Document 06GOLd3zDed99bnDbjy5eevnM
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-JUN-1996
PAGE I OF 5
ELECTRICAL SAFETY AND RELIABILITY AUDIT CHECK LIST ELECTRICAL ROOMS
BUILDING NUMBER/LOCATION I.D. #:
CC $
Doors/Exits
Yes No N/A
1 . Are there two means of egress from the room?
2 . Are the doors equipped with good working panic
bars? [LPP]
3 . Do all doors open to the outside?
4 . Are the doors self closing?
5. Are there warning signs posted on the doors? (i.e. DANGER: HIGH VOLTAGE)
Are the Exit Doors identified with Exit Lights or Sign?
Doors/Exits Index Score
________--
-4--
Lighting
Yes No N/A
1. Is lighting in good condition and lighting level adequate?
2. Are all lamps burning?
3 . Is there a good working emergency lighting system? [LPP-356]
4 . Is the Exit Sign Lighting working?
Lighting Index Score
Environment
Yes No N/A
Is the air conditioning system in good working condition? (Temperature, Humidity)
Is the air conditioning system isolated for switch room service only?"
?DO
DO
A/p
045079
td*ntih
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02 14-JUN-1996
PAGE 2 OF 5
3. Is the noise level acceptable?
4 . Are measures taken to keep water/ice out of the room or cable cellar effective?
5. Are openings in the walls, ceilings, floor, or cable cellar properly sealed?
Environment Index Score:
2
Housekeeping
Yes No N/A
1. Is the room cle-an and uncluttered?
2. Is the broom?
Housekeeping Index Score
*
Acc ess
Yes No N/A
1. Is the: the eli
2 . Is the
Access
.ex Score:
3.
Drawings
Yes No N/A
1. Is SEOLD posted properly in the room?
2 . Are drawing accurate and up to hate?
/
Z___________
_
Drawings Index Score: ------------ `i--
DO A 04S020 CONFIDENTIAL
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-JUN-1996
PAGE 3 OF 5
Labeling
Yes No N/A
1. Is the room identified with a formalized building number?
2. is the equipment in the room adequately
labeled?
Labeling Index Score:
Fire Protection
Yes No N/A
1 . Is the room separated from control QOm with 2 hour fire barrier wall? [LPP]
2. Is there a smoke and/or fire detection system in the room? [LPP-356]
3. Is the Smoke and/or Fire Detection System annunciated?
_./___________
4. Are all wall-penetrations closed with Fire Stop materials? [LPP]
5. Is the room free of stored combustible materials ?
6. Are the proper fire extinguishers the room?
cated in
________
___________ j/1 _
/. Does room have fire retardant wails and doors
to oil-filled transformers or trecess area?
Fire Protection Index Score:
4
04^0?"'DO *
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-JUN-1996
PAGE 4 OF 5
BATTERY/UPS SYSTEMS
Yes No N/A
1 . Is there a preventive maintenance schedule for UPS systems. Battery Banks, and Battery Chargers?
2. Is the battery rack grounded?
3. Are the battery posts and terminals free of corrosion?
4 . Is the battery charger in good working condition?
5 . Is the battery room or location designed according no the appropriate standards?
y
6. Do batteries have the proper water level?
__ /y/Ar3atterv/UPS Systems Index Score:
Other
Yes No
1. Is there Flash protection clothing/equipment in the room?
jZ
2 . Has all process piping been routed outside the switch room?
3. Is there a written set of Electrical Emergency V
plans for various situations like loss of
power, fire, or smoke in the room? [LPP]
4 . Is there room to grow?
z
5. Is there a preventive maintenance schedule for the room?
6. Are the cable raceways in the room/cable cellar in good shape?
7 . Are the cable raceways in the room/cable cellar overloaded?
_z.
8 . Are all the cable raceways in the room/cable cellar properly loaded?
N/A
0 A a *
C0NFtkS2?
lA/.