Document 0qRBkmvd53r3kjogxQ1BYRM3J
212
CHAPTER 10
1953 Guide
covered on the outside with materials highly resistant to water vapor such as paint or roll roofing, the winter season is a time of moisture accumulation in the cold outer elements and their safe moisture holding capacity is an important factor in determining the barrier requirement. A house without sheathing requires a better barrier; and a prefabricated design with only a sheet of metal outside of insulation requires very high barrier resistance. The interior vapor pressure and the length and severity of the winter are also important.
, For typical frame dwellings with wood sheathing and siding in the north ern United States, a barrier permeance of one perm or leSs has been found satisfactory. There are cases, however, in residential construction where a one perm barrier would not be adequate and there are also many industrial applications in which a very much higher vapor resistance is required. In any event, the choice of an adequate barrier implies that its permeance be definitely established. The usually accepted test procedure for this pur pose is a dry method at a temperature of 70 F to 80 F. If obtainable at reasonable cost (including good application), a barrier better than required should be chosen for any construction. Despite the theoretical possibility of safely discharging some vapor through a wall, a higher than minimum permeance is not prefen-ed.
An exact statement showing which buildings require a vapor barrier is not readily formulated. However, in view of the distressing results its omission may bring, it is tentatively recommended that the walls of every well constructed modem dwelling include a vapor barrier when the con struction includes any material that would be damaged by moisture or its freezing. This applies to all'condensation zones when the U value for the wall is lower than 0.25 Btu per (sq ft) (hr) (F deg), and it applies in zone I and zone II to walls of higher transmittance.
In applying vapor resistance to a wall, there are certain fundamental principles which should be followed. First, the vapor barrier should be placed as near to the warm surface of the wall as practicable. Second, it should be continuous with no direct openings through the barrier. Good workmanship and application are very important. Workmanship that leaves two openings through the barrier, or around its margin, at different levels, connecting air spaces at only slightly different temperatures, leaves a path for thermosyphon air rotation which will transport large amounts of water vapor from the warmer space to the colder. If a membrane barrier is used back of the plaster or interior finish, its joints should be made over some solid framing member, and not between the studs or in similar places. Usually a two-inch lap over a framing member will make a sufficiently tight joint when the interior finish is applied. . Such a lap, however, without backing would not be adequate. Barriers attached to the warm side of insulation should form a continuous unbroken membrane over the entire insulated area. Edges should be lapped over framing members; ends of strips should be fastened by lapping over plates or headers. All openings for electrical fixtures and joints around window and door casings should be carefully sealed. Holes accidentally made in the barrier should be sealed.
. 2. Ventilation of Living Space. The second measure listed for the control of concealed condensation is ventilation of the house. This measure is obviously necessary as an accompaniment.to a vapor barrier since, if the barrier blocks entrance into the walls, the water vapor must be removed by other means. No great volume of air change is necessary, however, and normal infiltration alone is frequently all that is required in winter weather.
' The effectiveness of ventilation is shown in Fig. 5, which also shows tho
- Water Vapor and Condensation in Building'Construction
213
. email amount of water vapor escaping into the barrier-equipped; well-in sulated walls and ceilings (2000 sq ft) of a typical small dwelling, the floor, being neglected. Evidently, ventilation of 2000 cu ft per hr will remove 21 lbs of vapor per day with the relative humidity at 40 percent, ,while at the same time 1.5 lbs escapes into the structure. The total vapor production (22.5 lb) is a typical amount. Double glass will be barely safe from visible condensation as will be seen in Fig. 1. By reference to Chapter 6; 2000 cu ft per hr appears to be near the minimum for odor control, and ventilation would have to be higher when cooking is done. By reference. to Chapter 11, it appears that usual infiltration will normally supply' the. necessary air change, but that supplementary ventilation may be neces sary in kitchen and iaundry for proper vapor control and for the reduc tion of peaks in relative humidity which would otherwise occur in those,
areas. 3. Ventilation of Structure. The third measure listed for the control oh
concealed condensation, ventilation of the structure itself, is effective in
Fig. 5. Water Vapor Balance in a Dwelling
(Vapor Barrier, 1 perm; Wall and Ceiling Area 2000 sq ft Insulated)
certain cases especially as a supplement to warm side vapor resistance which is considerable but not of itself fully adequate. Air from outside is used. The vents must be shielded from the entrance of rain and insects.
Attics and crawl spaces may be considered as parts.of the structure, and for these portions ventilation is practically a necessity. Attic ventilation has long been an established practice but its effectiveness is likely to be diminished by the newer practice of adding insulation to ceilings. In sulation requires added ventilation which in turn necessitates adequate insulation. The recommended ventilation shown in Table 3 for dwellings5 is based on such insulation. The net area refers to the total of all openings free from obstructions. The use of louvers and 8-mesh screen (usually, recommended) requires a gross area 2.25 times that listed. In Zone I, a ceiling vapor barrier is recommended for all constructions. It is also neces sary that stray openings from walls into the attic, or around a loose fitting attic door be avoided. The stack effect allows a large inflow of warm air from the dwelling, transporting much vapor to a danger area. More de-. sirable ventilation of the house can be arranged.
Crawl spaces under dwellings where the earth is damp and uncovered require a high rate of ventilation. At least four openings, one at each