Document 066L9eQRO26VZQ7y8yBOx8woJ

524 CHAPTER 23 . - 1950 Guide In the following example, itwitlbe assumed that the ceiling panel must deliver 70 per cent of its heat or $4,688 Btuh by radiation, since the-total calculated heat loss is 35,117. When two plane surfaces of infinite size are parallel to each other and their surfaces are at different temperatures, the exchange of heat between the two is proportional to the difference between the fourth powers of their absolute temperatures. This is also true when one surface is completely surrounded by another surface; for example, if one sphere is placed within another sphere, the flow of heat between the outer sur face of the smaller sphere and the inner surface of the larger sphere is proportional to the fourth power of the absolute temperatures of the two surfaces. In a panel-heated room, the heated panel may be considered to be completely en closed by the remaining surfaces, because all heat radiated by the heated panel is intercepted by those surfaces. Consequently, the flow of heat from the heated ceiling to the room,,by radiation, is proportional to.the difference between the fourthpowers of the absolute temperature of the ceiling and the absolute mean radiant, temperature of the remaining surfaces. The rate at which a surface emits heat varies with the temperature'-of the Surface and with other characteristics of the surface. For ordinary heat flow calculations, it TCMPCAATURC'Or MCATIN6 AAMCL - OCG. FAMR. Fig. 9. Heat Delivered To Room by Radiation from Panel -- :^ is sufficiently accurate to assume that the. materials which are commonly iised m building construction emit heat at a rate of: 0.166 ^ Btuh per square foot' where T is the absolute temperature of the surface in Fahrenheit degrees.. , . ', ; On this basis the flow of heat from the ceiling to its surrounding surfaces is at the rate of: \ l.' ' ' V'- . ;V- :' '''! - - 015^ [(iS)4 - (il)*] ^tut- In order that this'rate may be!equal to 24,582 Btuhf T must be 572 and.the'ceiling temperature about 112 F. T 1' Instead/of calculating this temperature; it may be'talcen from.Fife/follows: Tbe.ceilihg'must1 deliver heat to the'room, by radiation, at'the rate of 24,582/480 or 51, Btiih per. square foot.' Find `51 on the left margin and move horizontally to'the .intersection^with a 62 MRT line, and from the point of intersection to the loWer mar- ^n/and re^about 112 F. ` `. ,, * . , .With, a ceiling temperature of .112 F, the MRT of the room will .be .480 X..412. + 1,536"X 62; the.sum divided by 2,016, or 74 F. / ., ' , 'j\ r If an air temperature of 68 F and an MRT-of 74 F should not produce satisfactory Panel Heating and Radiant Heating. 525 conditions, the ceiling temperature can easily be changed as necessary by changing the temperature of the circulating water.. 7. Select the medium for heating the ceiling panel. . The medium may be electricity, steam, air,-or water, but usually is air or water: If air is used, it is generally heated in the basement, passed up through hollow inside walls or through ducts in those walls, allowed to flow between the ceiling and the floor above, and returned to the basement through hollow outside walls or through ducts in those walls. If the walls and floors are constructed of hollow tile, the cells in the tile can be placed so that they will form continuous ducts through which the warm air can flow up the inside walls, then between the ceiling and the floor above, and down the out side walls. In this way the walls and ceiling become heating panels. If water is used as the medium, the pipes through which the water circulates (almost always under forced circulation)are placed in the floor, walls', or ceiling in such a manner that the largest possible proportion of the heat emitted by the pipes will be delivered to the space to be heated. * , Practical limits for surface temperatures of :heating panels-are given in Table 2. Table 2. Highest Safe Surface Temperatures for Heating Panel Ttpb or Panel Surface Temperature F Dbq Plastered Ceiling (Pipes Imbedded)*..................................... ...... Plastered Walls (Pipes Imbedded)4.................................................. Floor, Any Method.............................................................................. Floor, Border and Aisles....................... ..........V.................. .. :............ . Iron, Hot Water Medium1*.............................................................:. Iron, Steam Vapor4............................................. ............................... Electrically Heated Panelsb.......... .................................................... 115 120 85 - 120 160 180 200 ' * Gypsum Association recommends that panels in which gypsum plaster or gypsum products are used should not have a surface temperature exceeding 115 F. b Low surfaoe temperature radiation is recommended regardless' of the heating medium employed. 8. In this example water will be selected as the medium. Determine the size; lengthy and location of the pipe coils in the panels. - When hot-water pipes are imbedded in concrete slabs or attached to plastered sur faces, their rate of heat emission varies with many factors.~ If the pipes are imbedded in dense concrete slabs, it may be assumed that the rate of heat emission of ^-in. pipe, spaced 6 in. on centers; f-in. pipe, spaced 9 in.' on centers; and1-in. pipe spaced 12 in; on centers; per foot of length of pipe and per degree difference between-the temper ature of the water in the pipe and tnat of the air in the space to be heated, is 0.8,1.0," and 1.2 Btuh, respectively. If the distance between the pipes is increased, the rate of heat emission, per foot of pipe, is also increased; if the distance is doubled, the rate of heat emission is increased about 15 per cent. If the pipes are attached to plastered ceilings, the rate of heat emission is slightly less, probably about 10 per cent less, than when the pipes are imbedded in concrete slabs. The data given regarding heat emission of panels are intended as general guides for the designer. Additional-expe rience and research are needed to develop definite and complete data. However, after a heating ;panel has been designed and installed, any small error can easily be.cor-* rected by modifying the temperature of the water circulating through the coils. ,' V" .When the heating pipes are attached to a plastered ceiling, a portion of the heat emitted by the pipes is delivered to the spiace below the ceiling, and a portion to the space above the ceiling..- The relative quantities depend on the degree of insulation applied above the heating coils. /. . When the heating pipes are imbedded in a concrete floor slab, a portion of the heat emitted by the pipes will flow upward into the space to be heated, and the remainder will flow downward into the ground. - When the heating pipes are placed below the concrete floor slab instead of being