Document 0J7ZvYeMVDy278dOd54NnggQn
EPA Region 5: Enforcement and Compliance Assurance Division
INSPECTION REPORT
Inspection Date: Time: Media: Statutes/Programs:
Type of inspection: Access:
October 4, 2023
Inspection Announced: No
Entry: 9:05 AM
Exit: 11:50 AM
Wastewater and Stormwater
Clean Water Act, NPDES, Direct Discharger Clean Water Act, NPDES, Industrial Stormwater, Direct Discharger
CEI - Compliance Evaluation Inspection
Granted
Permittee Name: Facility or Site Name: Facility/Site Physical Address: (City, State, Zip Code) County/Parish:
Leonardo DRS Leonardo DRS - Milwaukee 4265 North 30th Street Milwaukee, Wisconsin 53216 Milwaukee County
Permit Numbers: SIC or NAICS:
WI0062723, WIG004530 3625
BENJAMIN
Digitally signed by BENJAMIN
ATKINSON
ATKINSON
Date: 2023.11.15 09:54:17 -06'00'
Inspector Signature and Date:_________________________________________________
Approver Name and Title:
Ryan J. Bahr, Section 2 Supervisor Water Enforcement and Compliance Assurance Branch
RYAN BAHR Digitally signed by RYAN BAHR Date: 2023.11.15 16:57:01 -06'00'
Approver Signature and Date: ________________________________________________
Page 1 of 23
Leonardo DRS - Milwaukee, WI Persons Participating in Inspection:
October 4, 2023
Organization/Title
Name
Phone
EPA, Environmental
Engineer
Ted Flatebo (312) 353-5954
EPA, Inspector
Ben Atkinson (312) 353-8243
WDNR, Wastewater Field
Supervisor
Bryan Hartsook
(414) 607-2275
WDNR, Wastewater Engineer
Jacob Wedesky
(414) 259-1480
WDNR,
Jamie Lambert (414) 477-1119
Wastewater Specialist
WDNR,
Grace Barlow (414) 430-2483
Wastewater Specialist
Leonardo DRS, Facilities Manager
Joe Gajewski (262) 352-7837
Leonardo DRS, Facilities
Al Anderson (414) 530-4338
Leonardo DRS, EHS Intern
Yingshea Yang (414) 233-5055
Meverden Environmental,
Consultant
Kathy Hetzer (262) 714-5822
Email
flatebo.ted@epa.gov
atkinson.ben@epa.gov
bryan.hartsook @wisconsin.gov
jacob.wedesky @wisconsin.gov
jamie.labert @wisconsin.gov
grace.barlow @wisconsin.gov joseph.gajewski@drs.com
alanderson@drs.com
yingshea.yang@drs.com
kah@meverden.com
Present at Present at Opening Closing Conference Conference
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
Yes
TABLE OF CONTENTS
SECTION I - INTRODUCTION ......................................................................................................... 3 SECTION II - INSPECTION .............................................................................................................. 4 SECTION III - OBSERVATIONS ....................................................................................................... 5 SECTION IV - RECORDS REVIEW ................................................................................................... 6 SECTION V - SAMPLING ACTIVITIES AND ANALYTICAL RESULTS ................................................... 9 SECTION VI - AREAS OF CONCERN .............................................................................................. 10 SECTION VII - CLOSING CONFERENCE......................................................................................... 14 SECTION VIII - DOCUMENTS RECEIVED....................................................................................... 14 SECTION IX - LIST OF APPENDICES.............................................................................................. 14
Page 2 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
SECTION I - INTRODUCTION
Site Entry and Inspection Objectives
United States Environmental Protection Agency (EPA) Inspectors Ted Flatebo and Ben Atkinson, accompanied by Wisconsin Department of Natural Resources (WDNR) inspectors Bryan Hartsook, Jacob Wedesky, Jamie Lambert, and Grace Barlow, arrived at Leonardo DRS (the Site or Facility), located at 4265 North 30th Street, Milwaukee, Wisconsin at 9:05 AM on October 4, 2023 for an unannounced inspection. The six inspectors will collectively be referred to as the inspection team. Mr. Flatebo announced the inspection to the security staff at the Facility entrance gate on North 30th Street. After signing in at the gate, the inspection team parked their vehicles in the visitor parking lot. A second security guard instructed the inspection team to wait in the parking lot while an employee drove to meet us from a different Leonardo DRS facility in Menomonee Falls, Wisconsin. Mr. Yang arrived at approximately 9:35 AM and asked Mr. Flatebo to speak with John Spahr, EHS Director, on the phone. Mr. Flatebo explained the scope of the inspection to Mr. Spahr. Mr. Spahr stated he was unable to participate in the inspection because he was out of town and asked the inspection team to wait until Mr. Gajewski arrived and could further assist us. At approximately 9:45 Mr. Gajewski, Facilities Manager, arrived and brought the inspection team into the Facility, and, after signing in at the front desk, directed us to a conference room.
Mr. Flatebo presented his Temporary Letter of Authorization and Mr. Atkinson presented his inspector credential to the Facility representatives present at the opening conference, noted above. Mr. Flatebo informed the Facility representatives that this was an EPA Region 5 inspection to determine compliance with the Clean Water Act (CWA), the National Pollutant Discharge Elimination System (NPDES) permit program. The inspection was conducted under the authority of the CWA NPDES permit program and Section 308 of the CWA. The table above identifies the attendees who participated in the inspection.
This report is based on information supplied by Facility representatives, observations made by the EPA inspectors, and records and reports maintained by the Facility, WDNR, and EPA. These include the following: direct observations made by the EPA inspectors, photographs taken by EPA inspectors, and verbal or written statements made or supplied by Facility representatives during or subsequent to the on-site inspection, and materials, processes, data, photographs, or documents shown, demonstrated, or submitted to the EPA inspectors by Facility representatives during or subsequent to the on-site inspection. In addition, information gathered prior to or subsequent to the inspection from a review of EPA, WDNR, and public records may be included in this report.
This report was written by Mr. Flatebo. Because he conducted the inspection under a Temporary Letter of Authorization, the report is signed by Mr. Atkinson.
Background Information
Process wastewater generated at the Facility is covered by WDNR Wisconsin Pollutant Discharge Elimination System Permit number WI0062723-03. The effective date of the permit is August 1, 2017, and the permit was scheduled to expire on June 30, 2022. WDNR administratively continued the Permit, and it was in effect on the date of inspection. The Permit identifies three sampling locations described below. Each sampling location
Page 3 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
discharges to the Milwaukee Metropolitan Sewerage District (MMSD) storm sewer, which discharges to
Lincoln Creek northwest of the Facility.
Sampling Point No. 001
003 009
Sampling Point Location and Description Non-contact cooling water from test lab heat exchanger system and environmental test chambers located in the Vogel Lab. Grab composite samples are taken from either the manhole location in the southeast corner of the property near the main substation or from the drain valve located in the test cell. Flow is estimated. Temperature is measured with a continuous data logger. Cooling tower blowdown from roof top air conditioners. Discharges occurs once per year and grab samples are taken at the drain valve of the rooftop units just prior to discharge. Flow is estimated based on tank capacity. Non-contact cooling water from the PETF (acronym not clarified), Medium Voltage Test Facility (MVTF), and Rickover test lab heat exchangers. Grab samples are taken from the manhole located in the north parking lot, east of loading dock. Flow is estimated. Temperature is measured with a continuous data logger.
Stormwater generated at the Facility is covered by a WDNR Wisconsin Pollutant Discharge Elimination System General Permit for Stormwater Discharged from Tier 2 Industrial Activities (Stormwater General Permit) number WIG004530. The general permit number is WI-S067857-5. The effective date of the permit is May 31, 2021, and it is scheduled to expire on June 2, 2025. The Facility's Storm Water Pollution Prevention Plan (SWPPP) identifies one stormwater Outfall. The Outfall discharges to Lincoln Creek, which is Northwest of the Facility. Lincoln Creek is a tributary to the Milwaukee River.
SECTION II - INSPECTION
Opening Conference
The inspection team conducted an opening conference with Facility representatives, beginning at approximately 10:03 AM. The team gathered the following Facility information:
The Facility produces large-scale assembly of electric components. Mr. Gajewski explained that the Facility operations have been almost fully moved to the DRS's new facility in Menomonee Falls, Wisconsin and that they will vacate the Milwaukee facility by October 31, 2023. At full operation, the Facility had approximately 600 employees.
Mr. Gajewski stated the Facility was named Leonardo DRS - Milwaukee. The WDNR permit, WI0062723, states the Facility name is DRS Naval Power Systems. The WDNR permit application dated 9/24/2013 provided by Mr. Spahr following the inspection states the Facility name is DRS Power & Control Technologies, Inc. For this inspection report the Facility will be referred to as Leonardo DRS - Milwaukee.
Process wastewater is generated at the Facility during the testing of the electrical components. Non-contact, deionized (DI) cooling water is circulated through the cabinets the electrical components are installed in. The cabinets have internal piping for this purpose. During most tests, the DI water is recirculated through a closedloop system. Periodically, stress tests must be conducted. During these tests the cooling water is passed
Page 4 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
through a heat exchanger and discharged through a permitted sample location. Additional process
wastewater is discharged once annually when the Facility's cooling tower water is drained during the Fall.
During the opening conference, Facility representatives were asked if they considered any information confidential business information (CBI). Mr. Gajewski stated no information was considered CBI.
The opening conference concluded at approximately 11:25 AM. Afterwards the inspection team began the Facility walk through while accompanied by Mr. Gajewski, Mr. Anderson, and Mr. Yang. Below is a general description of the walk through. Specific observations are documented in Section III of this report.
Facility Walk Through
The Facility walk through began in the interior manufacturing area. Almost all equipment has been removed from the Facility. Mr. Gajewski stated that a single remaining electrical cabinet is being finalized before the company completely vacates the Facility. The inspection team observed most rooms and offices were vacant. The Columbia lab was still in operation due to the one remaining electrical cabinet. Approximately 10 employees were observed on Site.
The inspection team observed three deionized water (DI water) system at the Facility. Mr. Gajewski stated that each system is operable (Photos 1, 3, 4).
Stormwater
After conducting the interior Facility walk through, the inspection team continued outdoors to observe the stormwater best management practices (BMPs) and the stormwater Outfalls. Observations are documented in Section III of this report.
SECTION III - OBSERVATIONS Observations may not be in sequential order.
Unique Identifying No. TF-OB-001 TF-OB-002
TF-OB-003
TF-OB-004 TF-OB-005
Observation
Throughout the Facility almost all equipment had been removed. There was a single electrical cabinet still being assembled/tested by Facility personnel. The Columbia Lab was still operational for testing as necessary. Mr. Yang stated that the Columbia Lab had been most recently used in September 2023 to test an electrical cabinet. Three DI water systems were observed: Columbia Lab, Medium Voltage Facility Lab (MVTF), and Vogel Lab. Each system is operational. The MVTF and Vogel Lab systems were empty at the time of the inspection. Mr. Anderson stated that the Facility cooling towers were emptied at the end of 2022 and were never filled or operated in 2023. There are weather-proof boxes at Sample Points 001 and 009 which house ISCO temperature loggers.
Area of Concern?
No No
No
No No
Page 5 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
SECTION IV - RECORDS REVIEW Records may not be in sequential order.
Unique Identifying No. TF-RR-001
Record Non-Contact Cooling Water Discharge Sampling Plan (Sampling Plan)
TF-RR-002
-Developed in 2003 and has undergone multiple revisions. The most recent revision is dated 1/18/2018 -Discusses the need to sample for Total Residual Chlorine (TRC). The Sampling Plan does not discuss the need for TRC samples to be conducted in the field, with a maximum hold time of 15 minutes -States that compliance samples should be collected as grab samples, the Permit states that compliance samples should be collected as grab composite. -States that flow rates at the Sample Points can be estimated Wisconsin Pollutant Discharge Elimination System Wastewater Discharge Individual Permit Application - Signed 9/24/2013
TF-RR-003
-Facility operates 8 hours per day, 5 days a week -Facility purchases 15,600,000 gallons of water annually from MMSD -Outfall 001 discharged 50,000 gallons in the prior year -Outfall 001 reported a historic chloride concentration of 14 mg/L -Outfall 002 discharge has been rerouted out Outfall 003 and has been decommissioned -Outfall 003 is estimated to discharge 200 gallons/year during one day in the 4th quarter -Outfall 003 utilizes two biocides (CL215 and CL4) and one rust/scale inhibitor (CL1469) -Outfall 009 is estimated to discharge 11.5 million gallons/year, with a daily maximum of 36,000 gallons -Outfall 009 reported a historic chloride concentration of 14 mg/L -In the additional comments section, this statement was provided. "Due to intermittent flow, samples consisted of multiple grab samples occuring over a 30 minute period to create a composite sample" DRS Sewer Map - Updated 2023
TF-RR-004
-Property consists of 2.2 acres of paved or roofed areas -"Outfall 001 flows to line on Hope Street which then combines to 24" storm sewer line" -Outfall 001 & 003 discharge flows under building to 24" storm sewer line on west side of property" -"Outfall 009 discharge flows into North parking lot and out to 30th Street" Wastewater Discharge Monitoring Short Report - 2nd Quarter 2021
Area of Concern?
Yes
No
No Yes
Page 6 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Unique
Identifying
Area of
No.
Record
Concern?
-Halogen, Total Residual as Cl2 samples from Sample Point 001 and 009 were
collected after the end of the quarter (7/14/21)
-Chain of Custody was submitted to laboratory without specific analyses
identified
TF-RR-005 Wastewater Discharge Monitoring Short Report - 1st Quarter 2022
Yes
-Chain of Custody was submitted to laboratory without specific analyses
identified
TF-RR-006 Wastewater Discharge Monitoring Short Report - 3rd Quarter 2022
Yes
Total Phosphorus, Total Suspended Solids, and Halogen, Total Residual as Cl2
samples for Samples Points 001 and 009 were collected after the end of the
quarter (10/4/22)
TF-RR-007 Wastewater Discharge Monitoring Short Report - 4th Quarter 2022
Yes
-Total Phosphorus, Total Suspended Solids, and Halogen, Total Residual as Cl2
samples for Sample Points 001 and 009 were collected after the end of the
quarter (1/6/23)
-The Eurofins Laboratory report states that Sample Location 003 (Cooling
Towers) had a Total Residual Chlorine concentration of 0.235 mg/L. The
Wastewater Discharge Monitoring Short Report states that the concentration
was 0.235 g/L
TF-RR-008 Wastewater Discharge Monitoring Short Report - 1st Quarter 2023
Yes
-The Eurofins Laboratory report states that Sample Location 001 (Columbia
Lab) had a Total Residual Chlorine concentration of 0.593 mg/L. The
Wastewater Discharge Monitoring Short Report stated that the concentration
was 0.593 g/L
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab)
had a Total Residual Chlorine concentration of 0.212 mg/L. The Wastewater
Discharge Monitoring Short Report states that the concentration was 0.212
g/L
-Eurofins Laboratory effluent values have been assigned to the incorrect
Sample Point in the Wastewater Discharge Monitoring Short Report. MVTF
results were reported under Sample Point 001 but should have been reported
under Sample Point 009. The Columbia effluent values were reported under
Sample Point 009 but should have been reported under Sample Point 001
TF-RR-009 Wastewater Discharge Monitoring Short Report - 2nd Quarter 2023
Yes
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab) had a Total Residual Chlorine concentration of 1.30 mg/L. The Wastewater Discharge Monitoring Short Report states that the concentration was 1.30 g/L
Page 7 of 23
Leonardo DRS - Milwaukee, WI
Unique
Identifying
No.
Record
-No sample collection date/time were reported on the chain of custody. -
Samples were relinquished to the lab on 6/15/23
TF-RR-010 Wastewater Discharge Monitoring Short Report - 3rd Quarter 2023
October 4, 2023 Area of Concern?
Yes
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab)
had a Total Residual Chlorine concentration of 1.37 mg/L. The Wastewater
Discharge Monitoring Short Report states that the concentration was 1.37
g/L
TF-RR-011 Wastewater Discharge Monitoring Short Report - General Comments
Yes
-There is insufficient data to demonstrate that Halogen, Total Residual as Cl2
samples were collected and analyzed within the required 15-minute holding
time
-Chains of custody from the 1st quarter 2021 to 2nd Quarter 2022 do not
identify the type of sampling container used
-Chains of custody from the 1st quarter 2021 to 2nd Quarter 2022 do not
identify if a preservative was used/which preservative was used
-Chains of custody do not identify the specific sample location (i.e. sample port
with lab or manhole)
-Multiple Chains of Custody were not signed by a Facility representative
relinquishing samples to the laboratory
-There is insufficient data to determine if samples are representative of typical
flows
TF-RR-012 Wastewater Discharge Monitoring Short Report - Effluent Violations
Yes
See Appendix 2 for effluent violation summary
TF-RR-013 Letter from Leonardo DRS to WDNR: Report on Effluent Discharges and
No
Operational Evaluation Report - Dated 6/6/2018
The Facility provided historical Halogen effluent data and identified that they were not in compliance with the effluent limit in Permit No. WI0062723-03 which would become effective 7/1/2020.
Outfall 001 and 009 Action Plan: The Facility discussed the possibility of requesting WDNR's permission to reroute non-contact cooling water from the storm sewer to the sanitary sewer once WDNR creates an approval process for such a request.
Outfall 003 Action Plan: The Facility anticipated no long discharging cooling
tower effluent from this outfall and instead hauling the wastewater
TF-RR-014 Letter from Leonardo DRS to WDNR: Total Chlorine Action Plan and Total
No
Phosphorus Compliance Alterative, Source Reduction Plan - Dated 10/31/2019
Page 8 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Unique
Identifying
Area of
No.
Record
Concern?
The Facility requested a waiver from WDNR "...from implementation of source
reduction or compliance alternatives to meet the total chlorine limitations by
6/30/20 due to the upcoming relocation"
The Facility also requested a waiver from WDNR "...from the phosphrous
limitations [because] the Facility will cease operations prior to the June 20,
2026 final compliance date..."
TF-RR-015 Email from Bryan Hartsook (WDNR) to William Jones (Leonardo DRS) - Dated
No
4/3/2020
"Thank you for notifying the Department of DRS' progress in relocating to the
new facility location in Menomonee Falls. This does make the compliance
schedules for phosphorus and chlorine unnecessary. Therefore, future
reporting under these compliance schedules is not required. We may process a
minor permit medication to document this condition."
TF-RR-016 Storm Water Pollution Prevention Plan (SWPPP)
Yes
-Developed in 2003 and has undergone multiple revisions. The most recent revision is dated 3/7/2018 -Identifies that in 2011 Lincoln Creek was impaired for the following pollutants of concern: polycyclic aromatic hydrocarbons (PAHs), polychlorinated biphenyls (PCBs), metals, total suspended solids, phosphorous, and chlorine - SWPPP states that the Facility does not discharge any pollutants of concern to any water body on the State and Federal approved TMDL -The SWPPP does not discuss if the Facility's stormwater discharges to a fish and aquatic life water -States that employee training is not required because BMPs are in place -No employee SWPPP training records were provided -SWPPP does not discuss if the Facility discharges stormwater to an outstanding resource water as determined by WDNR -SWPPP was not certified/signed
TF-RR-017 Section 4 of the Facility's stormwater permit, WIG004530, requires the Facility
Yes
to conducted both annual facility site compliance inspections and quarterly
visual monitoring.
During the inspection, Mr. Flatebo requested these documents from 1/1/21 to present. In a follow up email on 10/10/23, Mr. Spahr stated that the Facility did not conduct any annual facility site compliance inspections and quarterly visual monitoring activities during that timeframe.
SECTION V - SAMPLING ACTIVITIES AND ANALYTICAL RESULTS No samples were collected as part of this inspection.
Page 9 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
SECTION VI - AREAS OF CONCERN The presentation of areas of concern does not constitute a formal compliance determination or violation.
Unique Identifying No. TF-RR-001
Record Non-Contact Cooling Water Discharge Sampling Plan (Sampling Plan)
-Discusses the need to sample for Total Residual Chlorine. The Sampling Plan does not discuss the need for TRC samples to be conducted in the field, with a maximum hold time of 15 minutes.
40 C.F.R. 136
-States that all compliance samples should be collected as grab samples, the Permit states that 001 compliance samples should be collected as grab composite.
NPDES Permit No. WI0062723-03, Section 1.2.1
TF-RR-004 Wastewater Discharge Monitoring Short Report - 2nd Quarter 2021
-Halogen, Total Residual as Cl2 samples from Sample Point 001 and 009 were collected after the end of the quarter (7/14/21)
NPDES Permit No. WI0062723-03, Section 1.2.1/1.2.3
-Chain of Custody was submitted to laboratory without specific analyses identified
40 C.F.R. 136
TF-RR-005 Wastewater Discharge Monitoring Short Report - 1st Quarter 2022
-Chain of Custody was submitted to laboratory without specific analyses identified
40 C.F.R. 136
TF-RR-006 Wastewater Discharge Monitoring Short Report - 3rd Quarter 2022
Total Phosphorus, Total Suspended Solids, and Total Residual as Cl2 (Halogen) samples for Samples Points 001 and 009 were collected after the end of the quarter (10/4/22)
NPDES Permit No. WI0062723-03, Sections 1.2.1/1.2.3
TF-RR-007 Wastewater Discharge Monitoring Short Report - 4th Quarter 2022
-Total Phosphorus, Total Suspended Solids, and Total Residual as Cl2 (Halogen) samples for Sample Points 001 and 009 were collected after the end of the quarter (1/6/23)
Page 10 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
NPDES Permit No. WI0062723-03, Sections 1.2.1/1.2.3
-The Eurofins Laboratory report states that Sample Location 003 (Cooling Towers) had a Total Residual Chlorine concentration of 0.235 mg/L. The Wastewater Discharge Monitoring Short Report stated that the concentration was 0.235 g/L.
40 C.F.R. 122.41
TF-RR-008 Wastewater Discharge Monitoring Short Report - 1st Quarter 2023
-The Eurofins Laboratory report states that Sample Location 001 (Columbia Lab) had a Total Residual Chlorine concentration of 0.593 mg/L. The Wastewater Discharge Monitoring Short Report stated that the concentration was 0.593 g/L.
40 C.F.R. 122.41
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab) had a Total Residual Chlorine concentration of 0.212 mg/L. The Wastewater Discharge Monitoring Short Report stated that the concentration was 0.212 g/L.
40 C.F.R. 122.41
-Eurofins Laboratory effluent values have been assigned to the incorrect Sample Point in the Wastewater Discharge Monitoring Short Report. MVTF results were reported under Sample Point 001 but should have been reported under Sample Point 009. The Columbia effluent values were reported under Sample Point 009 but should have been reported under Sample Point 001.
40 C.F.R. 122.41
TF-RR-009 Wastewater Discharge Monitoring Short Report - 2nd Quarter 2023
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab) had a Total Residual Chlorine concentration of 1.30 mg/L. The Wastewater Discharge Monitoring Short Report stated that the concentration was 1.30 g/L.
40 C.F.R. 122.41
-No sample collection date/time on chain of custody. Relinquished to lab on 6/15/23.
TF-RR-010
40 C.F.R. 136 Wastewater Discharge Monitoring Short Report - 3rd Quarter 2023
-The Eurofins Laboratory report states that Sample Location 009 (MVTF Lab) had a Total Residual Chlorine concentration of 1.37 mg/L. The Wastewater Discharge Monitoring Short Report stated that the concentration was 1.37 g/L.
Page 11 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
40 C.F.R. 122.41
TF-RR-011 Wastewater Discharge Monitoring Short Report - General Comments
-There is insufficient data to demonstrate that Halogen, Total Residual as Cl2 samples were collected and analyzed within the required 15-minute holding time
40 C.F.R. 136
-Chains of custody from the 1st quarter 2021 to 2nd Quarter 2022 do not identify the type of sampling container used.
NPDES Permit No. WI0062723-03, Section 3.1.2
-Chains of custody from the 1st quarter 2021 to 2nd Quarter 2022 do not identify if a preservative was used/which preservative was used
NPDES Permit No. WI0062723-03, Section 3.1.2
-Chains of custody do not identify the specific sample location (i.e. sample port with lab or manhole)
NPDES Permit No. WI0062723-03, Section 3.1.2
-Chains of Custody are not signed by a Facility representative relinquishing samples to the laboratory
NPDES Permit No. WI0062723-03, Section 3.1.2
-There is insufficient data to determine if samples are representative of typical flows.
NPDES Permit No. WI0062723-03, Section 3.1.2
TF-RR-012 Wastewater Discharge Monitoring Short Report - Effluent Violations
See Appendix 2 for effluent violation summary
NPDES Permit No. WI0062723-03, Sections 1.2.1/1.2.2/1.2.3
TF-RR-016 Storm Water Pollution Prevention Plan (SWPPP)
-Identifies that in 2011 Lincoln Creek was impaired for the following pollutants of concern: polycyclic aromatic hydrocarbons (PAHs), polychlorinated biphenyls (PCBs), metals, total suspended solids, phosphorous, and chlorine
NPDES Permit No. WIG004530, Section 2.8.2
Page 12 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Facility did not complete review annually, most recent impaired water body list released
by WDNR in 2022
- SWPPP states that the facility does not discharge any pollutant of concern to any water body on the State and Federal approved TMDL
NPDES Permit No. WIG004530, Section 2.8.5 Facility discharges phosphorous and total suspended solids which are included in the Milwaukee River Basin TMDL report dated March 19, 2018
-The SWPPP does not discuss if the Facility's stormwater discharges to a fish and aquatic life water
NPDES Permit No. WIG004530, Section 2.9
-States that employee training is not required because BMPs are in place.
NPDES Permit No. WIG004530, Section 2.11.7
-No employee SWPPP training records were provided.
NPDES Permit No. WIG004530, Section 2.11.7
-SWPPP does not discuss if the Facility discharges stormwater to an outstanding resource water as determined by WDNR
NPDES Permit No. WIG004530, Section 2.7.2
-SWPPP was not certified
NPDES Permit No. WIG004530, Section 3.3.2.11
TF-RR-017
Section 4 of the Facility's stormwater permit, WIG004530, requires the Facility to conducted both annual facility site compliance inspections and quarterly visual monitoring.
During the inspection, Mr. Flatebo requested these documents from 1/1/21 to present. In a follow up email on 10/10/23, Mr. Spahr stated that the Facility did not conduct any annual facility site compliance inspections and quarterly visual monitoring activities during that timeframe.
NPDES Permit No. WIG004530, Section 4
Page 13 of 23
Leonardo DRS - Milwaukee, WI SECTION VII - CLOSING CONFERENCE Closing Conference
October 4, 2023
The inspection team held a closing conference with Facility personnel beginning at approximately 11:20 AM. During the closing conference, inspectors discussed the observations and Areas of Concern identified during the inspection. Observations and Areas of Concern have not yet been evaluated for a formal compliance determination.
SECTION VIII - DOCUMENTS RECEIVED
The following documents were sent by Mr. Spahr electronically to Mr. Flatebo on October 10, 2023.
- Non-Contact Cooling Water Discharge Sampling Plan, updated 1/18/2018 - Wisconsin Pollutant Discharge Elimination System Wastewater Discharge Individual Permit Application,
signed 9/24/2013 - DRS Sewer Map, updated 2023 - Wastewater Discharge Monitoring Short Report: 1st Quarter 2021 through 3rd Quarter 2023 - Eurofins Analytical Reports and Chains of Custody: 1st Quarter 2021 through 3rd Quarter 2023 - Storm Water Pollution Prevention Plan, updated 3/7/2018 - Letter from Leonardo DRS to WDNR: Report on Effluent Discharges and Operational Evaluation Report, dated
6/6/2018 - Letter from Leonardo DRS to WDNR: Total Chlorine Action Plan and Total Phosphorus Compliance Alterative,
Source Reduction Plan, dated 10/31/2019 - Letter from Leonardo DRS to WDNR: Report on Effluent Discharges and Operational Evaluation Report, dated
6/6/2018 - Email from Bryan Hartsook (WDNR) to William Jones (Leonardo DRS), dated 4/3/2020
SECTION IX - LIST OF APPENDICES Appendix 1 - Photo Log Appendix 2 - Effluent Limit Violations Summary Table Appendix 3 - NPDES Permit No. WI-0062723-03-0 (DRS Naval Power Systems) Appendix 4 - NPDES Permit No. WI-S067857-5 (Tier 2 Industrial Facilities)
Page 14 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Appendix 1 - Photo Log
Page 15 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Leonardo DRS
EPA Inspection October 4, 2023
All photos taken by Ted Flatebo, Environmental Engineer, U.S. EPA
Camera: Pentax WG-1
1: IMGP0002 Description: Deionized water system overview. Location: Rickover Lab Camera Direction: South Date/Time: October 4, 2023, 10:23 AM
2: IMGP0003 Description: Piping for inlet and outlet of lab test water. Location: Rickover Lab Camera Direction: West Date/Time: October 4, 2023, 10:24 AM
Page 16 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
3: IMGP0004 Description: Deionized water system overview. Location: MVTF Lab (Medium Voltage Test Facility) Camera Direction: Northwest Date/Time: October 4, 2023, 10:28 AM
4: IMGP0005 Description: Deionized water system overview. Location: Columbia Lab Camera Direction: East Date/Time: October 4, 2023, 10:35 AM
Page 17 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
5: IMGP0006 Description: Sample Point 001 temperature logger Location: Outdoors, west fenceline Camera Direction: West Date/Time: October 4, 2023, 10:46 AM
6: IMGP0007 Description: Sample Point 001 overview Location: Outdoors, west fenceline Camera Direction: West Date/Time: October 4, 2023, 11:00 AM
Page 18 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
7: IMGP0008 Description: Sample Point 009 flow temperature logger Location: North parking lot Camera Direction: South Date/Time: October 4, 2023, 11:05 AM
Page 19 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Appendix 2 - Effluent Limit Violations Summary Table
Page 20 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Sample Date
3/26/2021 7/14/2021 7/14/2021 8/27/2021 8/27/2021 11/15/2021 11/15/2021 3/21/2022 3/21/2022 6/30/2022 6/30/2022 10/4/2022 10/24/2022 1/6/2023 3/2/2023 3/2/2023 6/15/2023 9/21/2023
Leonardo DRS - Milwaukee, WI
Effluent Limit Violations: 1/1/2021 to 9/30/2023
Permit Limit,
Sampling
Parameter
Monthly
Point
Average
(g/L )
001
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
003
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
001
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
009
Halogen, Total Residual at Cl2 10
Eurofins Value (g/L)
79 730 1400 * * * * 56 125 1230 1230 1390 235 1360 212 593 1300 1370
DMR Value (g/L)
79 73 140 73 140 73 140 0.056 0.125 1230 1230 1390 0.235 1360 0.212 0.593 1.30 1.37
* = Eurofins lab report not provided to EPA
Page 21 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Appendix 3 - NPDES Permit No. WI-0062723-03-0 (DRS Naval Power Systems)
Page 22 of 23
Leonardo DRS - Milwaukee, WI
October 4, 2023
Appendix 4 - NPDES Permit No. WI-S067857-5 (Tier 2 Industrial Facilities)
Page 23 of 23
Page 1 of 27 WPDES Permit No. WI-S067857-5
STATE OF WISCONSIN DEPARTMENT OF NATURAL RESOURCES
GENERAL PERMIT TO DISCHARGE UNDER THE WISCONSIN POLLUTANT DISCHARGE ELIMINATION SYSTEM
WPDES PERMIT NO. WI-S067857-5
TIER 2 INDUSTRIAL FACILITIES
In compliance with the provisions of ch. 283, Wis. Stats., and ch. NR 216, Wis. Adm. Code, any Tier 2 facility as defined in ch. NR 216, Wis. Adm. Code, and located in the State of Wisconsin, excluding section 2.5.1, that discharges
STORM WATER ASSOCIATED WITH INDUSTRIAL ACTIVITY
and meeting the applicability criteria in section 2 of this permit and that receives a letter from the Wisconsin Department of Natural Resources (Department) granting coverage under this permit, is authorized to discharge storm water to waters of the state provided that the discharge is in accordance with the conditions set forth in this permit.
This permit is issued by the Department and covers storm water discharges from the facility as of the Start Date of permit coverage to the permittee. For initial permit coverage, the Department will transmit a cover letter to the permittee stating that the facility is covered under this permit. Initial coverage under this permit will become effective at a facility beginning upon the Start Date specified by the Department in the cover letter. For an existing facility with permit coverage under a previously issued version of the Tier 2 general permit, coverage under this permit will become effective at the facility beginning upon the Effective Date below. For these facilities, the Effective Date is the Start Date.
State of Wisconsin Department of Natural Resources For the Secretary
By Brian Weigel, Director Bureau of Watershed Management
PERMIT EFFECTIVE DATE: May 31, 2021
May 14, 2021 Date
PERMIT EXPIRATION DATE: June 2, 2025
Page 2 of 27 WPDES Permit No. WI-S067857-5
Table of Contents 1. Application Requirements 2. Permit Applicability Criteria 3. Storm Water Pollution Prevention Plan 4. Monitoring Requirements 5. Compliance and Reporting Requirements 6. General Conditions
Page 3 of 27 WPDES Permit No. WI-S067857-5
Page 3 5 15 21 23 25
Note: Information about the Department of Natural Resources' storm water program, this general permit, forms, and other helpful resources is available at https://dnr.wisconsin.gov/topic/Stormwater.
1. APPLICATION REQUIREMENTS
Page 4 of 27 WPDES Permit No. WI-S067857-5
1.1 Initial Permit Coverage The owner or operator of a Tier 2 industrial facility type listed in s. NR 216.21(2)(b), Wis. Adm. Code, and not previously covered under the Tier 2 general permit shall submit a complete Notice of Intent (NOI) to the Department to apply for coverage under an industrial storm water discharge permit in accordance with the time frames in s. NR 216.22(2), Wis. Adm. Code. Within 30 calendar days of receipt of the NOI, the Department will evaluate the information submitted in the NOI to determine whether the NOI is complete, whether additional information is needed for review, whether the facility will be covered under this permit or an individual permit, or whether coverage under a permit will be denied. Based upon this evaluation, unless notified to the contrary by the Department, within 30 calendar days of receipt of the NOI, the Department will transmit a cover letter to the owner or operator indicating the Start Date upon which permit coverage becomes effective at the facility with instructions on where to download the permit from the Department website. In the alternative, a hard copy of the permit will be mailed to the owner or operator of the facility upon request.
Note: The NOI form (Form 3400-163), information about submitting via the Department's Water ePermitting System, and general permit are available for download from the Department website at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html. The Notice of Intent requires applicants to provide information on the applicant, facility location, applicability and operations information, storm water discharge information, and non-storm water discharge information.
1.2 Existing Permit Coverage Unless the Department makes a determination for an individual WPDES permit under section 2.5.7, a Tier 2 industrial facility type listed in s. NR 216.21(2)(b), Wis. Adm. Code, with existing Tier 2 general permit coverage prior to the Effective Date of this permit is automatically covered under this permit as of the Effective Date. For these permittees, the Effective Date is the permittee's Start Date. The Department will notify the owner or operator of the facility's continued coverage under this permit with instructions on where to download the permit from the Department website. In the alternative, a hard copy of the permit will be mailed to the owner or operator of the facility upon request.
Note: The general permit is available on the Department website at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html.
1.3 No Exposure Certification The owner or operator of a facility not currently covered under this permit that has submitted a Conditional No Exposure Certification to the Department in accordance with s. NR 216.21(3), Wis. Adm. Code, but that has been denied a No Exposure Exclusion by the Department shall apply for permit coverage in accordance with section 1.1 of this permit within 14-working days of being notified by the Department of the denial. The owner or operator of a facility that has previously been granted a No Exposure Exclusion by the Department but that has had that exclusion revoked shall apply for permit coverage in accordance with section 1.1 of this permit within 14-working days of being notified by the Department of the revocation.
1.4 Permit Coverage Transfers A permittee who will no longer control the permitted industrial facility may request that permit coverage be transferred to the person who will control the industrial facility. The transfer request shall be signed by both the permittee and the new owner or operator and sent electronically through the Department's Water ePermitting System. The Department may require additional information including an NOI to be filed prior to transferring permit coverage. Coverage is not transferred until the Department sends notification of transfer approval to the new owner or operator. The transfer request shall contain the following information:
1.4.1 The name and address of the facility.
Page 5 of 27 WPDES Permit No. WI-S067857-5
1.4.2 The Facility Identification Number.
1.4.3 The names of the persons involved in the transfer, their signatures, and date of signatures.
1.4.4 A description of any significant changes in the operation of the facility.
1.4.5 A statement of acknowledgement by the transferee that it will be the permittee of record and is responsible for compliance with the permit.
Note: The Transfer of Coverage form (Form 3400-222) and information about submitting via the Department's Water ePermitting System are available on the Department website at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html.
1.5 Permit Coverage Terminations If the permittee no longer claims coverage under this permit, the permittee shall submit a signed Notice of Termination (NOT) to the Department in accordance with s. NR 216.32, Wis. Adm. Code.
Note: The NOT form (Form 3400-170) and information about submitting via the Department's Water ePermitting System are available on the Department website at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html.
2. PERMIT APPLICABILITY CRITERIA
Page 6 of 27 WPDES Permit No. WI-S067857-5
2.1 Applicability This permit applies to point sources at facilities which discharge contaminated storm water associated with industrial activity to waters of the state, either directly or via a separate storm sewer system, originating from industrial facilities belonging to:
2.1.1 Manufacturing facilities described by the following SIC codes:
SIC
Description
20-21-22-23-2434 25-26526727-28328530-31-32334-35-36-37-38-39-4221 4222 4225
Food & Kindred Products Tobacco Products Textile Mill Products Apparel & Other Textile Products Wood Kitchen Cabinets Furniture & Fixtures Paperboard Containers & Boxes Misc. Converted Paper Products Printing, Publishing, & Allied Industries Drugs Paints & Allied Products Rubber & Misc. Plastics Products Leather & Leather Products Products of Purchased Glass Fabricated Metal Products Industrial & Commercial Machinery & Computer Equipment Electronic & Other Electrical Equipment & Components Transportation Equipment Instruments & Related Products Misc. Manufacturing Industries Farm Product Warehousing & Storage Refrigerated Warehousing & Storage General Warehousing & Storage
Note: Facilities in SIC codes 311-, 3441 and 373- are included in s. NR 216.21(2)(a) 1. as Tier 1 facilities.
2.1.2 Transportation facilities described by the following SIC codes that have vehicle maintenance shops, equipment cleaning operations, or airport de-icing operations. This only applies to those portions of these facilities that are either involved in vehicle maintenance including rehabilitation, mechanical repairs, painting, fueling, lubrication, and associated parking areas, or involved in cleaning operations, or de-icing operations, or that are listed as a pollution source area under s. NR 216.27(3)(e):
SIC
Description
40--
Railroad Transportation
41--
Local & Interurban Passenger Transit
42--
Trucking & Warehousing
43--
U.S. Postal Service
44--
Water Transportation
45-5171
Transportation by Air Petroleum Bulk Stations & Terminals
Page 7 of 27 WPDES Permit No. WI-S067857-5
2.1.3 Facilities described by the following SIC codes, including active and inactive mining operations. This permit only applies where storm water runoff has come into contact with any overburden, raw material, intermediate product, finished product, by-product, or waste material.
SIC
Description
10--
Metal Mining
12--
Coal Mining
13--
Oil & Gas Extraction
14--
Non-metallic Minerals, except fuels
Note: An industry-specific general permit has been developed by the Department that regulates both process and storm water discharges associated non-metallic mining operations, SIC code 14--. While the Department intends to cover non-metallic mining operations under the industry-specific general permit, it may alternatively cover storm water discharges associated with non-metallic mining operations under this Tier 2 general permit. This permit does not apply to non-coal mining operations which have been released from applicable state or federal reclamation requirements after December 17, 1990; nor to coal mining operations released from the performance bond issued to the facility by the appropriate Surface Mining Control and Reclamation Act authority under 30 USC 1201 et seq. and 16 USC 470 et seq. Production, processing, or treatment operations or transmission facilities associated with oil and gas extraction are included only if there has been a discharge of storm water after November 16, 1987 containing a reportable quantity of a pollutant, or if a storm water discharge contributed to a violation of a water quality standard.
2.1.4 Facilities subject to storm water effluent limitation guidelines, new or existing source performance standards, or toxic pollutant effluent standards under 33 USC 1251, 1311, 1314 (b) and (c), 1316 (b) and (c), 1317 (b) and (c), 1326 (c), except for those facilities identified in paragraph A.(1) that do not have contaminated storm water.
2.1.5 Treatment works treating domestic sewage or any other sewage sludge or wastewater treatment device or system, used in the storage, treatment, recycling, and reclamation of municipal or domestic sewage, including land dedicated to the disposal of sewage sludge that are located within the confines of the facility, with a design flow of one million gallons per day or more, or required to have an approved pretreatment program. Not included are farm lands, domestic gardens or lands used for sludge management where sludge is beneficially reused and which are not physically located in the confines of the facility, or areas that are in compliance with Section 405 of the Clean Water Act under 33 USC s. 1345.
2.1.6 Hazardous waste treatment, storage, and disposal facilities, including those operating under interim status or a permit under Subtitle C of the Resource Conservation and Recovery Act (RCRA), 42 USC 6901 et seq.
2.1.7 Landfills, land application sites, and open dumps that receive or have received any industrial waste from any of the facilities identified in this section 2.1 of this permit, including those subject to regulation under subtitle D of RCRA, 42 USC 6901 et seq., or ch. 289, Wis. Stats. For purposes of this section, landfills include those landfills for construction and demolition waste disposal.
Page 8 of 27 WPDES Permit No. WI-S067857-5 2.1.8 Steam electric power generating facilities, including coal handling sites but not including offsite transformer or electric substations.
2.1.9 Facilities described in SIC code 2951 for asphalt paving mixes and block, and facilities described in SIC codes 3271, 3272 and 3273 for cement products.
Note: In 1997, the North American Industry Classification System (NAICS) was developed as the standard for use by Federal agencies in classifying business establishments and has been adopted by Federal agencies to replace the SIC Code system. As a result, an industrial facility identified in sections 2.1.1 through 2.1.9 of this permit may have an NAICS Code assigned to it by a Federal agency, trade association, or other organization. If needed, the Department may use Federal data to convert the NAICS Code to the corresponding SIC Code for purposes of determining the applicability of this permit to the facility.
2.1.10 Facilities originally covered under a Tier 1 general permit, but subsequently covered under a Tier 2 general permit pursuant to s. NR 216.23(3), Wis. Adm. Code.
2.2 Authorized Discharges This permit authorizes storm water point source discharges to waters of the State from industrial activities identified in section 2.1 of this permit. This permit also authorizes the discharge of storm water commingled with flows contributed by process and non-process wastewater, provided those flows are regulated by other WPDES permits, if required.
2.3 Movement to Tier One Coverage In accordance with s. NR 216.23(4), Wis. Adm. Code, the Department may revoke coverage under this permit. In this case, the permittee shall reapply for Tier 1 general permit coverage.
2.4 Exclusions This permit does not apply to any of the following:
2.4.1 Diffused surface drainage or agricultural storm water discharges.
2.4.2 Non-storm water discharges.
2.4.3 Non-storm water discharges for which coverage under an individual or general WPDES permit is not required, including landscape irrigation, diverted stream flows, uncontaminated groundwater infiltration, uncontaminated pumped groundwater, discharges from potable water sources, foundation drains, air conditioning condensation, irrigation water, lawn watering, individual residential car washing, flows from riparian habitats and wetlands and fire fighting.
2.4.4 Inactive, closed or capped landfills that have no potential for contamination of storm water. The Department shall make a determination of contamination potential on a case-by-case basis.
2.4.5 Remedial action discharges or discharges authorized by a WPDES permit for discharging contaminated or uncontaminated groundwater.
2.4.6 Areas located on plant lands that are segregated from the industrial activities of the plant, such as office buildings and accompanying parking lots, if the drainage from the segregated areas is not mixed with contaminated storm water drainage.
2.4.7 Storm water discharges into a municipal combined sewer system.
Page 9 of 27 WPDES Permit No. WI-S067857-5
Note: Areas where this exclusion may apply include portions of the City of Milwaukee, the City of Superior, and the Village of Shorewood.
2.4.8 Storm water discharges from an industrial facility for which the owner or operator has submitted a Conditional No Exposure Certification to the Department in accordance with s. NR 216.21(3), Wis. Adm. Code, provided that the Department concurs with the no exposure certification and the conditions under which a No Exposure Exclusion was granted remain in effect.
2.5 Discharges Not Covered by this Permit The following are not authorized under this permit:
2.5.1 Storm water discharges within Indian Country.
Note: Indian County is defined under 18 USC 1151 and includes all lands within the exterior boundaries of federally recognized Indian reservations and on lands held in federal trust status. Facilities that currently do not have storm water discharge permit coverage and are located within Indian Country should contact the United States Environmental Protection Agency (USEPA) to apply. For existing discharges covered under a National Pollution Discharge Elimination System (NPDES) permit from USEPA, discharges will continue to be covered by a NPDES permit. Dischargers that previously held permit coverage under previous versions of this permit after September 30, 2001, are no longer eligible for coverage under this permit and must contact USEPA to apply.
USEPA's website contains information on the Multi-Sector General Permit: https://www.epa.gov/npdes/stormwater-discharges-industrial-activities. Facilities should verify eligibility for coverage under the general permit or determine if an individual permit is needed. Information on how to apply for the Multi-Sector General Permit can be accessed here: https://epanet.zendesk.com/hc/enus/articles/360001508168-How-to-Create-a-NOI-for-MSGP-PPT-.
2.5.2 Discharges of hazardous substances that are required to be reported under ch. NR 706, Wis. Adm. Code.
2.5.3 Storm water discharges that affect wetlands, unless the Department determines that the storm water discharges comply with the wetland water quality standards provisions in ch. NR 103, Wis. Adm. Code.
2.5.4 Storm water discharges that affect endangered and threatened resources, unless the Department determines that the storm water discharges comply with the endangered and threatened resource protection requirements of s. 29.604, Wis. Stats., and ch. NR 27, Wis. Adm. Code.
2.5.5 Storm water discharges that affect any historic property that is listed property, or on the inventory or on the list of locally designated historic places under s. 44.45, Wis. Stats., unless the Department determines that the storm water discharges will not have an adverse effect on any historic property pursuant to s. 44.40(3), Wis. Stats.
2.5.6 Storm water discharges from land disturbing construction activity affecting one acre or more of land that require storm water permit coverage under subch. III of NR 216, Wis. Adm. Code, for new construction, reconstruction, or expansion of an industrial facility.
Note: Storm water discharges from areas of bare soil due to the normal industrial operation of the facility are covered under this permit provided those areas are managed in accordance with section 3.3.2.8.2.
2.5.7 Facilities where the Department makes a determination, pursuant to s. 283.35(3), Wis. Stats. or
Page 10 of 27 WPDES Permit No. WI-S067857-5
s. NR 216.25(3), Wis. Adm. Code, that a storm water discharge is more appropriately covered under an individual WPDES permit. The Department may make this determination if one or more of the following conditions are met:
2.5.7.1 The storm water discharge is potentially a significant source of pollution and more appropriately regulated by an individual WPDES storm water discharge permit.
2.5.7.2 The facility is not in compliance with the terms and condition of this permit or Subchapter II of ch. NR 216, Wis. Adm. Code.
2.5.7.3 Numeric effluent limitations or standards are promulgated for a storm water discharge covered by this permit.
2.5.7.4 Storm water discharges that are regulated by permits containing storm water effluent limitations.
2.5.8 Storm water discharges in violation of the regulation of injection wells under ch. NR 815, Wis. Adm. Code.
Note: Information about the Department's injection well program may be found at: https://dnr.wi.gov/topic/wells/uiw.html.
2.5.9 Discharges associated with activities subject to any of the federal effluent limitation guidelines listed in Table 1 below:
Table 1. Regulated Activity
Discharges resulting from spray down or intentional wetting of logs at wet deck storage areas
40 CFR Part/Subpart
Part 429, Subpart I
Runoff from phosphate fertilizer manufacturing facilities that comes into contact with any raw materials, finished product, by-products or waste products (SIC 2874)
Part 418, Subpart A
Runoff from asphalt emulsion facilities
Runoff from material storage piles at cement manufacturing facilities
Mine dewatering discharges at crushed stone, construction sand and gravel, or industrial sand mining facilities
Runoff from hazardous waste landfills
Runoff from non-hazardous waste landfills
Runoff from coal storage piles at steam electric generating facilities
Part 443, Subpart A Part 411, Subpart C
Part 436, Subparts B, C, and D Part 445, Subpart A Part 445, Subpart B Part 423
Runoff containing urea from airfield pavement deicing at existing and new primary airports with 1,000 or more annual non-propeller aircraft departures
Part 449
Page 11 of 27 WPDES Permit No. WI-S067857-5
Note: The federal effluent limitations guidelines are available at the following website: https://www.epa.gov/eg/industrial-effluent-guidelines. Discharges associated with activities subject to any of the federal effluent limitation guidelines listed in Table 1 require coverage under a separate WPDES general permit or individual permit. However, these industrial facilities still require coverage under this permit for discharges not subject to the federal effluent limitation guidelines listed in Table 1.
2.6 Water Quality Standards
2.6.1 This permit specifies the conditions under which storm water may be discharged to waters of the state for the purpose of achieving water quality standards contained in chs. NR 102 through 105, NR 140, and NR 207, Wis. Adm. Code. For the term of this permit, compliance with water quality standards will be addressed by adherence to general narrative-type storm water discharge limitations and implementation of a storm water pollution prevention plan.
2.6.2 This permit does not authorize storm water discharges that the Department, prior to authorization of coverage under this permit, determines will cause or have reasonable potential to cause or contribute to an excursion above any applicable water quality standard. Where such determinations have been made prior to authorization, the Department may notify the applicant that an individual permit application is necessary. However, the Department may authorize coverage under this permit where the storm water pollution prevention plan required under this permit will include appropriate controls and implementation procedures designed to bring the storm water discharge into compliance with water quality standards.
2.7 Outstanding and Exceptional Resource Waters
2.7.1 Storm water discharges from industrial facilities covered under a previously issued version of this permit shall comply with sections 2.7.2 through 2.7.5 as of the Effective Date. Storm water discharges from industrial facilities covered under this permit after the Effective Date shall comply with sections 2.7.2 through 2.7.5 as of the Start Date of coverage under this permit.
2.7.2 The permittee shall determine whether any part of its facility discharges storm water to an outstanding resource water (ORW) or exceptional resource water (ERW). ORWs and ERWs are listed in ss. NR 102.10 and 102.11, Wis. Adm. Code, respectively.
Note: A list of ORWs and ERWs may be found on the Department website at: https://dnr.wi.gov/topic/surfacewater/orwerw.html.
2.7.3 The permittee may not establish a new storm water discharge of pollutants directly to an ORW or an ERW unless the discharge of pollutants is equal to or less than existing levels of pollutants immediately upstream of the discharge site. The storm water pollution prevention plan required under section 3 of this permit shall include practices designed to meet this requirement for new discharges.
2.7.3.1 "New storm water discharge" or "new discharge" means a storm water discharge that would first occur after the permittee's Start Date of coverage under this permit to a surface water to which the facility did not previously discharge storm water, and does not include an increase in a storm water discharge to a surface water to which the facility discharged on or before coverage under this permit.
2.7.4 The permittee may increase an existing storm water discharge directly to an ERW only if the increased discharge will not cause a significant lowering of water quality and the discharge is to accommodate to important economic or social development.
Page 12 of 27 WPDES Permit No. WI-S067857-5
2.7.5 The permittee may increase an existing storm water discharge to an ORW only if the increased discharge of pollutants is equal to or less than the background levels of the pollutant upstream of the discharge and the discharge is to accommodate to important economic or social development.
2.8 Impaired Water Bodies and Total Maximum Daily Load Requirements
2.8.1 "Pollutant(s) of concern" means a pollutant that is contributing to the impairment of a water body.
2.8.2 By February 15th of each calendar year, the permittee shall perform an annual check to determine whether its facility discharges a pollutant of concern via storm water to an impaired water body listed in accordance with Section 303 (d) (1) of the Federal Clean Water Act, 33 USC 1313 (d) (1) (C), and the implementing regulation of the U.S. Environmental Protection Agency (USEPA), 40 CFR 130.7 (c) (1). Impaired waters are those listed as not meeting applicable surface water quality standards. The results of the annual check shall be documented with the Annual Facility Site Compliance Inspection required under section 4.3.1 of this permit.
Note: The Department updates the list approximately every two years. The updated list is effective upon approval by the USEPA. The current list may be found on the Department website at: https://dnr.wi.gov/topic/impairedwaters/.
2.8.3 A permittee that discharges a pollutant of concern via storm water to an impaired water body shall, within 180 days of the annual check that determines the facility discharges to an impaired water body, include a written section in the storm water pollution prevention plan that specifically identifies source area pollution prevention controls and storm water best management practices that will collectively be used to reduce, with the goal of eliminating, the storm water discharge of pollutant(s) of concern that contribute to the impairment of the water body and explain why these controls and practices were chosen as opposed to other alternatives. Changes identified in the storm water pollution prevention plan shall be implemented with the 180-day timeframe.
Note: For a permittee that discharges a pollutant of concern via storm water to an impaired water body, amending the storm water pollution prevention plan will be required after the initial annual check and if subsequent annual checks indicate additional pollutants of concern have been added, additional water bodies have been designated as impaired, or other relevant changes to the designation have occurred.
2.8.4 The permittee may not establish a new storm water discharge of a pollutant of concern to an impaired water body or significantly increase an existing discharge of a pollutant of concern to an impaired water body unless the new or increased discharge does not contribute to the receiving water impairment, or the discharge is consistent with a State and Federal approved total maximum daily load (TMDL) allocation for the impaired water body.
2.8.4.1 "New storm water discharge" or "new discharge" has the meaning given in section 2.7.3.1 of this permit.
2.8.5 By February 15th each calendar year, the permittee shall perform an annual check to determine whether its facility discharges a pollutant of concern via storm water to a water body included in a State and Federal approved TMDL. If so, the permittee shall assess whether any TMDL wasteload allocation for the facility's discharge is being met through the existing pollution prevention controls and storm water best management practices or whether additional controls or treatment are necessary and feasible. The assessment of the feasibility of additional controls or treatment shall focus on the ability to improve
Page 13 of 27 WPDES Permit No. WI-S067857-5
pollution prevention and treatment system effectiveness and the adequacy of implementation and maintenance of the additional controls or treatment. The results of the annual check shall be documented with the Annual Facility Site Compliance Inspection required under section 4.3.1 of this permit.
Note: The current State and Federal approved TMDLs may be found on the Department website at: https://dnr.wi.gov/topic/tmdls/.
2.8.6 Within 180 days of the annual check that determines the facility discharges to a TMDL allocated water body, a permittee that is included in a State and Federal approved TMDL shall submit to the Department a proposed implementation plan for the storm water discharge that meets the requirements of the State and Federal approved TMDL wasteload allocation for the facility. The proposed TMDL implementation plan shall specify any feasible pollution prevention and treatment improvements that could be made and specify any revisions or redesigns that could be implemented to increase the effectiveness of the permittee's storm water pollution prevention controls and treatment practices. The TMDL implementation plan shall also specify a time schedule for implementation of the improvements, revisions or redesigns necessary to meet the wasteload allocation for the facility. If a specific wasteload allocation has not been assigned to the facility under a TMDL, compliance with this permit shall be deemed to be in compliance with the TMDL.
2.9 Fish and Aquatic Life Waters
2.9.1 The permittee shall determine whether it will have a storm water discharge to a fish and aquatic life water as defined in s. NR 102.13, Wis. Adm. Code.
Note: Most receiving waters of the state are classified as a fish and aquatic life waters and this classification includes all surface waters of the state except ORWs, ERWs, Great Lakes system waters and variance water identified within ss. NR 104.05 through 104.10, Wis. Adm. Code. The Department may be consulted if the permittee is not certain of the classification.
2.9.2 The permittee may not establish a new storm water discharge of pollutants to a fish and aquatic life water if the discharge will result in the significant lowering of water quality of the fish and aquatic life water. Significant lowering of water quality is defined within ch. NR 207, Wis. Adm. Code.
2.9.2.1 "New storm water discharge" or "new discharge" has the meaning given in section 2.7.3.1 of this permit.
2.9.3 If the permittee's facility has an existing storm water discharge to a fish and aquatic life water, it may not increase the discharge of pollutants if the increased discharge would result in a significant lowering of water quality.
2.9.4 Any increased or new discharge of storm water authorized under this permit shall be to accommodate to important economic or social development.
2.10 Toxic Pollutants In accordance with s. NR 102.12 Wis. Adm. Code, a new discharge and increased discharge as defined in ch. NR 207, Wis. Adm. Code, of persistent, bioaccumulating toxic substances to the Great Lakes waters or their tributaries shall be avoided or limited to the maximum extent practicable. Any new or increased discharge of these substances is prohibited unless the permittee certifies that the new or increased discharge is necessary after utilization of best technology in process or control using waste minimization, pollution prevention, municipal pretreatment programs, material substitution or other means of commercially available technologies which have demonstrated capability for similar applications.
Page 14 of 27 WPDES Permit No. WI-S067857-5
2.11 Minimum Source Area Control Requirements All permittees shall comply with the following minimum source area control requirements. The Storm Water Pollution Prevention Plan required under section 3 shall identify how each source area control requirement will be met. Source area controls shall be utilized to prevent storm water from becoming contaminated at the facility. Structural source area controls that are either proposed or in place at the facility shall be indicated on the facility drainage base map described in section 3.3.2.2 of this permit. The permittee shall:
2.11.1 Minimize exposure of pollutants associated with the potential sources of storm water contamination identified in section 3.3.2.4 of this permit.
2.11.2 Use good house-keeping measures such as sweeping, appropriate storage, and proper management of waste materials and dumpsters/compactors.
2.11.3 Maintain both structural and non-structural control measures, institute preventive maintenance for vehicles and equipment, and perform routine visual inspections.
2.11.4 Minimize the potential for leaks, spills, and other releases that may contaminate storm water, and institute spill prevention and response measures, including spill reporting described in section 6.5 of this permit.
2.11.5 Stabilize areas of bare soil with vegetation or through permanent land cover to control soil erosion, or when that is not possible, implement best management practices to meet the requirements of section 3.3.2.8.2 of this permit.
2.11.6 Construct and maintain salt storage facilities so that neither precipitation nor storm water runoff can come into contact with the stored salt in order to minimize pollutant discharges.
2.11.6.1 Salt storage piles shall be constructed on an impervious, curbed surface to prevent salt or brine from passing through the base and reaching waters of the state. Salt storage piles shall be enclosed by a building or structure with walls and a cover sufficient to prevent contact between precipitation and the salt and to prevent wind from eroding the salt or carrying any amount of the substance into potential contact with the waters of the state. Alternatively, for permittees that use brine and have salt storage piles on impervious curbed surfaces, install a means of diverting contaminated storm water to a brine treatment system for process use.
2.11.6.2 Any salt spillage resulting from activities such as loading or unloading, shall be immediately cleaned up to minimize contact with storm water.
2.11.7 Train and raise awareness of employees as appropriate on storm water pollution prevention, the requirements of this permit, and their specific responsibilities in implementing any of the requirements, practices, or activities of this permit or the Storm Water Pollution Prevention Plan.
2.11.8 Evaluate the facility for the presence of non-storm water discharges as specified in section 4.2. of this permit.
Note: This permit does not cover non-storm water discharges. See section 2.3. 2.11.9 Minimize dust and off-site tracking of soil, raw materials, intermediate products, final products, or waste materials.
Page 15 of 27 WPDES Permit No. WI-S067857-5
2.11.10 If applicable, use a combination of storm water contact control or containment, drainage controls, or diversions to control SARA Title III Section 313 "Water Priority Chemicals" (42 USC s. 11023 (c)) potentially discharged through the action of storm water runoff, leaching, or wind.
2.12 Compliance with Runoff Management Performance Standards The owner or operator of a facility subject to the performance standards in s. NR 151.12 or ss. NR 151.121 to 151.128, Wis. Adm. Code, shall describe in the Storm Water Pollution Prevention Plan the best management practices necessary to maintain compliance with the applicable performance standards in s. NR 151.12 or ss. NR 151.121 to 151.128, Wis. Adm. Code, for those areas that are described in s. NR 151.12(2) or s. NR 151.121(2), Wis. Adm. Code, respectively. Best management practices installed to meet the performance standards in s. NR 151.12 or s. NR 151.121 to 151.128, Wis. Adm. Code, shall be maintained to meet the treatment capability as originally designed.
2.13 Post-Construction Performance Standards for Landfills For landfills, post-construction storm water best management practices constructed after the effective date of this permit shall be in compliance with the performance standards in ss. NR 151.122 and NR 151.123, Wis. Adm. Code.
Note: The infiltration performance standard in s. NR 151.124, Wis. Adm. Code, does not apply to landfills.
3. STORM WATER POLLUTION PREVENTION PLAN
Page 16 of 27 WPDES Permit No. WI-S067857-5
3.1 Storm Water Pollution Prevention Plan Required In accordance with s. NR 216.27, Wis. Adm. Code, and section 3.3 of this permit, the owner or operator of a facility requiring coverage under this permit shall prepare a Storm Water Pollution Prevention Plan (SWPPP) prior to applying for permit coverage under s. NR 216.22, Wis. Adm. Code.
3.2 Incorporation by Reference When plans are developed or activities conducted in accordance with other federal, state or local regulatory programs that meet the requirements of section 3.3.2 of this permit, the plans may be incorporated by the permittee into the SWPPP by reference.
3.3 Purpose and Content of a Storm Water Pollution Plan
3.3.1 Purpose of the Plan Any SWPPP prepared to comply with this permit shall do all of the following:
3.3.1.1 Identify sources of storm water and non-storm water contamination to the storm water drainage system.
3.3.1.2 Identify and prescribe appropriate "source area control" type best management practices designed to prevent storm water contamination from occurring.
3.3.1.3 Identify and prescribe "storm water treatment" type best management practices to reduce pollutants in contaminated storm water prior to discharge.
3.3.1.4 Prescribe actions needed either to bring non-storm water discharges under an appropriate WPDES permit or to remove these discharges from the storm drainage system.
3.3.1.5 Prescribe an implementation schedule so as to ensure that the storm water management actions prescribed in the SWPPP are carried out in a timely manner and evaluated on a regular basis.
3.3.2 Required Plan Content The SWPPP shall contain, at a minimum, the following items and provisions:
3.3.2.1 Pollution Prevention Individual The SWPPP shall identify by job title the specific individual who has primary responsibility for all aspects of SWPPP development and implementation and identify any other individuals concerned with SWPPP development or implementation, and their respective roles. The specific individual who has primary responsibility shall develop, evaluate, maintain and revise the SWPPP, and carry out the specific management actions identified in the SWPPP, including maintenance practices, monitoring activities, preparing and submitting reports, recordkeeping, and serving as facility contact for the Department.
3.3.2.2 Facility Site Description and Drainage Base Map The SWPPP shall contain a short summary of the major activities conducted at various locations throughout the facility. The SWPPP shall also include a facility drainage base map depicting all of the following:
3.3.2.2.1 How storm water drains on, through and from the facility to groundwater, surface water, or wetlands.
3.3.2.2.2 The facility property boundaries.
Page 17 of 27 WPDES Permit No. WI-S067857-5
3.3.2.2.3 The storm drainage collection and disposal system including all surface and subsurface conveyances.
3.3.2.2.4 Any secondary containment structures.
3.3.2.2.5 The location of all outfalls that discharge channelized flow to groundwater, surface water or wetlands, including outfalls recognized as permitted outfalls under another WPDES permit, numbered for reference.
3.3.2.2.6 The drainage area boundary for each outfall.
3.3.2.2.7 The surface area in acres draining to each outfall, including the percentage that is impervious such as paved, roofed or highly compacted soil, and the percentage that is pervious such as grassy areas and woods.
3.3.2.2.8 Existing structural storm water controls.
3.3.2.2.9 The name and location of receiving waters.
3.3.2.2.10 The location of activities and materials that have the potential to contaminate storm water.
3.3.2.3 Summary of Existing Sampling Data or Observations The SWPPP shall summarize any results of available storm water sampling data or other observations that characterize the quality of storm water discharges or identifying sources of storm water contamination. Available data that characterizes the quality of storm water discharges under dry weather flow conditions shall also be included, except when such data has been or will be reported to the Department under another WPDES permit.
3.3.2.4 Potential Sources of Storm Water Contamination The SWPPP shall identify any significant pollutants or activities associated with the storm water pollution source areas identified in this permit. When possible, specific pollutants likely to be present in storm water as a result of contact with specific materials shall also be listed. The SWPPP shall identify all potential source areas of storm water contamination, including but not limited to:
3.3.2.4.1 Outdoor manufacturing areas.
3.3.2.4.2 Rooftops contaminated by industrial activity, exhaust vents, or a pollution control device.
3.3.2.4.3 Industrial plant yards.
3.3.2.4.4 Storage and maintenance areas for material handling equipment.
3.3.2.4.5 Immediate access roads and rail lines owned or operated by the permittee.
3.3.2.4.6 Material handling sites including storage, loading, unloading, transportation, or conveyance of any raw material, finished product, intermediate product and byproduct or waste areas.
Page 18 of 27 WPDES Permit No. WI-S067857-5
3.3.2.4.7 Storage areas (including tank farms) for raw materials, finished and intermediate products.
3.3.2.4.8 Disposal or application of wastewater.
3.3.2.4.9 Areas containing residual pollutants from past industrial activity.
3.3.2.4.10 Areas of significant soil erosion, including areas of bare soil.
3.3.2.4.11 Refuse sites.
3.3.2.4.12 Vehicle maintenance and cleaning areas.
3.3.2.4.13 Washing areas for equipment, vehicles, containers, or other items.
3.3.2.4.14 Shipping and receiving areas.
3.3.2.4.15 Manufacturing buildings.
3.3.2.4.16 Residual treatment, storage, and disposal sites.
3.3.2.4.17 Any other areas capable of contaminating storm water runoff.
3.3.2.5 Status of Non-Storm Water Discharges to the Storm Sewer The SWPPP shall identify all known contaminated and uncontaminated sources of non-storm water discharges to the storm sewer system or waters of the state and indicate which are covered by WPDES permits. The SWPPP shall contain the results of the non-storm water discharge monitoring required by s. NR 216.28, Wis. Adm. Code. If monitoring is not feasible due to the lack of suitable access to an appropriate monitoring location, the SWPPP shall include a statement that the monitoring could not be conducted and an explanation of the reasons why.
3.3.2.6 Source Area Control Best Management Practices The SWPPP shall rely, to the maximum extent practicable, on the use of source area control best management practices designed to prevent storm water from becoming contaminated at the facility. Source area control best management practices that are either proposed or in place at the facility shall be indicated on the facility drainage base map described in section 3.3.2.2 of this permit. The SWPPP shall provide for the use of the following source area control best management practices:
3.3.2.6.1 Activities to stabilize areas of bare soil with vegetation or through permanent land cover to control soil erosion.
3.3.2.6.2 Good house-keeping measures, preventive maintenance measures, visual inspections, spill prevention and response measures, and employee training and awareness.
3.3.2.6.3 Manage salt storage facilities so that neither precipitation nor storm water runoff can come into contact with the stored salt in order to minimize pollutant discharges. Alternatively, for permittees that use brine and have salt storage piles on impervious curbed surfaces, install and
Page 19 of 27 WPDES Permit No. WI-S067857-5
maintain a means of diverting contaminated storm water to a brine treatment system for process use.
3.3.2.6.4 Use of a combination of storm water contact control or containment, drainage controls, or diversions to control SARA Title III Section 313 "Water Priority Chemicals" (42 USC s. 11023 (c)) potentially discharged through the action of storm water runoff, leaching, or wind.
3.3.2.7 Residual Pollutants The SWPPP shall identify pollutants that are likely to contaminate storm water discharges to waters of the state following implementation of source area control best management practices. Past sampling data collected at the facility or at sufficiently similar outfalls at other facilities may be used in making this determination. At a minimum, the following pollutants shall be considered for their potential to contaminate storm water:
3.3.2.7.1 Any pollutant for which an effluent limitation is contained in any discharge permit issued to the permittee, for this facility, by the Department.
3.3.2.7.2 Any pollutant contained in a categorical effluent limitation or pre-treatment standard to which the facility is subject.
3.3.2.7.3 Any SARA Title III Section 313 "Water Priority Chemical" (42 USC s. 11023 (c)) for which the permittee, for this facility, has reporting requirements and which has the potential for contaminating storm water.
3.3.2.7.4 Any other toxic or hazardous pollutants from present or past activity at the site that remain in contact with precipitation or storm water and which could be discharged to the waters of the state, and which are not regulated by another environmental program.
3.3.2.7.5 Any of the following parameters which might be present in significant concentrations: Oil and grease, pH, total suspended solids, 5-day biological oxygen demand, and chemical oxygen demand.
3.3.2.8 Storm Water Treatment Best Management Practices When source area control best management practices are not practicable or are inadequate to control storm water pollution, or when the Department determines source area control best management practices are inadequate to achieve a water quality standard, the SWPPP shall prescribe appropriate storm water treatment practices as needed to reduce the pollutants in contaminated storm water prior to discharge to waters of the state. Proposed or existing storm water treatment practices shall be shown on the facility drainage basin map described in section 3.3.2.2 of this permit. The SWPPP shall provide for the following types of storm water treatment practices:
3.3.2.8.1 Storm water significantly contaminated with petroleum products shall be treated for oil and grease removal by an adequately sized, designed, and functioning wastewater treatment device. Coverage under a separate individual or general permit is required for discharges of storm water from oil/water treatment devices. Under s. 281.41, Wis. Stats., prior Department approval of plans for oil and grease removal devices may be required.
3.3.2.8.2 Storm water discharges contaminated by sediment eroding from areas of bare soil that cannot be stabilized by pavement, gravel, vegetation, or other permanent land cover shall be treated by best management practices designed, installed and maintained to achieve compliance with the
Page 20 of 27 WPDES Permit No. WI-S067857-5
construction site performance standards in s. NR 151.11(6m), Wis. Adm. Code, and in accordance with the Department's Construction Site Erosion and Sediment Control Technical Standards.
Note: The Construction Site Erosion and Sediment Control Technical Standards are available at the following Department website: https://dnr.wi.gov/topic/stormwater/standards/const_standards.html.
3.3.2.9 Facility Monitoring The SWPPP shall include provisions for complying with the monitoring requirements specified in s. NR 216.28, Wis. Adm. Code, and section 4 of this permit. The SWPPP shall include a checklist of inspections to be made during the annual facility site inspection required by s. NR 216.28(2), Wis. Adm. Code. The SWPPP shall also identify for each outfall the type of monitoring that will be conducted, such as non-storm discharge monitoring and storm water discharge quality inspections.
3.3.2.10 SWPPP Implementation Schedule The SWPPP shall include an implementation schedule for the requirements of this permit that meet the compliance timeframes set forth in this permit.
3.3.2.11 Certification and Signature The SWPPP shall be signed in accordance with s. NR 216.22(7), Wis. Adm. Code, and contain the following statement:
"I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations."
3.4 Amending a SWPPP Unless an alternative timeframe is specified by the Department, the permittee shall amend and submit the SWPPP to the department within 30 days of the occurrence of any of the following circumstances:
3.4.1 When expansion, production increases, process modifications, changes in material handling or storage, or other activities are planned which will result in significant increases in the exposure of pollutants to storm water discharged either to waters of the state or to storm water treatment devices. The amendment shall contain a description of the new activities that contribute to the increased pollutant loading, planned source control activities that will be used to control pollutant loads, an estimate of the new or increased discharge of pollutants following treatment, and when appropriate, a description of the effect of the new or increased discharge on existing storm water treatment facilities.
3.4.2 The comprehensive annual facility site compliance inspection, quarterly visual inspection of storm water quality, or other information reveals that the provisions of the SWPPP are ineffective in controlling storm water pollutants discharged to waters of the state.
3.4.3 Upon written notice that the Department finds the SWPPP to be ineffective in achieving the conditions of this permit.
3.5 Storm Water Discharges to Outstanding and Exceptional Resource Waters If the permittee's industrial storm water will discharge to an outstanding resource water or exceptional resource water, the permittee shall include a written section in the SWPPP that discusses and identifies the management practices and control measures the permittee will implement to prevent the discharge of any pollutant(s) in excess of the background
Page 21 of 27 WPDES Permit No. WI-S067857-5
level within the water body. This section of the permittee's plan shall specifically identify control measures and practices that will collectively be used to prevent the discharge of pollutants in excess of the background level within the water body.
4. MONITORING REQUIREMENTS
Page 22 of 27 WPDES Permit No. WI-S067857-5
4.1 Purpose Monitoring includes site inspections and non-storm water discharge assessments. The purpose of monitoring is to evaluate storm water outfalls for the presence of non-storm water discharges, and to evaluate the effectiveness of the permittee's pollution prevention activities in controlling contamination of storm water discharges.
4.2 Evaluation of Non-Storm Water Discharges
4.2.1 The permittee shall evaluate all storm water outfalls for non-storm water contributions to the storm drainage system for the duration of this permit. Any monitoring shall be representative of non-storm water discharges from the facility. Evaluations shall take place during dry periods, and may include either end of pipe screening or detailed testing of the storm sewer collection system. Either of the following monitoring procedures is acceptable:
4.2.1.1 A detailed testing of the storm sewer collection system may be performed. Acceptable testing methods include dye testing, smoke testing, or video camera observation. The Department may require a re-test after 5 years or a lesser period as deemed necessary by the Department.
4.2.1.2 End of pipe screening shall consist of visual observations made at least twice per year at each outfall of the storm sewer collection system. Instances of dry weather flow, stains, sludge, color, odor, or other indications of a non-storm water discharge shall be recorded.
Note: The department recommends compiling photographic documentation of visual observations made during non-storm water discharge evaluations.
4.2.2 In addition to maintaining results on-site at the facility, results of the non-storm water evaluations shall be included in the SWPPP required in section 3.3.2.5 of this permit and the Annual Facility Site Compliance Inspection report required in section 5.2 of this permit. Information reported shall include the date of testing, test method, outfall location, testing results, and potential significant sources of non-storm water discovered through testing. Upon discovering non-storm water flows that are not covered under another WPDES permit, the permittee shall either immediately seek coverage under another permit from the Department or eliminate the non-storm water flow.
4.2.3 Any permittee unable to evaluate an outfall for non-storm water discharges shall sign a statement certifying that this requirement could not be complied with, and include a copy of the statement in the SWPPP and the Annual Facility Site Compliance Inspection report. The statement shall be submitted to the Department within 30 days after the permittee determines that it is unable to evaluate an outfall.
4.3 Evaluation of Storm Water Discharges The permittee shall evaluate storm water outfalls for storm water contributions to the storm drainage system. Any monitoring shall be representative of storm water discharges from the facility.
4.3.1 Annual Facility Site Compliance Inspection Permittees shall perform and document the results of an Annual Facility Site Compliance Inspection (AFSCI). The AFSCI shall be adequate to verify that the site drainage conditions and potential pollution sources identified in the SWPPP remain accurate, and that the best management practices prescribed in the SWPPP are being implemented, properly operated and adequately maintained. Information reported shall include the inspection date, inspection personnel, scope of the inspection, major observations, and revisions needed in the SWPPP.
The AFCSI Report Form can be accessed at the following website: https://dnr.wi.gov/files/PDF/forms/3400/3400-176.pdf
Page 23 of 27 WPDES Permit No. WI-S067857-5
4.3.2 Quarterly Visual Monitoring Permittees shall perform and document quarterly visual inspections of storm water discharge quality at each storm water discharge outfall. Inspections shall be conducted within the first 30 minutes of discharge or as soon thereafter as practical, but not exceeding 60 minutes. The inspections shall include any observations of color, odor, turbidity, floating solids, foam, oil sheen, or other obvious indicators of storm water pollution. Information reported shall include the inspection date, inspection personnel, visual quality of the storm water discharge, and probable sources of any observed storm water contamination.
The Quarterly Visual Inspection Form can be accessed at the following website: https://dnr.wi.gov/files/PDF/forms/3400/3400-176a.pdf
4.3.3 Monitoring Waivers The Department may waive specific monitoring requirements for the following reasons:
4.3.3.1 The permittee indicates that either an employee could not reasonably be present at the facility at the time of the snowmelt or runoff event, or that attempts to meet the monitoring requirement would endanger employee safety or well-being.
4.3.3.2 The permittee indicates that there were no snow melt or runoff events large enough to conduct a quarterly visual inspection at an outfall. A waiver is automatically granted for a quarter where the permittee sufficiently documents and retains records demonstrating that there were no snow melt or runoff events large enough to conduct a quarterly visual inspection at the facility during that quarter. Documentation and records used to qualify for an automatic waiver shall be submitted to the Department upon request.
4.3.3.3 The facility is inactive or remote facility (such as an inactive mining operation) where the permittee demonstrates that monitoring and inspection activities are impractical or unnecessary. At a minimum, the Department shall establish an alternative requirement that the permittee make site inspections by a qualified individual at least once in every 3-year period.
4.3.3.4 The permittee demonstrates to the Department's satisfaction that the sources of storm water contamination are outside of the permittee's property boundary and are not associated with the permittee's activities. The demonstration shall be presented in the SWPPP or AFSCI report and submitted to the Department for evaluation.
5. COMPLIANCE AND REPORTING REQUIREMENTS
Page 24 of 27 WPDES Permit No. WI-S067857-5
5.1 SWPPP Compliance and Reporting Requirements
5.1.1 An owner or operator of a facility requiring coverage under this permit shall prepare a Storm Water Pollution Prevention Plan (SWPPP) prior to applying for permit coverage under s. NR 216.22, Wis. Adm. Code, and shall submit the SWPPP summary to the Department when applying for coverage under this permit. For existing facilities that previously operated without required permit coverage and without a SWPPP as required, the owner or operator shall immediately develop a SWPPP, submit the SWPPP summary to the Department when applying for coverage under this permit, and implement the SWPPP to achieve compliance with this permit in the shortest practicable time. A facility has the option to submit their full SWPPP in lieu of the SWPPP summary when applying for coverage.
5.1.2 The SWPPP shall conform to the requirements specified in s. NR 216.27 (3), Wis. Adm. Code, and section 3.3 of this permit.
5.1.3 The SWPPP shall be kept at the facility and made available to the Department for inspection and copying upon request. If storm water discharges from the facility enter a municipal separate storm sewer system covered under a storm water permit pursuant to Subchapter I of ch. NR 216, Wis. Adm. Code, the SWPPP shall be made available to the owner or operator of the municipal separate storm sewer system for inspection and copying upon request.
5.1.4 Unless an alternate implementation schedule is specified by the Department, the SWPPP shall be implemented in accordance with the implementation schedule developed under section 3.3.2.10 of this permit.
5.1.5 The permittee shall keep the SWPPP current and amend it as necessary to correct deficiencies in the SWPPP as they are identified. The permittee shall amend the SWPPP and submit it to the Department in the event of any facility operational changes that may result in additional significant storm water contamination.
5.2 Monitoring Compliance and Reporting Requirements
5.2.1 The permittee shall conduct the first Annual Facility Site Compliance Inspection (AFSCI) within 12 months of the Start Date of coverage under this general permit. Subsequent AFSCIs shall be conducted and AFSCI reports prepared by the permittee by the anniversary of the Start Date for each year of coverage under this permit. Reports shall be written on forms available from the Department and shall contain information from the AFSCI, the quarterly visual inspection, and the non-storm water evaluation. Copies of all AFSCI reports, quarterly visual inspections and nonstorm water monitoring reports shall be maintained on site at the facility and made available to the Department for inspection and copying upon request for the duration of permit coverage.
Note: The AFSCI Report form, Quarterly Visual Inspection form, and Storm Water Chemical Analysis Report form are available on the Department website at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html.
5.2.2 Quarterly visual inspections of storm water discharge quality shall be conducted by the permittee four times annually by the anniversary date of Start Date of coverage under the permit.
Page 25 of 27 WPDES Permit No. WI-S067857-5
5.3 Discharges to Regulated Municipal Separate Storm Sewer Systems
5.3.1 Permittees regulated under this permit with storm water discharges and non-storm water discharges entering a municipal separate storm sewer system covered under a storm water permit pursuant to Subchapter I of ch. NR 216, Wis. Adm. Code, shall provide information on these discharges to the owner or operator of the municipal separate storm sewer system upon request. Information the permittee shall provide includes the area or sub-areas of the facility draining to the municipal separate storm sewer system, the nature of industrial activity and potential storm water contamination sources in the areas draining to the system, the nature and number of non-storm water discharges to the system, storm water best management practices employed at the facility and their effectiveness at pollutant removal, storm water monitoring data, and copies of the SWPPP and AFSCI reports.
5.3.2 Upon discovering a previously unknown non-storm water discharge to the municipal separate storm sewer system that is not authorized to discharge under a required WPDES permit or that is an illicit discharge as defined by s. NR 216.002(11), Wis. Adm. Code, the permittee shall immediately report the discharge to the owner or operator of the municipal separate storm sewer system.
5.3.3 The permittee shall immediately report spills or dumping of materials that enter the municipal separate storm sewer system to the owner or operator of the system.
5.3.4 In accordance with the owner or operator's established authority to control discharges to its municipal separate storm sewer system, the permittee shall assist the owner or operator of the system with detecting and eliminating illicit discharges to the system to the maximum extent practicable if the owner or operator finds that the source of an illicit discharge may originate from the permittee's facility.
Page 26 of 27 WPDES Permit No. WI-S067857-5
6. GENERAL CONDITIONS The general conditions in s. NR 205.07(1), (3), and (5), Wis. Adm. Code, are hereby incorporated by reference into this permit, except for s. NR 205.07(1)(n) and(3)(b), Wis. Adm. Code. Under s. NR 205.08(9), Wis. Adm. Code, dischargers covered under a storm water general permit are not required to submit an application for reissuance unless directed to do so by the Department under s. NR 216.22(9), Wis. Adm. Code. The requirements for spill reporting are in section 6.5 below.
Note: Chapter NR 205 is available at the following website: https://docs.legis.wisconsin.gov/code/admin_code/nr/200.
6.1 Work near Surface Waters and Wetlands Activities performed in wetland areas, in floodplains, or near shorelands may require permits or approvals through applicable state law, state regulations, or county or local ordinances. Additionally, state permits or contracts required by chs. 30, 31 and 87, Wis. Stats. and s. 281.36, Wis. Stats. (or Wisconsin Administrative Code promulgated under these laws), and federal permits may be applicable.
6.2 Continuation of the Expired General Permit As provided in s. NR 205.08(9), Wis. Adm. Code, and s. 227.51, Wis. Stat., the terms and conditions of this general permit shall continue to apply until this general permit is reissued or revoked or until an individual permit is issued for the discharge to which the general permit applied.
6.3 Petition to Move to Individual Permit Coverage Any person may submit a written request to the department to withdraw coverage under this general permit and to replace it with an individual storm water permit under s. NR 216.25(4), Wis. Adm. Code.
6.4 Liabilities under Other Laws Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties to which the permittee is or may be subject under Section 311 of the federal Clean Water Act (33 USC s. 1321), any applicable federal, state, or local law or regulation under authority preserved by Section 510 of the Clean Water Act (33 USC s. 1370).
6.5 Severability The provisions of this permit are severable, and if any provisions of this permit or the application of any provision of this permit to any circumstance is held invalid the remainder of this permit shall not be affected thereby.
6.6 Spill Reporting The permittee shall notify the Department immediately of any release or spill of a hazardous substance to the environment in accordance with s. 292.11, Wis. Stats., and ch. NR 706, Wis. Adm. Code.
Note: The 24-hour toll free spills hotline number is (800) 943-0003. Information about hazardous substance spills is available from the Department's website at: https://dnr.wi.gov/topic/Spills/.
6.7 Submitting Records Any forms or reports submitted to the Department of Natural Resources in accordance with this permit shall be submitted via the Department's Water ePermitting System available at: https://dnr.wi.gov/topic/stormwater/industrial/forms.html.
6.8 Enforcement Any violation of s. 283.33, Wis. Stats., ch. NR 216, Wis. Adm. Code, or this permit is enforceable under s. 283.89, Wis. Stats.
6.9 Permit Fee A storm water discharge permit fee shall be paid annually for each industrial facility covered under this permit. The permittee will be billed by the Department annually in May of each year and the fee is
Page 27 of 27 WPDES Permit No. WI-S067857-5
due by June 30 of each year in accordance with s. NR 216.30, Wis. Adm. Code. A permittee may be referred to the Wisconsin Department of Revenue for the collection of any unpaid storm water fee.