Document 0q87pyz5039LgGJ7pEQ0pJ5Kn
428
CHAPTER 30
1959 Guide
Step V. Design S'ami Area
Divide the room heat toes found in Step 1 by the design panel output found in Step 8.
Room
A B C
Design Panel Area (A,) Sq ft
132 (Unchanged from Step 2) 77 242
Step 10. Total Panel Output
Add the beat flow upward (?.) to the design panel outpnt (g*) and multiply by tne design panel area to obtain the total panel output. If the design panel output is different from the panel output (ft) used in Steps 3 and 4, the heat flow upward (?) ahoufd be redetermined.
Room
9-
Total
9*
9* + 9* A,
Panel Output A,(9* + q<)
Btu/hr
A 12.5 47.7 B 9.6t 32.5 C 5.5f 33.0
t redetermined
60.2 42.0 38.5
132 77 242
7946 3234 9317
Step It. Fluid Circuit Design the fluid circuit (panel piping and mains) for a tem
perature drop of 10 to 20 F deg between the water inlet and outlet of the panel (see Chapter 28, Hot Water Heating Sys tems).
Step IB. Boiler Site
Size the boiler according to method contained in Chapter 35, Heating Boilers, Furnaces, and Space Heaters. The net Btu rating of the boiler should equal or exceed the total out put of all panels plus any other loads on the boiler.
Procedure for Metal Ceiling Panels11
Follow the procedure for Hot Water Plaster Ceiling Panels.
Procedure for Concrete Ceiling Panels1*
Concrete ceiling panels are distinguished from concrete floor panels in intermediate floors by the position of the tubes in the concrete slabs (see Tables 2 and 3). Both types of panels have heat outputs in both directions in amounts determined by the thermal resistances and the temperature differences in the two directions. The effect of both outputs on heating requirements of the spaces and the comfort of the occupants should always be considered. (See section on Procedure for Concrete Floor Panels--Intermediate Slab.)
The procedure for hot water plaster ceiling panels cannot be applied in its entirety to concrete ceiling panels because some of the simplifying assumptions regarding the upward heat flow from plaster panels are not valid for concrete panels. The necessary modification of the plaster ceiling panel procedure is as follows:
Step 1. Heat Loss
Follow the procedure for Plaster Ceiling Panels, Step 1.
Step f. Required Panel Output Follow the procedure for Plaster Ceiling Panels, Step 2.
(able 1.... thermo) Resistance ot Concrete ceiling Faneis
Panel Construction
Tberaof Rndftanoe (F d*g)(q ff) (hr) per Sto
*/j taSMCII ' / I MNEI |\
covtwS t
6-m. Concrete Slob--1-in. cover
Heat Row Ratio aufqi
In. 0
0.5" 1.0"
UP down P dawn up dawn
r- U r rt
in. (nom.) nonferrous tube
9 3.6 0.30 0.9 0.35 0.7 0.45 12 5.1 0.35 1.1 0.45 0.9 0.55
}-in. (nom.) ferrous pipe or H*iQ- (nom.) nonferreus tube
9 2.6 0.25 0.7 0.30 0.6 0.35 12 4.C 0.30 0.9 0.40 0.8 0.50
H-in. (nom.) ferrous pipe or 1-in. (nom.) nonferrous tube
9 2.1 0.20 0.6 0.25 0.6 0.30 12 3.3 0.30 0.8 0.35 0.7 0.40 15 4.5 0.35 1.0 0.45 0.8 0.55
1-in. (nom.) ferrous pipe
9 1.6 0.20 0.5 0.25 0.5 0.25 12 2.6 0.25 0.7 0.30 0.6 0.35 .15 3.6 0.30 0.9 0:40 0.7 0.45
6-m. Concrete Slab--I-m. Cover
H-in. (nom.) nonferrous tube
(nom.) ferrous pipe or %-in. (nom.) nonferrous tube
9 3.6 0.30 1.0 0.35 0.8 0.40 12 5.2 0.35 1.2 0.45 1.0 0.55
9 2.9 0.25 0.9 0.30 0.8 0.35 12 4.0 0.30 i.i 0.40 [0.9 0.45
Ji-in. (nom.) ferrous pipe or 1-in. (nom.) nonferrous tube
9 2.2 0.20 0.8 0.30 0.7 0.30 12 3.3 0.30 1.0 0.35 0.8 0.40 15 4.3 0.35 1.1 0.40 0.9 0.50
1-in. (nom.) ferrous pipe
9 1.7 0.20 0.7 0.25 0.7 0.25 12 2.7 0.25 0.9 0.30 0.8 0.35 15 3.7 0.30 1.0 0.40 0.9 0.45
* Any railing pane) tlao nete a* Boor panel to the extent of it* upward beat flow. If the upward beat Bow ta high and the apace above is occupied, check floor eurfaoe temperature tea poeaible foot diacomlort (eee Reference 7). Atao check effect on heating requirement* of the apace above. It ia not sood practice to have the major portion of the upper room'* heetinc requirements supplied by the upward heat flow of a cmlinf panel below.
Step S. Panel Surface Temperature Follow the procedure for Piaster Ceiling Panels, Step 3.
Step 4- Upward Heat Flow Estimate
a. If the upper surface of the slab is exposed to form a floor, find the heat flow upward from Fig. 16, using the panel surface temperature (t,) found in Step 3, and the air tempera ture of the space above.
b. If the upper surface of the slab is not exposed, use the equation:
9. - C,(t - t,)
(10)
Panel Heating
Table 3 .... Thermat 'Resistance of Bare Concrete Floor Panels
SpocPanel Construction
thermal Re&jfonce IF deglUq Mhri/Bht Hoot Row Ratio WW ** <1m/qe*
4-in. Concrete Stab--2-in. Cover
1 3 5 )0
-i-- up
up
r,, te r,, *it r ti. fat Tit
(nom.) nonferrous tube
9 0.57 0.52 0.46 0.84 0.43 1.17 0.42 1.97 12 0.73 0.68 0.58 1.16 0.54 1.65 0.51 2.86
H-in. (nom.) ferrous pipe or $$-in. (nom.) nonferrous tube
9 0.49 0.42 0.41 0.66 0.39 0.90 0.38 1.80 12 0.63 0.55 0.50 0.93 0.48 1.30 0.46 2.35
6-fc. Concrete Slob 2-in. Cover
%-in. (doid.) nonferrous tube
9 0.59 0.70 0.47 1.05 0.45 1.39 0.43 2.25 12 0.78 0.90 0.60 1.40 0.56 1-97 0.54 3.21
%-in. (nom.) nonferrous tube
9 0.51 0-61 0.43 0.87 0.41 1.13 0.40 1.78 12 0.68 0.78 0.54 1.23 0.51 1.63 0.49 2.61
K-in- (nom.) ferrous pipe
9 0.47 0.55 0.40 0.77 0.39 0.98 0.38 1.50 12 0.63 0.71 0.50 1.07 0.48 1.44 0.46 2.36
1-in. (nom.) nonferrous tube or 1-in. (nom.) fer rous pipe
12 0.59 0.66 0.48 0.98 0.46 1.30 0.45 2.11 15 0.73 0.83 0.57 1.21 0.54 1.73 0.61 2.74
Step 6. Upward and Downward Panel Resistance
Follow the procedure for Plaster Panels, Step 5, using Table 2 to find both resistances (ru and r*).
Step 6. Mean Water Temperature-and Upward Heat Flow
a. Follow the procedure for Plaster Panels, Step 6.
b. Find the heat flow upward from the panel (9*) from Fig. 16. Add to the thermal resistance of the slab to upward heat flow (r,,), the resistance to beat flow (rM) of any material between the upper surface of the slab and the space above to obtain the resistance (r,) to be used in Fig. 16. The mean 'water temperature ((*) found and the air temperature of the space above the panel are the other two factors to be used.
Step 7.-Design Mean Water Temperature
Select the highest mean water temperature (() as the de sign mean water temperature (<*)-
Step 8. Design Panel Output
Follow the procedure for Plaster Panels, Step 8.
Step 9. Design Panel Area
Follow the procedure for Plaster Panels, Step 9.
429
Step 10. Total Panel Output Follow the procedure for Plaster Panels, Step 10.
Step 11. Fluid Circuit Follow the procedure for Plaster Panels, Step 11.
Step IB. Boiler Size Follow the procedure for Plaster Panels, Step 12.
Procedure for Plaster Wall Panels
A datagn graph has not been prepared for wall panels but a design can be approximated using the equations of heat transfer from walls together with the thermal resistance properties of plaster wilingn from Table 2. The procedure for Plaster Ceiling Panels is used as a guide.
Step 1. Heat Loss Follow the procedure for Plaster Ceiling Panels, Step 1.
Step B. Required Panel Output Follow the procedure for Plaster Ceiling Panels, Step 2.
Step 5. Panel Surface Temperature
AuminriA a trial panel surface temperature and determine the resulting heat output from Figs. 9 and 10 as explained in the accompanying sectioo of the test. (Additional neat flow due to the infiltration can be estimated from Fig. 12, if de sired.) Aftnmg successive trial panel surface temperatures until the temperature is found at which the combined heat transfer from the panel equals the output determined in Step
2.
Step 4. Reverse-Side Heat Flow Follow the procedure for Plaster Ceiling Panels, Step 4.
Step S. Panel Resistance Follow the procedure for Plaster Ceiling Panels, Step 5.
Step 6. Mean Water Temperature
For the required panel output found in Step 2, the panel resistance found in Step 5, and the room air temperature, calculate the required mean water temperature as follows:
- t, + r<(q<)
(II)
Step 7. Design Mean Water Temperature Follow the procedure for Plaster Ceiling Panels, Step 7.
Step 8. Design Panel Output
From equations, Step 6, and Figs. 9 and 10 find the panel output for design mean water temperature by successive trials.
Step 9. Design Panel Area Follow the procedure for Plaster Ceiling Panels, Step 9.
Step 10. Total Panel Output Follow the procedure for Plaster Ceiling Panels, Step 10.
Step 11. Fluid Circuit Follow the procedure for Plaster Ceiling Panels, Step 11.
Step IB. Boiler Size Follow the procedure for Plaster Ceiling Panels, Step 12.
Procedure for Hot Water Concrete Floor Panels (Slab-On-Grade)u
The procedure for designing a concrete floor panel (slabon-grade) will be illustrated by Example B.
Example B: Three rooms. A, B, and C, are to have a com mon water supply temperature; that is, they represent a single sone. They are to be maintained at 72 F air temperature