Document 0670ZN2B5enp09z3gL1G8nL5R
AN INDIRECT AROCLOR HEATER FOR UNIT CHEMICAL OPERATIONS
f
I-----
! Monsanto
j Chemicals - Plastics
j k/ri__
AN INDIRECT AROCLOR HEATER for UNIT CHEMICAL OPERATIONS
Monsanto Technical Bulletin No. P-130
September, 1949
Monsanto Chemical Company
St. Louis (4), Missouri
o
Aroclor* 1248 (chlorinated biphenyl) is an ideal nonflammable liquid phase heat-transfer medium for temperatures up to 300C.
This bulletin describes the physical properties of Aroclor 1248 and illustrates the design and operation of heaters that have been used successfully by Monsanto plants during the past seven years. The units described are gas fired and the capacities are in the range of 200,000 to 400,000 B.t.u. per hour.
Other larger commercial installations using Aroclor 1248 have capac ities ranging up to 2,000,000 B.t.u. per hour.
Also small electrically heated stationary and portable units with capac ities around 40,000 B.t.u. per hour,using Aroclor 1248 as the heattransfer medium,are in service.
Several leading manufacturers of heating equipment are in position to build or offer Aroclor heating units to meet specific requirements.
Mo' nsanto _Tech, n.ical, nBulletin NMo. PD-130 Sc ep.temube- r, i1o9>4fo9
Rf. V. S. Pat. Office
The information contained in thit bulletin ia, to our boat knowledge, trua and accurate, bat all recommendations or eu^tfeein'ne are made tnhut guarantee, since the conditions of usa are beyond Our control. The Monsanto Chemical Company di*.-|aims any liability mcurred In connection with th# uas of these date or auggeationa. fiethrrmnrr. nothing contained herein shall be construed at a recommendation to use any product in conflict with aatetn* patrnu covering any material or its use.
DSW 322936
STLCOPCB4074587
Reprinted from INDUSTRIAL AND ENGINEERING CHEMISTRY, Vol. 41, Page 1341, July 1949 Copyright 1919 by the American Chemical Society and reprinted by permission of the copyright owner
An Indirect Aroclor Heater for
Unit Chemical Operations
MEADE McARDLE1, L. C. GARRETT, AND P. G. BENIGNUS*
' Monsanto Chemical Company, Anniston, Ala.
o
The characteristics of Aroclor 1248 indicate that it
Sprat Flammability. When a tube ruptures in a liquid heat-
is an ideal liquid phase heat-exchange medium for
transfer system under high pressure, a spray or mist forms.
temperatures up to 300 C. This article' discusses its The possible fire hazard under these conditions requires considera
properties and illustrates the design and operation of tions not covered by the foregoing discussions relative to the ma
heaters that have been used successfully by Monsanto
terial in the liquid form. In their comprehensive study of
plants during the past seven years.
flammability of the higher boiling liquids and their mists, Sulli
van, Wolfe, and Zisman (0) determined the spray flammability
IN CERTAIN manufacturing processes of the Monsanto limit of numerous materials in accordance with the percentage of Chemical Company, it was necessary to employ a noncom oxygen required for combustion. This value was then correlated bustible heat-transfer medium at pressures of 30 pounds per with the results of incendiary firing tests of the fluids conducted
square inch or less and temperatures up to 300 C. The following at the Naval Proring Ground, Dahlgren, Va. The oxygen re
general properties of a heat-exchange medium were required:
quirement for Aroclor 1248 combustion in the spray flammability
Freedom from fire hazards.
Viscosities to permit pumping at room temperatures.
Boiling point sufficiently above 300 C. to assure a liquid con
dition at all times.
Stability against heat, with enough safety factor to accommo
date accidental overheating.
Controllable vaporization losses. _
_
Freedom from corrosive action against valves, piping, tank
jackets, etc., made of cast iron and steels, bronze, and stainless
steel.
_
Freedom from toxicity hazard.
limit studies was found to be C4%, Fluids requiring over 45 to 50% oxygen in the spray test failed to cause a fire in the incendiarj' test. These results establish the nonflammable and noncom bustible qualities of Aroclor 1248.
VISCOSITY CONSIDERATIONS
Cold Flow. For most inside installations centrifugal pumps will handle Aroclor at reduced rates without preheating. Experi ence confirms this. Outside installations have been started at
Aroclor, chlorinated biphenyl (registered in U. S. Patent 0 C. by heating the pump and feed line until circulation through
Office), was selected. The pertinent physical characteristics
relative to its use as a heat-transfer medium are given in Table I.
Table I. Physical Properties of Aroclor 1248
FREEDOM FROM FIRE HAZARDS
Flash Point. Limitations of this test for the prediction of the fire hazard of relatively nonvolatile organic fluids have been recognized by the American Society for Testing Materials com
mittee (5, 4 ) Fire Point is a more significant measurement. The Under
writers' Laboratories (10) state that fire tests more truly reflect the (lack of) fire hazard of Aroclor.
Spontaneous Ionition Temperature. The combustionresisting qualities of Aroclor 1248 are indicated by its high spon taneous ignition temperature of 704 C. (1299 F.) determined by Sullivan, Wolfe, and Zisman (9), using the convenient apparatus described by Sortman, Beatty, and Heron (9).
Under conditions of industrial use the spontaneous ignition temperature will be determined by factors including the nature of the hot surface, the amount of liquid impinging on it, the volume of enclosed space, and the ventilation.
An accidental failure in a heating system demonstrated the nonflammability of Aroclor 124S and its freedom from the hazard of fire propagation. An operator's failure to start thu circulation of the heat-transfer medium when the gas heater was on resulted in excessive coil temperatures and caused the lower coil to soften and sag into the fire chamber. A weld ruptured and Aroclor 1248 poured into the red-hot tire chamber in contact with the flame. Dense smoke arose from the heater but there was uo external fire. After the gas flame was cut off, the smoking stopped.
1 Prrttnt addreu, Monunto Chemical Company, Organic Chemical* Division, 8t. Louie, Mo.
1'rreent addreae. Monaanto Chemical Company, Phoephata Divieion, 8l. Louie, Mo.
Appearance Absolute density, g./ml.
Practically colorless mobile liquid
c. CF.)
1.44 1.41 1.37 1.27 1.17
30 (86)
60 (140) 100 (212) 200 (392)
300 (572)
Absolute viscosity, centipoises
112 17.5
4.2 0.99
0.47
30 (80) 60 (140)
100 (212)
200 (392)
300 (572)
Thermal conductivity, B.t.u./hour/eq. foot/ 0 F./foot
Distillation range, A.S.T.M. D-20, * C.
Flash poiqt, Cleveland open cup, A.S.T.M. D 92-45, C.
Fire point, Cleveland open cup, A.S.T.M. D 92-45
Pour point, A.S.T.M. D-7, * C.
Coefficient of expansion, ml./ml./* C. (2565 C.)
Specific volume, ml./g.
0.0613 0.0698 0.0800
340-375
30 (86) 60 (140) 100 (212)
193-196
None -7
0 000702
0.696 0.709 0.728 0.787 0.860
30 (86)
60 (140) 100 (212) 200 (392)
300 (572)
Specific heat, eal./g./* C. Vapor pressure, mm. Kg
0.143 4.1M 0.326 0.355
0.00037 0.16 2.9 18.0 8C0.O
to 11121 too 13121 300 13921 300 15121
37.8 100 150 200 300
(100) (212) (302)
(392) (572)
DSW 322937
STLCOPCB4074588
1342
INDU STRI AL AND EN G INEERING CHE MI STRY
Vol. 41, No. 7
Table II.
Stability of Aboclok 1248 Heated fob 30 Hours
Temperature,
M(. of HQ per Cram of Aroclor
280 9.079
*00 0.186
*10 0.190
320 0.222
*30
0.248
Table III.
Stabiutt of Aroclor 1248 Continuously Heated at 280 and 330 C.
Hours
Mg. of HC1 per Gram of Aroclor
280' C
330' C.
30
0.079
0.248
60
0.116
0.510
90
0.160
0.923
120
0.194
1.141
150
0.261
1.362
Table IV. Gab Analysis of Aroclor 1248 Heated 4 Hours at 260 C. and 210 Pounds per Square Inch Pressure
Gu
%
Carbon dioxide Carbon monoxide Oxygen (derived from air)
Methane Hydrogen chloride Chlorine
Acidity (% by weight HC1) Prior to exposure After exposure
None None 20.2
0.2 None None
0.0075 0.0075
the heater had been effected so that the system could operate
normally.
'
BOILING POINT
Operating experience has shown that the boiling point of Aro clor 1248 (340 C. at 760 mm.) is enough above the 300" C. operating limit to prevent trouble from this cause. At the maxi mum operating temperature the vapor pressure is less than 0.5 atmosphere.
HEAT STABILITY
In order to establish a maximum practical operating tempera ture, the stability of the material when heated to elevated tem peratures in the presence of iron was noted. A slow stream of nitrogen was passed over the hot Aroclor to sweep the decom position products into a caustic trap. The amount of acidic material was determined and calculated as hydrochloric acid. The results given in Table II indicate the stability of Aroclor 1248 when individual samples were heated for 30 hours at the given `emperatures. The decom
at 340 C. fitted with an internal gas burner so that the gas flame impinged directly on the surface of the Aroclor. Analysis of the gases produced under these conditions included 0.6% carbon monoxide, 0.17% oxygen (derived from the air). 0.99% hydrogen ohloridc, 2.1% combustible gas calculated as methane, 0.002% chlorine, and no phosgene.
The same workers studied the stability of Aroclor when heated for 4 hours in an iron pipe at 200 C. under an internal pressure of 210 pounds per sauare inch, resulting from the introduction of compressed air. Following this treatment and cooling, the gases removed from the system were analyzed. The acidity of the Aroclor was determined prior to and after exposure to these con ditions. .
The results given in Table IV reflect an extremely small amount of decomposition under conditions similar to those selected for the practical use of Aroclor 1248 as a heat-transfer medium.
In actunl practice using the type of heating unit described below there has been no evidence of hydrochloric acid effect and no car bon deposits have been noted in the heater, pipes, or valves. The heaters have been operated successfully with combustion gases at approximately 600 C. in contact with the coils.
At one time, a spiral coil type of heater was built and through faulty design a burner tunnel was located 1.5 inches from the 2inch steel pipe coil. The radiation from the white-hot refractory tunnel and the direct impingement of the flainc on the pipe caused the pipe to glow a dark red for a space of about 2 inches. This unit was operated almost 3 months before a circulation stoppage occurred. When the line was opened lumps of carbon were found to have come loose and moved forward to lodge in the glebe valves. The lumps measured about 1 X 2.5 cm. and one face was formed to fit the pipe curvature. No hydrochloric acid effect was noted and the system was put back into operation after the burner location was changed.
CONTROLLABLE VAPORIZATION LOSSES
The heating systems in which Aroclor 1248 is used are sealed
except for the expansion tank, which has a loose cover or a vent pipe. Because this tank is separated from the stream by a sub stantial length of pipe, the temperature in the tank remains low.
In the light of the relatively low vapor pressure values for Aroclor 1248 (7), and as it is unlikely that the expansion tank will ever reach even the 1-mm. state (130 C-), there should not be a measurable loss of Aroclor from the system. Actual experience
bears out this contention. Other Losses. Although Aroclor darkens on use, its charac
teristics remain the same and replacement has not been found necessary after 7 years of continuous use. Accidental leaks or
spills constitute the only observed losses.
dsnn 322938
STLCOPCB4074589
nly 1949
INDUSTRIAL AND ENGINEERING CHEMISTRY
1343
Table V. Resistance of Structural Materials to Aroclor 1248
MetaU
Aluminum Copper Mifioenuru Nickel Silver Tio
At 25' C.
R R 11R RR R R
At 125' C.
R U K R R R
Metals
Zinc Mild steel Phosphor bronte Red brass Stainless steel Yellow brass
At 25* C.
R RR R D RR R
At 125* C.
R R D D RR Re
RR. Excelled resistance, leu then 1.0 X 10 cm. per dey penetration or
0.00014 inch per year.
. . _ . .,, .
A. Good resistance. penetretion between 1.0 X 10"*end 10 X lO'X cm.
per dey or between 0.00014 end 0.0014 inch per year. D. Doubtful resistance. penetretion between 10 X 10"* cm. per dey
end 100 X 10** cm. per dey or between 0.0014 end 0.014 inah per year.
e. Following letter indicating resistance, signifies materiel may be
better then indicated if totally immersed, as weight loss is believed to come
from otydation of part of teat atrip exposed to air.
DESIGN AND CONSTRUCTION
Heating System. The heating system required to utilize Aroclor 1248 as the exchange medium includes a heater (Figure 1), cooler, pump, and expansion tank (Figure 2), and control and safety circuits (Figure 3).
FREEDOM FROM CORROSIVE ACTION
The resistance of various metals (7) at 25 and 125 C. is given
in Table V. Similar studies made at 325 C. (6) indicate that the penetra
tion, in inches per year, for mild steel is 0.0028; for yellotv brass,
0.00047; for copper, 0.00145. Many years of practical operating experience with Aroclor 1248
Heater Design. The general requirements of the heater are
as a heat-transfer medium have shown that the material is prac tically noncorrosive to valves, piping, tank jackets, etc., made
compactness, ease of construction and service, and avoidance of direct flame impingement on the tubes.
of cast iron and steels, bronze, and stainless steel.
Direct flame impingement is prevented by directing the gas
. FREEDOM FROM TOXICITY HAZARD
flame through an enclosed channel with half-thickness fire brick protecting the tubes above until the high temperature of the
Aroclor 1248 is a very stable, unreactive liquid. If the material is spilled on the skiu, there are no noticeable ill effects; however, it is well to wash the skiu with soap and water after contact.
flame is reduced by heat conducted through these bricks and radiated to the two bottom coils. The size of the heater is reduced to a minimum by using only 4.5 inches of insulating fire brick in the hottest areas and 2 inches of Eagle No. 66 insulation on the
A skin burn resulting from accidental contact with hot Aroclor cooler spots.
9 should be treated in the normal procedure used for hot oil bums.
Two sizes of units arc used: One lias a maximum capacity of
Aroclor adhering to the burned area need not be removed im
200,000 B.t.u. per hour, as shown in Figure 1. The larger has a range of 200,000 to 400,000 B.t.u.
mediately unless treatment of the burn demands it; in this case
The small size consists of 90 feet of 1-ineii standard weight steel
soap and water or repeated washings with a vegetable oil (linseed pipe made into three coils of six pipes each and connected in
oil) should be used. The vapors emitted by Aroclor 1248 heated to elevated tem
peratures are injurious to the liver on prolonged exposure and
series. The larger size consists of 144 feet of 1.5-inch standard
weight steel pipe arranged in the same fashion. Results of tests on the small-size heater covering temperatures from 150 to 300 C. show temperature rises to 10 to 20 C. in the Aroclor
should not be breathed. Drinker (5) indicated that 0.5 mg. of while circulating at a rate of 15 to 20 gallons per minute. The
Aroclor 1248 per cubic meter of air is the maximum safe amount permissible in workrooms.
In commercial lieat-transfer installations, the presumption is that the Aroclor is in a closed system free from leaks. Accord
outlet gas temperature is consistently within 75 C. of the outlet Aroclor temperature. It is observed that the bottom two coils ab sorb the major part of the heat. The small unit indicates 50 to 60% efficiencies for capacities up to 200,000 B.t-.u. per hour when a natural gas of 1000 B.t.u. per cubic foot is burned. A Surface
ingly, there should be no opportunity for workers to come in con tact with vapors from the hot heat-transfer medium.
Combustion Company high pressure inspirator and tunnel burner set is used in this installation.
Over-all heat-exchange coefficients (.') for the furnace are in
n EXPANSION TANK
the range of 7 to 10 B.t.u. per hour per square foot per degree Fahrenheit. Over-ail heat-exchange coefficients for Aroclor 1248 to water in a double pipe heat-exchanger made from 1.25-iuch pipe with a 2-inch pipe jacket are in the 120 to 180 range. These figures are calculated from test results on this
STEAM Oft WATER
YOUTLET
AftOCLOA
& HrpoM kcatca
jacketed pipe cooler
^Water inlet
installation.
-G>heater
.
Cooler. A very useful adjunct to the system is a double pipe cooler on the outlet of the heater shown in Figure 2. By turning water into the
jacket, the Aroclor can be cooled and
BRAIN ---- fXH-CxJ
<D-tKi>(D-
the temperature of the system lowered. This is helpful when it is necessary to
-A0
AAOCUX TO HEATft
rx_L
J. AfiOCLOA PUMP o
SL
CAS
6 PILOT LIGHT
I------------- -----------XI---------------
cool a batch before removing it or when an exothermic reaction starts to get out of control.
Pump. The pump for circulating
HEATER PIPING
the Aroclor 1248 may be any one of a number of standard centrifugal units
Figure 2. Cooler, Pump, and Expansion Tank
designed for hot liquid service.
DSW 322939
STLCOPCB4074590
1344
INDUSTRIAL AND ENGINEERING CHEMISTRY
Vol. 41, No. 7
Pipe Cooatnjctioo
Ell*, teee. and reducers
Flaaiee Bolts
Unions
Dope Gaskets Shut-off valves Control valves Check valves Safety valves Relief valves Valve stem
packing Gage and glass
Strainers
Table VI. Piping Detail
(Dimensions in inches)
>/ through V 1 through 6 V through /< 1 throug' 6
>/ through / 1 through 6 1 through 6
V through V
*/ through >/4 1 through 2 2*/i through 6 V4 through /4 1 through 2 2>/* through 6 */ through */4 1 through 2 2 through 6
/
iVt through 3
/4 gage
>/*-*/ 1 through 3
Schedule 80, A.S.T.M. A53 or A106
Schedule 40. AJLT.M. A53 or AI06 Screwed
Flanged Bend in shop and
field where possiblc. Must be
cleaned to remove scale Forged steel screwed. Crane 300d
series Welded fittings. Crane 300e
Series 30 (to match valves) Machine bolts A.S.A.
H-18.2 with^hex-
agonal nuts for service below 500*
F. Above use alloy steel. Crane tri plex A.S.T.M. A96
Crane 252h forged stee Crane 425 high tem
perature thread compound
Soft iron ring flat or corrugated
Crane 360GW, screwed, gate
Crane 3615W, flange, gate Crane 33XR, flange, gate Crane 3040 XR, screwed, globe Crane 3G5G XR, flange, globe
Crane 151 XR, flange, globe Crane 3074 X, screwed Crane 3680 X, flanged Crane t59 X, flanged Consolidated 1070 BW, screwed
Consolidated 1012 W, flanged Goetze 340 D or
DuramctaUic D-
110 Type 100 PCPR Marsh O-100
Ib./sq. inch gage siphon with Crane 222H bar stock valve,
.lergueon Scries R20 Reflex type
liouid level gage 821 Yarway threaded
822 Yarway flanged
The Dayton Dowd Type C pump is an example of the type required. It should be made of cast steel and have a watercooled stuffing box and water-cooled bearings. The stuffing box should have room for at least six rings of packing and a lantern ring. Durametallic No. D-110 or Garlock Xo. 234 may be used for packing the pump. An open impeller is desirable, as it will handle the cool, more viscous liquid on starting the system better than will a closed impeller. Enough horsepower for the most viscous conditions is required.
Piping System and Expansion Tank. The detail of the piping system for Aroclor 1248 used up to temperatures of 3009 C. (572 F.) and 100 pounds per square inch pressure is given in Table VI. The valves and specialties given indicate the type re quired. All piping larger than 0.75 inch is flanged or welded; ex perience has shown that hot Aroclor penetrates screwed joints of the larger sizes. Steel and cast steel are used throughout.
The system requires an expansion tank located at the highest level of the installation. The size of this tank is normally about 25% of the capacity of the Aroclor system. Connections with valves, made on either side of the pump, enable the operator to connect a flexible hose and to pump in or out as required.
For operation in locations where the Aroclor temperature may drop to where the attendant viscosities may make pumping im practical in the system as designed, it may be desirable to steamjacket the Aroclor circulating lines to facilitate rapid start-up. Suitable safety provisions, such as safety pop-off valves, must be installed in the 6lcam jacket system to prevent pressure ruptures which would develop if any condensate remained in a closed sys tem during high temperature operation.
In order to establish operating conditions and to check the operation of the heater itself, it is often desirable to measure the temperatures of the Aroclor in and out of the heater and cooler. Items 10, and 11 (Figure 2) provide for this. They may be dial thermometers or mercury bulb thermometers of any commercially available type recommended for the service.
Table VII. Safety and Control Equipment
1. High pressure alarm Mereoifl DA-31, open circuit on high pressure.
(detects stoppage Actual settings depend on individual layout
of pipe)
2. Low pressure alarm Mercoid DA-31-3, open circuit on low pressure.
(detects stoppage Actual settings depend on individual layout
of pump)
3. Thermostat (detects Fenwal 18002. Contacts open on temperature
excessive heating increase
hence obstruction
of flow)
4. Float switch (detects Mercoid Figure 40. 8.P. twitch. Open at low
leakage from ayn- level
tern)
5. Flame failure system Combustion Control Corp. Fireye FF6. Flame
(cuts off gas if failure control for manual ignition gas burner
pilot flame goes systems
out)
6. Css valve (cuts off General Control Corp. K-10-2. Closes with
in case preceding current off
devices act)
.
7. Red light (alarm)
Killark VA-1 GO W, or Benjamin 7013-V
8. Horn (sounds alarm) Edwards 312
Alarm relay
Type C-1104 1-NO, 1-NC watertight (/)
Stop horn relay
Type C-1104 1-NO, 1-NC, watertight (I)
Stop horn button
1-1IA-4 ()
0. Thermometer well 0-300 C. mercury bulb thermometer
(visual check of
heater perform
ance)
10. Thermometer well 0-300 C. mercury bulb thermometer
(visual check of
neater perform
ance)
11. Thermometer well 0-360 C. mercury bulb thermometer
(visual check of
cooler perform
ance)
12. Solenoid valve
General Control K-10-2. Controls Aroclor
temperature to meet demands of system
For automatic temperature control a solenoid valve, item 12, is indicated in a by-pass arrangement with a manuallyoperated needle valve. The needle valve is adjusted to give almost enough heat to meet the requirements and the actual control is carried on by the solenoid valve, which opens and closes as directed by a tem perature-control instrument connected to the equipment being
One unit was set up with temperature control using a Leeds & Northrop Model S all-electric control with droop corrector. Very close control over a wide range of heat demand resulted, when a throttling range adjustment of 4 was used on this control device.
Safety Circuit. Figure 3 shows a safety circuit which auto matically protects the system by closing off the gas supply in the event of faulty operating conditions. Provision is made for shutting off the warning horu while the system is being put back into operation after a safety shutdown.
A detailed list of the safety and control equipment is given in Table VII. The equipment named indicates the type required.
ACKNOWLEDGMENTS
The authors are grateful to A. M. Ellenburg of Monsanto's Re search Laboratory at Anniston, Ala., for furnishing many of the technical data about Aroclor 1248 and for assistance in preparing the manuscript.
LITERATURE CITED
(1) Allen Bradley Co., Milwaukee, Wis., Bull. 700. (2) Ibid., Bull. 800. (3) Am. Soc. Testing Materials, Proc. Am. Soc. Titling MaleHalt,
34,53(1934). . (4) Am. Soc. Testing Materials, "Standards on Petroleum Prod
ucts and Lubricants," 1945. (5) Drinker, C. K., J. Jnd. Hyg. Toxicol., 21, 155 (1639). (C) Monsanto Chemical Co., Anniston, Ala., private communica
tion, April 13, 1944. (7) Monsanto Chemical Co., St. Louis. Mo., Montanio Tech. Bull.
P-115 (August 1947). (6) Sortman, C., Beatty, H., and Heron, B., Ikd. Eko. Chew., 33,
357(1941). (9) Sullivan, M. V., Wolfe, J. K,, end Ziam&n, W. A., Ibid., 39, 1607
(1947). (10) Underwriters' Laboratories, Chicago, 111., "Miscellaneous
Haiards," No. 2498,1934.
Received August 27, 1048. Presonted before the Meeting-in-Miniature, Alabama 8eetion, Ameeicam Chemical Bocistt, December 8. 1045.
Feinted in U. 8. A.
DSW 322940
STLCOPCB4074591
Monsanto
: Chemicals-Plastics
MONSANTO CHEMICAL COMPANY
ST. LOUIS
AKRON BIRMINGHAM BOSTON CHARLOTTE CHICAGO
CINCINNATI CLEVELAND DETROIT HOUSTON LOS ANGELES
NEW YORK PHILADELPHIA SAN FRANCISCO SEATTLE
MONSANTO (CANADA) LTD.
MONSANTO (AUSTRALIA) PTY LTD.
Montreal* Toronto Vancouver
Melbourne
MONSANTO CHEMICALS LTD. London
Representatives in the Principal Cities of the World
DSW 322941
POB:UAO-UDM-9-9
Printed In U.S.A.
STLCOPCB4074592