- observed pressure, u = (Approximately the same as but not identical with relative humidity. See Chapter 1).
Dehumidify: To reduce, by any process, the density of'water vapor within a given
space.
-' .
Dehydrate: To separate or to remove water in all forms from matter. Liquid water, hygroscopic water, and water of crystallization or water of hydration.are included.
"Density: The weight of a unit volume, expressed in pounds per cubic foot, d = W -fe V.
Dew-Point Temperature: ,The temperature corresponding to saturation (KXFper cent relative humidity) lor a given moisture content.
Direct-Indirect Heating Unit: A heating unit located in the room or space to be heated and partially enclosed, the enclosed portion being used to heat air which enters from outside the room.
Direct Radiator: Same as Radiator.
.
Direct-Return System (Hot Water): A hot water system in which the water, after it
has passed through a heating unit, is returned to the boiler along a direct path so that the total distance traveled by the water is the shortest feasible, and so that there are considerable differences in the'lengths of the several circuits composing the system.
Down-Feed One-Pipe Riser (Steam): A pipe which carries steam downward to the heating units and into which the condensation from the heating units drains.
Down-Feed System (Steam): A steam heating system in which the supply mains are above the level of the heating units which they serve.
Draft Head (Side Outlet Enclosure): The height of a gravity convector between the
bottom of the heating unit and the bottom of the air outiet opening. (Top Outlet En closure): The height of a gravity convector between the bottom of the heating unit and the top of the enclosure.
Drip: A pipe, or a steam trap and a pipe, considered as a unit, which conducts con densation from the steam side of a piping system to the water or return side of the system.
Dry: (a) To separate or to remove liquid water or water vapor from matter, (b) To separate or to remove any readily condensible vapor from other matter.
Dry Air: In psychrometric work, dry air is defined as air without water vapor. This, state, though not obtained practically, is used as the basis of calculations.
Dry-Bulb Temperature: The temperature indicated by a standardized thermometer after correction for radiation, etc.
Dry Return: A return pipe in a steam heating system which carries both water of condensation and air. The dry return is above tne level of the water line in the boiler in a gravity system. (See Wet Return.)
Dust: Solid material in a finely divided state, the particles of which are large and heavy enough to fall with increasing velocity, due to gravity in still air. For instance,
particles of fine sand or grit, the average diameter of which is approximately 0.01 centimeter, such as are blown on a windy day, may be called dust.
Dynamic Head or Pressure: Same as Total Pressure.
Effective Temperature: An arbitrary index which combines into a single value. the effect of temperature, humidity, and movement of air on the degree of warmth or cold
felt by the human body. The numerical value is that of the temperature of still, satu rated air which would induce an identical sensation of warmth.
Enthalpy: Enthalpy was formerly called heat content, sometimes total heat. It is a
thermodynamic property which serves as a measure of the quantity of thermal energy conceded by a fluid in steady flow. In a non-flow process the increase of enthalpy equals
the quantity of heat absorbed provided pressure is constant. Specific enthalpy is the ratio of total enthalpy to total weight, that is, enthalpy per unit weight of substance, Btu per pound.
Entropy: Entropy is the ratio of the heat added to a substance to the absolute temperature at which it is-added. It is a thermodynamic property which, for-practical
Terminology___________'.789
purposes, is best defined by stating its principal functions: (1) during a reversible adiabatic change of state, entropy .is constant; (2) during a reversible isothermal change of state, the heat absorbed is equal to absolute temperature times change of entropy. Specific entropy is the ratio of total entropy-to total weight, that is, entropy per unit weight, Btu per degree Fahrenheit per pound.
Equivalent Evaporation; The amount of water a boiler would evaporate, in pounds per hour, if it received feed water at 212 F and vaporized it at the same temperature and atmospheric pressure.
Estimated Design Load: The sum of the heat emission of the equivalent direct radia tion to be installed plus the allowance for heat loss of the connecting piping plus the heat requirements of any auxiliary apparatus connected with the system.
Estimated Maximum Load: The load stated in Btu per hour or equivalent direct radiation that has been estimated to be the greatest or maximum load that the boiler will be called upon to carry. (See Chapter 12).
Extended Heating Surface: See Heating Surface.
Extended Surface Heating Unit: A heating unit having a relatively large amount of extended surface which may be integral with the core containing the heating medium or assembled over such a core, making good thermal contact by pressure or by being soldered to the core or by both pressure and soldering. An extended surface heating unit is usually placed within an enclosure and therefore functions as a convector.
Fan Furnace System: See Warm Air Heating System.
Force: The action on a body which tends to change its relative condition as to rest or motion. F = (WV) -5- (gt).
Free Enthalpy: A thermodynamic property which serves as a measure of the available energy of a system with respect to surroundings at the same temperature and same pressure as that of the system. No process involving an increase in available energy can occur spontaneously. (See example on Free Enthalpy in Chapter 1.)
Fumes: Particles of solid matter resulting from such chemical processes as combus tion, explosion, and distillation, ranging from 0.1 to 1.0 micron in size.
Furnace: That part of a boiler or warm air heating plant in which combustion takes place. Also a complete heating unit for transferring heat from fuel being burned to the air supplied to a heating system.
Furnace Volume (Total): The total furnace volume for horizontal-return tubular boilers and water-tube boilers is the cubical contents of the furnace between the grate and: the first plane of entry into or between tubes. It therefore includes the volume behind the bridge wall as in ordinary horizontal-return tubular boiler settings, unless manifestly ineffective (*.., no gas flow taking place through it), as in the case of wasteheat boilers with auxiliary coal furnaces, where one part of the furnace is out of action when the other is being used. For Scotch or other internally fired boilers it is the cubical contents of the furnace, flues and combustion chamber, up to the plane of first entry into the tubes. (A.S.M.E. Power Test Codes, Series 1929.)
Gage Pressure: Pressure measured from atmospheric pressure as a base. Gage pressure may be indicated by a manometer which has one leg connected to the pressure source and the other exposed to atmospheric pressure.
Grate Area: The area of the grate surface, measured in square feet, to be used in estimating the rate of burning fuel. This area is construed to mean the area measured in the plane of the top surface of the grate, except that with special furnaces, such as those having magazine feed, or special shapes, the grate area shall be the mean area of the active part of the fuel bed taken perpendicular to the path of the gases through it. For furnaces having a secondary grate, such as those in double-grate down draft boilers, the effective area shall be taken as the area of the upper grate plus one-eighth of the area of the lower grate, both areas being estimated as previously defined.
Gravity Warm Air Heating System: See Warm Air Heating System.
Heat: That form of energy which flows from one body to another by virtue of a difference in temperature between the bodies.
Heating Medium: A substance such as water, steam, air, or furnace gas used to convey heat from the boiler, furnace or other source of heat or energy to the heating unit from which the heat is dissipated.