Document 0qYMb5oXLkZZv6L4vXxr2VMgx
PLAINTIFF'S EXHmrr
CT-1260
ANSI A21.4-1974 (AWWA C104-74)
Revision of A21.4--1971 (AWWA C104-71)
AMERICAN NATIONAL STANDARD
for
CEMENT-MORTAR LINING FOR CAST-IRON AND DUCTILE-IRON PIPE
AND FITTINGS FOR WATER
Administrative Secretariat AMERICAN WATER WORKS ASSOCIATION
Co-Secretariats AMERICAN GAS ASSOCIATION NEW ENGLAND WATER WORKS ASSOCIATION
Revised edition approved by American National Standards Institute, Inc., Mar. 7, 1974.
PUBLISHED BY
AMERICAN WATER WORKS ASSOCIATION
6666 West Quincy Avenue, Denver, Colo. 80235
CTD000362
s
American National Standard
An American National Standard implies a consensus of those substantially concerned with its scope and provisions. An American National Standard is intended as a guide to aid the manufacturer, the consumer, and the general public. The existence of an American National Standard does not in any respect preclude anyone, whether he has approved the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standard. American National Standards are subject to periodic review, and users are cautioned to obtain the latest editions. Producers of goods made in conformity with an American National Standard are encouraged to state on their own responsibility in advertising and promotion ma terial or on tags or labels that the goods are produced in conformity with particular American National Standards.
CAUTION NOTICE. This American National Standard may be revised or with drawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five (5) years from the date of publication. Purchasers of American National Stand ards may receive current information on all standards by calling or writing the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018. (212) 868-1220.
L Jr*.
Copyright 1974 by the American Water Worts Assn., Inc. Printed in USA II
CTD000363
Table of Contents
SEC.
Foreword
PACE
I History of Standard........................ II Major Revision ............................... III Options .............................................
v vi vi
Standard
4-1 Scope ............................................... 4-2 Cement ............................................. 4-3 Sand ................................................. 4-4 Water ............................................... 4-5 Mortar .............................................
1 1 1 2 2
SEC.
PACE
4-6 Preparation of Pipe and Fittings for Lining ...................................
4-7 Method of Lining .......... 4-8 Socket ........................................... 4-9 Protection of Work ...................... 4-10 Thickness of Lining ...................... 4-11 Determination of Thickness ......... 4-12 Curing ........................................... 4-13 Lining Quality ............................... 4--14 Seal Coat ........................................
2 2 3 3 3 3 3 3 4
Table
1 Requirements for Sand Tested With Standard Sieves ..............
ill CTD000364
Committee Personnel
Subcommittee 4--Coatings and Linings--which reviewed and developed this revision, had the following personnel at the time of revision :
W. Harry Smith, Chairman Kenneth W. Henderson, Vice-Chairtnan
User Members
Stanley C. Baker Kenneth W. Henderson Raymond C. Holman David A. Lincoln R. E. Morris Jr. Peter E. Pallo Everett C. Rowley
Producer Members
Frank J. Camerota W. D. Goode William U. Maher James H. Sale Edward C. Sears W. Harry Smith Ernest F. Wagner
Standards Committee A21--Cast-Iron Pipe and Fittings--which reviewed and approved this standard, had the following personnel at the time of approval '
Walter Amory, Chairman Carl A. Henrikson, Vice-Chairman
James B. Ramsey, Secretary
Organization Represented
American Gas Association American Society of Civil Engineers American Society of Mechanical Engineers American Society for Testing and Materials American Water Works Association Cast Iron Pipe Research Association
Individual Producers
Manufacturers' Standardization Society of the Valve and Fittings Industry
Xew England Water Works Association Xaval Facilities Engineering Command Underwriters' Laboratories, Inc. Canadian Standards Association
Liaison representative without vote.
IV
Name of Representative
Leonard Orlando Jr. Kenneth W. Henderson James S. Vanick Albert H. Smith Jr. Lloyd W. Weller Carl A. Henrikson Edward C. Sears W. Harry Smith Alfred F. Case William T. Maher
Abraham Fenster Walter Amory Stanley C. Baker Stanley E. Auck W. F. Semenci-iuk*
CTD000365
Foreword
This foreword is for information and is not a part of ANSI A21.4-1974 (A WWA C104-74).
I--History of Standard
The first recorded installation of cement-mortar linings in cast-iron pipe was in 1922 at Charleston, S.C., un der the supervision of J. E. Gibson.
From 1922 to 1929, many installa tions were made under various manu facturers' specifications. In 1929, ASA (now ANSI) Sectional Committee A21 issued a tentative standard for cementmortar linings. This was published as a tentative standard by AWWA in 1932. After many revisions and refine ments, it was finally adopted by ASA in 1939 under the designation A21.4-- Specifications for Cement-Mortar Lin ing for Cast-Iron Pipe and Fittings.
During the period 1940-52, much research was done on various types of cement, methods of manufacture, and methods of curing cement mortar to improve the quality of cement-mortar linings. As a result of this research, a revised edition of the 1939 standard was approved and issued in 1953.
The centrifugal process for lining was further developed during the 1940-52 period to provide the con trols and techniques necessary for as surance of uniformity of thickness throughout the length of a pipe. An other major revision recognized the ability of cure-assist bituminous ma terials to provide controlled curing of the mortar. The use of this method was permitted as a substitute for the moist-curing process.
In 1958, Sectional Committee A21 was reorganized and subcommittees
were established to study each group
of standards in accordance with ASA's
review and revision policy.
Subcommittee 4 (Coatings and Lin
ings for Cast-Iron Pipe) was organ
ized to examine the existing ASA A21.4--1953, "Standard for CementMortar Lining for Cast-Iron Pipe and Fittings." This subcommittee com pleted its study of A21.4--53 and sub mitted a proposed revision to Sectional Committee A21 in 1963. The revised third edition was approved and is sued in 1964.
The 1964 standard reduced the minimum permissible thickness of the lining. This reduction was based on more than 20 years of Cast Iron Pipe Research Association (CIPRA) stud ies of experimental test lines having cement-mortar linings varying from in. to I in. in thickness, on field tests of linings of these thicknesses that had been in service for more than 30 years, and on the assurance of uniformity of thickness afforded by improvements in the centrifugal lining process.
Two thicknesses of lining were made available, and purchasers who required a lining thickness twice the standard thickness had the option of so specify ing.
The cement linings were specified for use in water lines only. This qual ification was made to avoid the use of cement-mortar linings in pipe carrying aggressive liquids, which would react with the lining to produce undesirable
results.
v
CTD000366
VI AMERICAN NATIONAL STANDARD
The purchaser of cement-mortarlined pipe or fittings for use with a water that is corrosive to calcium car bonate, such as a very soft water, is advised, before specifying the omis sion of the seal coat, to satisfy him self by appropriate test that such a lining will not impart objectionable hardness or alkalinity to the water. The procedure outlined in Sec. 4-14.4, modified by the substitution of the wa ter with which the pipe is to be used for distilled water, is suggested as a convenient form of test.
The 1971 revision incorporated a standard test for toxicity of the seal coat material.
This standard does not include pro visions for cement-mortar lining of pipelines in place.
II-- Major Revision
The title of Sec. 4-13 has been changed from Finished Lining to Lin ing Quality, and the entire section has been rewritten to provide new require ments of acceptable lining.
III-- Options
This standard includes certain op tions, which, if desired, must be speci fied. These are:
1. Thickness of lining. Two thick nesses of lining are available, and pur chasers who require a lining thickness twice the standard thickness have the option of so specifying (Sec. 4-10).
2. Seal coat. As other seal coats than bituminous ones are available, this standard makes provision for their use (Sec. 4-14).
CTD000367
ANSI A2I.4-I974 (AWWA C104-74)
Revision of A21.4-1971 (AWWA C104-71)
American National Standard lor
Cement-Mortar Lining for Cast-Iron and Ductile-Iron Pipe
and Fittings for Water
Sec. 4-1--Scope
This standard covers cement-mortar linings specified in the A21 series of ANSI Standards for Cast-Iron and Ductile-Iron Pipe and Fittings for Water and is intended for use as a supplement to those standards.
Sec. 4-2--Cement
The cement shall meet the require ments of "Standard Specifications for Portland Cement," ASTM Designa tion C150-73-a. The analysis and physical test records of each shipment shall be kept for reference for 1 year.
The type of cement selected shall be left to the option of the pipe and fitt ings manufacturer.
4--3.2.2. Sieve tests. The sand shall be tested with standard sieves, as defined in ASTM Designation Ell-70, "Standard Specification for Wire-Cloth Sieves for Testing Pur poses," and shall meet the require ments listed in Table 1. One sieve analysis shall be performed on each carload of sand delivered. For sand delivered by other means, one sieve analysis shall be made for each 50 tons.
4-3.2.3. Colorimetric test. The test
for impurities shall be in accordance with ASTM C40-73, "Standard
Method of Test for Organic Impuri
ties in Sands for Concrete."
Sec. 4-3--Sand
4-3.1. Type of sand. The sand shall be well graded, from fine to coarse, and consist of inert granular material having hard, strong, durable, uncoated grains and meet the test re quirements of Sec. 4--3.2.
4--3.2. Testing of sand. The sand shall be tested in accordance with the requirements of these sections:
4--3.2.1. Sampling. The sand to be tested shall be sampled according to Sections 14 and 15 of ASTM D75-71, "Standard Methods of Sampling Ag gregates."
TABLE 1
Requirements for Sand Tested With Standard Sieves
Min. Thickness of Lining
in.
Sieve Requirement*
100 Per Cent of 75 Per Cent of
Sand Shall Pass Sand Shall Pass
(Sieve No.)
(Sieve No.)
T6 12
32 12
i 12
TT 8
46
20 16 t t t
* Not more than 10 per cent, by weight, of any sand shall pass through sieve No. 100.
t Not applicable.
1
CTD000368
2 AMERICAN NATIONAL STANDARD
Under this test, the sand shall not produce a color darker than required in the standard. The sand shall be ac ceptable, however, if it is shown by adequate test that the impurities caus ing the color are not harmful to the strength or other specified properties of the finished lining.
The colorimetric tests of sand from an established source of supply shall be made once each 6 months. For sand from a new source, these tests shall be made not less than once a month for a period of 6 months.
4--3.2.4. Decantation test. The sand shall be tested according to ASTM Cl 17-69, "Standard Method of Test for Materials Finer Than No. 200 (75-/xm) Sieve in Mineral Aggregates by Washing."
At the option of the manufacturer, the clay content and sand grain fine ness may be determined by using the American Foundrymen's Society pro cedure, described in the Foundry Sand Handbook, Seventh Edition, Section 5. By this latter method, the total percentage finer than No, 200 sieve, as defined in ASTM Designation Cl 19-- 71, is equal to the AFS percentage of clay plus the percentage passing through the No. 200 sieve.
No more than 2 per cent shall be lost in the decantation test.
The decantation tests of sand from an established source of supply shall be made once each 6 months. For sand from a new source, these tests shall be made not less than once a month for a period of 6 months.
4--3.2.5. Test records. The require ments of Sec. 4--3.2.2, 4-3.2.3, and 4--3.2.4 shall be met, and the records shall be filed for reference for 1 year.
Sec. 4-4--Water
The water used for tempering the mortar shall meet the requirements of
the United States Public Health Serv ice Drinking Water Standards 1962.
Sec. 4-5--Mortar
Mortar for the lining shall be com posed of cement, sand, and water. The mortar shall be well mixed and of proper consistency to produce a dense, homogeneous lining that will adhere firmly to the pipe or fitting surface. Admixtures may be used, provided the linings meet all the requirements of this standard. The cement mortar shall contain not less than one part of cement to two parts of sand, by volume.
Sec. 4-6--Preparation of Pipe and Fittings for Lining
The surface to be lined shall be free from foreign material, which would adversely affect the lining adhesion or cause inclusions, blisters, or voids in the lining. The surface shall be free from projections of iron which may protrude through the lining.
Sec. 4-7--Method of Lining
4-7.1. Lining of pipe and fittings. Pipe shall be lined by the centrifugal process. Fittings shall be lined by a process that will produce linings meet ing the requirements of this standard.
4--7.2. Mortar. The waterway sur faces of pipe and fittings shall be com pletely covered with the specified mor tar. The mortar shall be entirely free from holidays or visible bubbles of air and shall be thoroughly compacted throughout. The consistency of the mortar and the time and speed of spinning of the pipe shall be so ad justed as to minimize the segregation of the sand from the cement and to deliver the finished lining substantially free of laitance.
4-7.3. Repair of defective or dam aged areas of linings. Defective or
CTD000369
CEMENT-MORTAR LININGS
3
damaged areas of linings may be patched by cutting out the defective or damaged lining to the metal so that the edges of the lining not removed are perpendicular or slightly undercut. A stiff mortar shall be prepared in ac cordance with Sec. 4-5. The cut-out area and the adjoining lining shall be thoroughly wetted, and the mortar ap plied and troweled smooth with the adjoining lining. After any surface water has evaporated, but while the patch is still moist, it shall be cured as specified in Sec. 4-12.
Sec. 4-8--Socket
The socket shall be free of mortar.
Sec. 4-9--Protection of Work
The lined pipe and fittings shall be protected from extreme heat due to direct rays of the sun, from impact of rainfall, and from freezing tem peratures until the linings have cured sufficiently to withstand these condi tions.
Sec. 4-10--Thickness of Lining
4-10.1. Standard thickness. The thickness of linings for pipe and fit tings, as determined in Sec. 4-11, shall be not less than iV in. for 3-12 in. pipe, in. for 14--24 in. pipe, and in. for 30-54 in. pipe.
4--10.2. Double thickness. Linings with thicknesses twice those specified in Sec. 4-10.1 shall be furnished if specified by the purchaser.
4-10.3. Taper of linings. Lining thickness may taper to less than the specified minimum thickness at the ends of the pipe or fitting. The length of the taper shall be as short as practi cable and shall not exceed 2 in.
4--10.4. Permitted tolerances. A thickness tolerance of t| in. shall be permitted on pipe and + in. on fittings.
Sec. 4-11--Determination of Thickness
Lining thickness shall be determined at intervals frequent enough to assure compliance. Thickness of lining may be determined by means of spear mea surement, with a hardened-steel point not larger than iV in. in diameter. The inspector shall pierce the lining immediately after it is placed in the pipe or fitting and before the mortar has set. The lining shall be pierced at four equidistant points on two cross sections of the barrel at each end of the pipe or fitting. The first set shall be not more than 4 in. from the re spective ends of the pipe or fitting. The second set shall be made as far into the interior of the pipe or fitting as can be readily reached without injuring the lining.
Sec. 4-12--Curing
The lining shall be cured in such a manner as to produce a properly hy drated mortar lining that is hard and durable and will otherwise meet the requirements of Sec. 4-13. The cure may be effected by the application of a seal coat to the still-moist lining.
Sec. 4-13--Lining Quality
The lining shall be free from voids, ridges, or corrugations that reduce the thickness of lining to less than the specified thickness.
Unbonded areas of cement lining in a pipe or fitting are acceptable if the dimension of any single area does not exceed the nominal diameter in the cir cumferential direction and in longitudi nal direction does not exceed the nom inal diameter or 12 in., whichever is greater.
Longitudinal cracks less than 9 ;n. in length or less than the nominal diam eter, whichever is greater, are accept
CTD000370
4 AMERICAN NATIONAL STANDARD
able. Circumferential cracks of any length are acceptable. Surface crazing is acceptable.
Repair of any unacceptable condition is permitted in the field, in accordance with Sec. 4--7.3.
Sec. 4-14--Seal Coat
4--14.1. General. Unless otherwise specified, the cement lining shall be given a seal coat of bituminous ma terial. Other seal coat materials may be used, but they shall be agreed upon at the time of purchase and shall be specified on the purchase order.
4--14.2. Seal coat characteristics. The seal coat shall be continuous and shall adhere to the mortar lining at all points. The seal coat, after drying for at least 48 hr, shall have no deleterious effect upon the quality, color, taste, or odor of potable water.
4--14.3. Limit of toxic substances. 4--14.3.1. Requirements. The seal coat material shall not yield chloro form-soluble extractives, corrected for zinc extractives as zinc oleate, in ex cess of 18 mg per sq in. of surface exposed or of 50 ppm by weight of the water capacity of the test container. 4--14.3.2. Frequency of test. The seal coat material shall be tested at suf ficiently frequent intervals to deter mine that it meets the requirements prescribed in Sec. 4--14.3.1. 4--14.3.3. Method of testing. The procedure used in the determination of the amount of toxic substances shall be in accordance with the FDA "Method of Testing for Toxicity of Coating Material Intended for Use in Transporting or Holding Food or Pot able Water,'' as described in Food Ad ditives Amendment and Code of Fed eral Regulations, pp. 13.0 through 13.8, April 16, 1963, Food and Drug
Administration, US Department of Health, Education and Welfare. The seal coat material shall be extracted with distilled or demineralized water at 120F for 24 hr.
4-14.4. Leaching resistance. 4--14.4.1. Requirements. The sealcoated pipe shall impart to the water during any 24-hr test period no more than 25 ppm of hardness or 25 ppm of total alkalinity, and shall impart no caustic alkalinity. 4-14.4.2. Frequency of test and records. Leaching tests shall be made at sufficiently frequent intervals to as sure compliance. The results of one test each month shall be filed for reference for 1 year. 4-14.4.3. Method of testing. The seal-coated pipe shall be tested as follows: The test specimen shall be at least 6 in. in length, either cut or isolated by suitable closure pieces. When a cut section is used, it shall be bedded on end in a shallow pan of molten paraf fin. After the paraffin has cooled, the cut section shall be filled nearly to the top with distilled or demineralized wa ter at laboratory temperature. The top shall be covered with a glass plate and sealed with petroleum jelly. If an iso lated section is used, it shall be filled through a tap in the closure device with distilled or demineralized water at laboratory temperature. In either case, the water in the specimen shall be changed and tested after 24-hr contact on each of 3 suc cessive days. The methods and pro cedures used in the determination of hardness and alkalinity shall be those prescribed in Standard Methods for the Examination of Water and Wastezvater, APHA, AWWA, and WPCF.
thirteenth edition, 1971.
CTD000371
:ij--io.M--
CTD000372