CHAPTER 22
1949 Guide
Register and Grille Openings
Supply registers located in the floor require attention to keep them-clean and are usually avoided. Tests conducted in the Warm Air Research Residence at the University oflllinois have, indicated that comparable results are obtainable with either high side wall or baseboard registers, if proper registers and air velocities are selected. Baseboard registers should . be of a deflecting-diffuser type which throw the, air. downward toward the floor and diffuse it at the. same time. For baseboard registers air'temperatures under 125 F and air velocities over 500 fpm-should be avoided as they may cause drafts.
High side wall registers must be of such type that the air is delivered horizontally or in'a slightly downward direction, and must be so located as , to avoid impingement of air on ceiling or, wall. Directionaljflow diffusing.
Ceiling^
High Siden/a// Location
Fro. 1; .Recommended,Type op. Base-. , Fig.. 2. Recommended Type of. High
Board and Low SidEWall Registers*
, . Sidewall Registers11
'
* Vertical -bars -with, adjustable defection, or fixed vertical tiara with defections to'right and'left not exceeding about 22 deg. For low sidewall location, the deflection for horizontal, multiple valve, registers should not exceed 22 deg. For baseboard locations; the deflection for' horizontal, multiple valve, registers ^should not exceed about 10 deg.
. k Horizontal;valves, in back or front, to give downward deflections.not to
from 15 to 22 deg.
type registers should be used to insure best results. . Register air velocities should be such that the air velocity will be about 50 fpm three quarters of the distance from the register to.the opposite wvall.
Velocities through.registers may be reduced by the use of registers larger than the . connecting ducts.' Diffusers should be used to' spread the air uniformly over the register face, .Basic rules for the location mid selection of/registers are given in Section C of Manual No. .7 of the National Warm Air Heating and Air Conditioning Association.
Registers should be .well proportioned and decorated to harmonize with, the trim. Air supply registers should'be equipped with dampers and all registers should be sealed against leakage around edges. The register types shown in Figs. 1 and 2 have been recommended as standard by the National Warm Air. Heating and Air.Conditioning. Association. .
-.Retumairgrilles may be.located in hallways, near entrance doors, under windows, in exposed comers, or. inside; walls,.depending on; location of
supply registers, Baseboaiti. returns aimpreferable, to floor grilles.'
Mechanical Warm Air Systems
445
Table 1.
Warm Air Duct System Combinations of Parts Selected as Standard
Combina
tion No.
1
41 42 43 44
Stack Size In.
2
10 x 31 10x31 12 x 31 14x31
Branch Pipe Size, In.
Round
Rec tangular
34
r 4x8 6 4x8 7 5x8 8i: 6x8
Regibter Size,-In; (See Figs. 1 and 2)
Base-board ' High or Low
Sidewall
Floor Registers*
56
10 x 6
8 x 10*
10 x 6
8 x 10*
12x6
9 x 12*
14x6
9 x 12*
or longer
45 10 x 31 9 8x8 (2) 10 x 6 10 x 12*
(2-Stacks)
or
(1) 24 x 6
46
.12x3}
10 10x8 (2) i2 x 6 12 x 14*
(2-Stacks)
or
(1) 30 x6
Required Increase in
Trunk Duct, In.
7 i.
2 3 4
5
t.<
7
* Use trb*"* items only when the building construction or capacity requirements necessitate the use of floor registers. The sizes listed for floor registers correspond to the standard sizes for gravity warm air furnace systems, except for the sizes of:the floor box collars.. The use of standard blind boxes issuggested. A 12 x 5Jin. stack may be used on Combination 45 and a 14 x 51 in. stack on Combination 46 with floor
registers. -
-'
Dampers
Suitable dampers for air direction or volume control are essential to any duct system. .Special , care must be used in the design of any system to avoid turbulence and to minimize resistance. Sharp elbows, angles, and offsets should be avoided. Three., types of dampers are commonly used. Volume dampers are used to completely cut off or reduce the flow through pipes. Splitter dampers are used where a branch is taken off from a main trunk. Squeeze dampers are used for adjusting the volume of air flow and resistance through a given duct. It is essential that a damper with positive, locking device be provided; for. each main or duct branch. Labels placed on ducts should indicate the room being served. Damper positions should be marked for summer and winter operation, and to avoid tampering.
Ducts--
The ducts may be either round or rectangular in cross section. -Theradii of elbows should preferably be not less than one andone-half times: the pipe diameter for round pipes, or the equivalent round pipe size in the case of rectangular, ducts. . Warm air ducts pasting through cold spaces, or where located in .exposed walls, should have to 2 in. of insulation.
Special attention ; should be given to the problem of noise elimination. The metal duct' connection.to and from the furnace casing and fan housing should be broken-by strip's of canvas. Motors and mountings must becarefully selected for quiet operation. . " Electrical conduit and-water piping must not be fastened to,-nor-make contact'with fan housing. ^Installation' of a fan directly under a cold air grille is usually avoided.