CHAPTER 25
1960 Guide
Sound Power Level L* in decibels is ten times the logarithm to the base 10 of the ratio of the sound power to the reference power of 10~u watt. Choice of the reference power is arbi trary, and throughout this text, 10~u watt will be used, as it b convenient in the English system* using square feet, etc. Thus,
Lw - 10 logu TTTTj
(5)
Sound Intensity Level Li in decibels b ten times the loga rithm to the base 10 of the ratio of the sound intensity I to the reference intensity of IQ-18 watt per sq cm (or its equiva lent of 1 picowatt per sq m). Thus
Li = 10 logM ----
(6)
where or
I TM watts per square centimeter
Li (7)
where
Im = watts per square meter.
Sound Pressure Level Lp in decibels b twenty times the logarith m to the base 10 of the ratio of the sound pressure p to the reference sound pressure of 0.0002 microbar, i.e.,
L, - 20 logj*-
(8)
where
p -- sound pressure, microbars (dynes per square centimeter)
Loudness N b the intensive subjective attribute of an audi tory sensation, in terms of which sounds may be ordered on a scale extending from soft to loud. The unit b the sone. The number of solies b directly proportional to the loudness. By definition, a 1000 cps pure tone with a sound pressure level of 40 db has a loudness of 1.0 sone.
Loudness Level (L#) of a sound b numerically equal to the sound pressure level L, of a simple tone of frequency 1000 cps that b judged by the listeners to be equivalent in loud ness. The unit b the phon. In this text, for a 1000 cps tone, Lh in phons is assumed to be related to iV in sones by toe for-
10 of the sound energy incident on an obstruction in an acoustic path to the sound energy that b transmitted through the obstruction. The unit b the decibel.
Noise Reduction b the difference in decibels of the sound pressure levels at two points along an acoustic path in the direction away from the source; alternatively, it b the dif ference in decibels of the sound pressure levels exbting at a single point before and after the addition of acoustic treat ment to the path.
APPARATUS FOR MEASURING SOUND
The measurement of sound or noise b usually accomplished by means of (a) a sound level meter consisting of a micro phone, an amplifier, a variable attenuator, weighting net works, and an indicating meter which reads directly in de cibels, and (6) an octave band analyser which b a set of filters for determining the sound pressure level of the sound being measured in each of eight octave-frequency bands. The approved sound level meter and octave band analyzer should comply with the specifications in the latest version of the American Standard Sound Level Meters for Measurement of Noise and Other Sounds, Z24.3-1944,' and American Standard Specifications for an Octave-Band Filter Set for the Analysis of Noise and Other Sounds, Z24.10-1953, published by the Ameri can Standards Association.
The sound level meter b designed to indicate either the sound pressure level Lw or toe sound level (if weighting net works are used) above toe standard reference level of 0.0002 microbar. The sound level meter itself has three weighting networks, which are approximations to toe equal loudness contours for pure tone sounds of three discrete loudness levels. The equal loudness contours give toe L, of a 1000 cps pure tone that sounds equally as loud to the average listener as the tone whose loudness level b desired.*
Unfortunately, standard sound level meters do not give an indication of the loudness of more complex noises. To serve as a basis for determining the loudness of more complex noises, measurements of complex sounds are taken on the fiat scale (C scale) of the sound level meter using the octave band an alyzer to determine the distribution of the sound pressure level as a function of frequency. Computations of loudness and loudness level are made from these data.
Allowable deviations in response and acceptable tolerances recognized in the standard for the sound level meter are shown in the following tabulation.
Lh - 33 logit N + 40
(9)
This approximation b Amimed valid* for N > 1. Sound Lend at a point in a sound field b the reading in deci bels of a sound level meter constructed and operated in ac cordance with the latest edition of American Standard Sound Level Meters for the Measurement of Noise and Other Sounds* The reading b taken with the proper weighting network switched into the circuit. The use of these networks, called the A, B, and C scales, b discussed later.
Attenuation b ten times the logarithm to toe base 10 of the ratio of the sound intensities at any two points along any continuous acoustic path in the direction away from the source. The unit b toe decibel. For a signal confined to a chan nel or duct, the intensity values are averaged over the crosssection.
Transmission Loss b ten times toe logarithm to the base
Ocfora Sand Nambar
Approprioto Geooetric Metro Frwquanejr ep*
1 40 2 105 3 210 4 425
5 850 6 1700 7 3400 8 6900
Tolerance
db
+1.0, -1.5 0.5 0.5 0.5
1.1 2.1 +4.6, -3.6 +6.0, -5.4
Calibration of the sound level meter and octave band analyser should preferably be made before, during, and after
Sound Control
each use by a calibrated loudspeaker.* In turn, the loudspeaker should be calibrated at the factory at frequent intervals. Instructions and precautions in toe use of sound level meters are given in Reference 2.
approaches to the general problem of noise control
It b usually necessary to think of noise control problems as
composed of three parts: (1) toe source, (2) the path, (3) the
receiver. It b sometimes possible to reduce the noise at any or all of
these parts. However, in construction design, the engineer b
usually able to do something only with the path.
The source may be any piece of equipment or person gener
ating audible noises. The transmission path may be & path
directly through air or may be a path which includes solid
structure such as walls, floors, pipes, duct walls, or air within
ducts in various combinations. The receiver b usually a per
son who might be disturbed by toe noise; however, toe re
ceiver might
be a delicate machine or manufacturing
process that must be isolated from vibration.
The acoustic output of a source b ideally specified by its
total sound power level and the sound power level in each of a
group of frequency bands, preferably octave frequenter bands.
If pure tones are present, a M octave band analysis b prefer
able. Where the source b not confined to a duct or the like, it
may also be necessary to specify the source directivity, i.e., the
relative amount of sound radiating in each direction of inter
est. In general, the specification of the acoustic output of a
source by a
number b not adequate for engineering
design of noise control measures. The sound power outputs of
fans and grilles as noise sources are discussed in later sections.
Acoustic losses along a path from source to receiver nor
mally exist in any building structure. These losses are a func
tion of frequency and can be defined adequately when ex
pressed as losses in each of eight octave bands. Losses for common structures, and for ducts of various sizes and shapes, as well as for some packaged sound attenuation devices, are
published. Some values particularly applicable to ventilating
problems are given in a later section. The response of a person as a receiver has been determined
under certain conditions. Nobe levels which are found ac
ceptable to the average person under specified conditions are
called noise criteria. Several frequently used nobe criteria are summarized in a later section. The noise criteria to be used
must be chosen with regard to toe type of activity to be car
ried on is the space being considered. Where delicate machines
or manufacturing processes are toe receiver, special nobe
criteria must be determined to fit the need. Noise criteria
should best be specified as sound pressure levels in octave
frequency bands. A good procedure for attacking a nobe control problem in a
ventilating system will be illustrated by reference to Fig. 1.
Sound attenuation in the duct b composed of losses in the
unlink and lined portions of the duct, losses at the bend, and
end reflection losses. Added attenuation of the fan nobe is
achieved by adding additional lining to the duct or providing
package attenuation units. Noise b also produced at the grille.
AH losses (attenuation) are expressed in decibels. The pro
cedure follows:
Step 1. Determine the sound power level of the grille nobe either from published data, or from actual measurements, or from approximate data given in the section on Nobe Generated by Grilles.
Step 2. Determine the sound pressure levels in octave bands
347
at a specified listener's position due to grille noise alone which b radiated from the ena of the duct, using the acoustical prop erties of the room and the position of the lbtener (see the fol lowing section on Determination of Room Levels).
Step 3. Determine the allowable sound pressure level in oc tave bands (the criterion) at the listener's position either from
foiblbhcd standard data (see the following section on Criteria
or Noise Control) or from discussions with the architect or the ultimate user of the room under design.
Step 4. Subtract the criterion levels from the sound pressure levels at the listener's position (in decibels) to determine that the levels at least meet the criterion in each octave band. If the grille noise b higher than the criterion in any octave band, a larger grille size must be used.
Note: The total noise in the room b due to both the grille noise and the fan noise. If the grille noise levels just meet the criterion, then the fan noise emitted in the room must be at least 5 db below the criterion. Alternatively, the grille nobe levels and the fan noise levels in the room could each be 3 db below the criterion, because when two noises of the same in-
Rg. 1 .... Typical Ventilation System Problem
tensity are combined, the total level is 3 db higher than either. As a third choice, the fan noise could just meet the criterion, and the grille noise be at least 5 db below the criterion.
Step 5. Obtain the sound power level in octave bands of the fan, either from published data, or from actual measurements, or from approximate formulas given in the following section on Noise Generated by Fans.
Step 6. Determine the existing attenuations in the path, for example, natural duct losses, losses at bends, and reflection losses at the outlet (see the following section on Sound At tenuation in Ducts).
Step 7. Determine the net source power levels by substracting values from Step 6 from Step 5.
Step 8. Determine the sound pressure levels in octave bands at a specified listener's position using as basic data the net source power level from the duct, the acoustical properties of the room, and the position of the lbtener as done in Step 2.
Step 9. Subtract the criterion levels from the sound pres sure levels at the lbtener's position (in decibels) aa done in Step 4 to obtain the required amount of noise reduction NR in each of the eight octave bands (refer again to note following Step 4).
Step 10. Choose an economical means of providing the re quired noise reduction which usually must be obtained by treating the ducts between the source and the receiver either by adding an absorbing lining or by inserting a package unit (see Fig- 1) of known attenuation as a function of frequency. Because noise may be induced by vibration, a consideration of the fan mounting may be necessary. Abo, if the fan room is adjacent to a quiet space, the construction of the fan room walls to provide adequate noise reduction should require atten tion. It is usually good policy to provide slightly more acous tical treatment than is necessary, thus obtaining a safety factor. A safety factor often used is 5 db greater noise reduction ' than would be indicated by the above procedure.
Frequently the controlling noise source in a building with a centre! station system is sound transmission through tne walls