-2-70 AFK out by 9-9-70 II. Aroclor Water Recycle A. Reduce flow from 250 gpm to approximately 50 gpm. B. Two water recycle system (4 jets) ' a. Still jet water recycle (1 jet) b. Absorber v?ater recycle (3 jets) C. Job by Jim Mattern Premise in circulation (8-31-70) III. Acid Sewer Revision A. Three choices of operation . Route 11C1 effluent to Aroclor tump. ' b. Install sump in existing acid sewer. c.. Install new acid sewer with sump, B. Job being done by Ktheredge Premise by 9.-7-70 C. This job will also provide a system for keeping spent carbon from the HC1 carbon towers out of the acid sewer. V. Temporary Limestone Pit A* Divert Aroclor containing effluent through temporary pit while cleaning existing limestone pit. B. TSD and Maintenance. C, Start up by 9-11-70. MOWS 093602 VI. Niran Phosphoric Acid Pic Effluent A. Neutralize and divert north, a. Efficient limestone pit to ph 5.2; max. b. NbOH to 5.7 ph. B. Neutralize and divert to 36" storm sewer a. Efficient limestone pit to ph 5.2 max. b. NflOH to ph 5.7. C. Do nothing 1). Send to city sever at Niran E. Divert to a new acid sewer at 5th and Duncan and route to Snow Creek. F. Acetone - Optional Process 1. Cut down Niran residue to incinerator Thereby reducing water flow. G. A. McCarty K. Hale H. 200 gptu flow. MCNS 093603