Document 0JJqdQQjBBj1241V0OeNvVYad
J-M MICRO-AIRE Specification Data
Density (nominal) Maximum Air Velocity Maximum Service Temp. Maximum Internal Pressure
3.3S pcf 2000 fpm**
250F 2" water
THERMAL CONDUCTIVITY
MEAN TEMPERATURE, F
50 75
100
.22 .23 .24
CONDUCTIVITY: BTU IN. PER SO FT PER F PER HR
STANDARD SIZES
Micro-Aire is available in standard round duct sizes from 4" through 30" I.D. Rectangular Micro-Ajre is available in vari ous cross-sectional dimensions ranging from 6" x 8" to 16" x 18" internal dimensions. All sections are furnished in 6' lengths overall.
UNDERWRITERS' LAB. CLASS.
Listed by U.L. as complying with Class 1 (UL 181) Standards of Safety for Air Ducts
Flame Spread Fuel Contributed Smoke Developed
Exterior Face 15 20
5
Interior Face
15 25
0
The figures given in this table are average values obtained In accord ance with accepted test methods.
**Mlcro-A!re has been tested In the Underwriters' Laboratories at ve* locities of SOOO fpm and in the J-M laboratories at velocities exceeding 13,000 fpm. The local J-M sales representative can make recommenda tions for systems operating at velocities higher than 2000 fpm.
SOUND ATTENUATION
Tested on a #6 mounting, Micro-Aire has an NRC over .90. The following tabulation reflects duct sound attenuation in decibels/foot based on actual laboratory tests:
Round Duct Size, I.D., inches
5 8 10
14
Sound Attenuation in Decibels per Foot at Frequency (cycles per second) of
125 250 500 1000 2000 4000
0.5 2.0 5.3 11.4 18.6 29.0 0.3 1.3 3.2 7.8 14.4 18.5 0.2 1.1 2.5 6.0 12.2 16.0 0.1 0.9 1.5 3.2 4.3 6.8
BUILD. CODE COMPLIANCE
Micro-Aire is approved by alt major building code authorities including: Building Officials Conference of America, Inc. Southern Building Code Congress International Conference of Building Officials National Board of Fire Underwriters (meets fire rating re quirement Standards 90A, 90B)
r.
Duct Sizes*, inches
4 5 6 7 8 9 10 12 14 16 18
Carton Contents
No. of
No. of
Sections
Feet
24 144 15 90 13 78
8 48 8 48 6 36 6 36 3 18 2 12 4 12 4 12
An Insiilatinn fnr
Carton Type**
A B A C B A A A C C B
Approx. Gross Shipping Weight,
lbs. per carton
70 52 51 40 46 38 40 28 23 26 28
0
For rectangular duct sizes, and round duct sizes treater than 18", consult local J-M Sales Office.
Carton Dimensions: Type A--24" x 36" x 72V*"; Type 8-20* x 40* x 72V**; Type C--18* x 36* x 72tt*.
ET-000064
JOKtfS'MAMVtUt
i.tti
31
8C16