Document 10YJg4e2oLgxmVxNmE7q6YVdX
Section Number Issue Number Origination Date Revision Date
Ethanolamines/Glycol Ethers
In Plant Training (IPT)
:13 :1.4 :06-25-92 : 12-23-97
Section Test 13 Control Board Ethanolamines Finishing End
Objectives/Answers:
1. State what type cooling tower water should be used on E-241. All fresh water.
2. Explain how the bottoms temperature control scheme works on T-240. Steam to feed ratio
3. State what you would do if T-240 bottoms percent water were .09. Increase the steam to feed ratio.
4. Explain what process variable would cause the pressure on T-240 to raise. State what should be done to correct this problem. T-230 bottoms temperature (tray #4) is too cool, ammonia in T-230 bottoms feed to T-240. Increase T-230 temperature control set point and flush VP-240 with fresh water. Also to much C02 in EO could cause a swing.
5. State the areas you would suspect as the source of water in T-250 overheads. T-240 bottoms, E-251 or E-252 and E-250.
6. State what adjustment you would make if T-250 overheads contained .22% impurities and T-260 overheads contained .20% MEA. Lower the steam/feed ratio point on T-250.
7. State what adjustment you would make if T-250 overheads contained .22% impurities and T-260 overheads contained .39% MEA. Increase the control temperature and steam/feed ratio.
8. Demonstrate how to put T-250 reflux flow on VAX control.
Date Printed: April 18,1998
Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File: T:\ORIGINAL\IPT\SECTTEST\SECTST13.DOC
Page 1 of 2
D0 A 058637
confidential
9. State the set pressure of PSV-T250. 50 pounds per square inch.
10. State the purpose of MEA recycle. To drive the reactor toward more DEA production.
11. State what adjustment you would make if the TEA in T-260 overheads was .03% and the DEA in T-271 overheads was .85%. Increase the feed/steam ratio set point on T-260.
12. State what adjustment you would make if the TEA in T-260 overheads was .20% and the DEA in T-271 was .45%. Lower the feed/steam ratio set point on T-260.
13. State the set pressure on PSV-T260. 50 pounds per square inch.
14. State the set pressure on PSV-T271. 100 pounds per square inch.
15. State the parameters) on T-271 controlled by the VAX computer. None (as of the date of this module)
16. State the set pressure of PSV-E273 A/B. 100 pounds per square inch.
17. State the conditions that need to exist for packing auto ignition. Product saturated packing exposed to air at high temperatures.
Revisions:
Revision No. 1
07-21-93 Yearly review
Revision No. 2
12-02-94 Yearly review
Revision No. 3
12-28-95 Made changes to #2, 3, 4, 6, 7, 11, 12
Revision No. 4
12-23-97 Yearly review
Date Printed: April 18,1998
Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File: T:\ORIGINAL\IPT\SECTTEST\SECTST13.DOC
Page 2 of 2
DO A 058638 CONFIDENTIAL.