Document 0gGYz2nBbjapJpZjM7jBDDKKm

HEATINC VENTILATING AIR CONDITIONING GUIDE 1943 Table 1. Conductances (C) for Surfaces and Air Spaces All conductance values expressed in Btu per hour per 'square foot per degree Fahrenheit temperature difference. Section A. Surface Conductances for Still Aira__________ Position of Surface of Heat Flow Surface Emissivity e - 0.83 e = 0.05 Horizontal___ --................ -- Vertical...................................-........................ Upward Downward 1.95 1.21 1.52* 1.16 0.44 0.74 Section B. Conductance of Vertical Spaces at Various Mean Temperaturesb Temp Dbg Fahr Conductances of Ant Spaces for Various Widths in Inches 0-128 . 0.250 0.364 0-493 0.713 1.00 1.500 20 2.300 1.370 1.180 1.100 1.040 1.030 1.022 30 2.385 1.425 1.234 1.148 1.080 1.070 1.065 40 2.470 1.480 1.288 1.193 1.125 1.112 1.105 50 2.560 1.535 1.340 1.242 1.168 1.152 1.149 60 2.650 1.590 1.390 1.295 1.210 1.195 1.188 70 2.730 1.648 1.440 1.340 1.250 1.240 - 1.228 80 2.819 1.702 1.492 1.390 1.295 1.280 1.270 90 2.908 1.757 1.547 1.433 1.340 1.320 1.310 100 2.990 1.813 1.600 1.486 1.380 1.362 1.350 110 3.078 1.870 1.650 \ 1.534 1.425 1.402 1.392 120 3.167 1.928 1.700 1.580 1.467 1.445 1.435 130 3.250 1.980 1.750 1.630 1.510 1.485 1.475 140 3.340 2.035 1.800 1.680 1.550 1.530 1.519 150 3.425 2.090 1.852 1.728 1.592 1.569 1.559 Section C. Conductances and Resistances of Air Spaces Faced with Reflective Insulations_____________ Location and Position of AtR Space Direction of Heat Flow Temp3* Diff Deg Fahr Winter Summer Conductance* (O No. of Air Spaces 123 Resistance* (*) No. of Air Spaces 123 Rafter Space Horizontal Horizontal Horizontal Horizontal 30 deg slope 30 deg slope 30 deg slope 30 deg slope Down Up Down Up Down Up Down Up 45 45 45 45 25 25 25 25 0.10 0.27 0.09 0.24 0.15 0.25 0.13 0.23 0.07 0.17 0.06 0.16 0.10 0.17 0.09 0.14. 10.00 3.70 11.11 4.17 6.67 4.00 7.69 4.35 14.29 5.88 16.67 6.25 10.00 5.88 11.11 7.14 Stud Space (3H in ) Vertical/ Vertical r 30 0.34 v 2.94 40 0.23 0.13 4.35 7.69 Vertical 15 0.32 3.13 20 0.18 0.11 5.56 9.09 Vertical* 30 0.46 2.17 Radiation and Convection from Surfaces in Various Positions, by G. B. Wilkes and C. M. F. Peterson (A.S.H.V.E. Transactions. Vol. 44, 1938. p. 513). bA.S.H.V.E. Research Report No. 825--Thermal Resistance of Air Spaces, by F. B. Rowley and A. B. Algren (A.S.H.V.E. Transactions. Vol. 35, 1929. p. 165). ... , cThermal Test Coefficients of Aluminum Insulation for Buildings, by G. B. Wilkes, F. G. Hechler and E. R. Queer (A.S.H.V.E. Transactions, Vol. 46, 1940). ^Temperature difference is based on total space between plaster base and sheathing, flooring or roofing. These air space conductance and resistance values are based on one reflective surface (aluminum) having an emissivity of 0.05 facing each space and are based on total space between plaster base and sheath ing, flooring or roofing. The rafter and stud spaces are divided into equal spaces. /Stud space is lined on plaster base side with loose paper with aluminum on surface facing-air space.; The resistance of the small air space between the piaster base and paper was 0.43. Radiation and Convection Across Air Spaces in Frame Construction, by G. B. Wilkes and C. M. F. Peterson (A.S.H.V.E. Transactions, Vol. 43. 1937, p. 351). *The recommended surface conductance for calculating heat losses for still air for non-reflective surfaces is 1.65 Btu. For a 15 mph wind velocity, the recommended value is 6.0 Btu. These coefficients were derived from Fig. 1 which was based on tests conducted at the University of Minnesota, and apply to vertical surfaces. 92 CHAPTER 4. HEAT TRANSMISSION COEFFICIENTS resulted in comparable values. For 3% in. horizontal air spaces having an effective emissivity of 0.83, the conductance for heat flow upward was 1.32 and for heat flow downward, 0.94. The conductance for a similar vertical air space was 1.17, the resistances of course being the reciprocals of these values in each case. A large part of the heat transferred across air spaces bounded by ordi nary materials is by radiation. Therefore, if such air spaces are faced with metallic surfaces such as aluminum foil, coated sheet steel or other low-emissivity, infra-red reflective metal surfaces, the radiant heat trans fer will be substantially reduced, thus causing the major portion of the remaining transmitted heat to be by convection. Table 1, Section C, gives conductances and resistances for air spaces bounded by one reflec tive surface having an emissivity of 0.05. It will be noted that the con ductance values given in this table are a function of the temperature differences across the space rather than mean temperature, the larger the temperature difference, the larger the conductance. The radiant heat transfer is the same regardless of whether the low emissivity surface is on the high or low temperature surface of the space, and is independent of the width of the. space. To minimize the convection transfer the vertical air space should be at least % in. in width. A conductance of 0.46 was used for computing the over-all coefficients in Tables 3 to 12 inclusive for air spaces bounded by aluminum foil applied to plasterboard. When referring to reflective heat-insulating surfaces, the term brightness which deals with visible light has no specific meaning and should be avoided3. Emissivity and reflectivity definitely define the radiating and reflecting properties and values may be determined directly for long wave length radiation corresponding to room temperature. As previously stated, the values in Table 1, Section C, are based on an emissivity of the reflective surface of 0.05. Obviously for higher emissivity values the conductances will increase accordingly. For example, non-metallic reflec tive materials are available having emissivity values approximately midway between those of metallic reflective insulations and ordinary building material surfaces. These materials will have a correspondingly higher radiant heat transfer and where such materials are under con sideration, due allowance should be made for the higher emissivity value in arriving at the proper air space conductance. Where reflective insulating materials are involved the possible increase in the emissivity coefficient due to surface coatings or chemical action* should be studied by the engineer in order to satisfy himself as to the permanence of the reflective surface for the conditions under which this material will be used. In making installations of this material the par titions between air spaces should be tight, particularly at the top and bottom so that air cannot circulate between adjacent spaces. When reflective insulating materials are installed with multiple air spaces, the position (vertical, horizontal or inclined) of the material in the structure must be taken into consideration. For example, the resistance to heat flow upward is about one-third that of downward flow in a hori- Some Reflection and Radiation Characteristics of Aluminum, by C. S. Taylor and J. D. Edwards (A.S.H.V.E. Transactions, VoL 45, 1939, p. 179). Thermal Test Coefficients of Aluminum Insulation for Buildings, by G. B. Wilkes, F. G. Hechler and E. R. Queer (A.S.H.V.E. Transactions, Vol. 46, 1940). 93