Healing and Ventilating Unit, Air
G. C. Shipp & Company Indianapolis, Indiana, U. S. A.
AUTOMATIC
D-ITrade Mark
Reg. U- S. Pat. Office
SANITARY
VENTILATING RADIATOR UNITS
for
SCHOOLS, HOSPITALS AND OTHER PUBLIC BUILDINGS
Three vital and important factors are assured by the use of the Automatic D-I Sanitary Ventilating Radiator Units
HEAT-___ l........... --Distributed properly and automatically to every comer of the room.
MOISTURE............-In just the proper percentage assured automatically and without noise.
VENTILATION__ ..Controlled automatically by the temperature within the room, without draughts and without the use of mechanical appliances of any kind, or the services of an expert operating engineer.
Thus it will be seen that the D-I System is a natural, easy, simple, efficient and economical way of obtaining heat, ventilation and humidity for old and new buildings
See Pages 653, 654, 655, 656.
Copyright 19S7. 19SS. C. C. Shipp & Company
C. C. Shipp & Company
Healing and Ventilating Unit, Air
CAPACITIES OF D-I SANITARY VENTILATING RADIATOR UNITS
Series No.
1 2 3 4 5 6
Sire of D-I Wall Box In.
8 x 20 8 z 24 8 z 30 !<% 20
24 30
Cu. Ft. Air per Minute
180 240 300 270 330 420
Air per Pupil
30 30 30 30 30 30
in Radiator
12 14 16 14 16 18
Sections of Radiator Covered
8 10 12 10 12 14
(1) D-I Ventilating Wall Box with Storm Louvers, Insect Screen, Adjustable Extension Sleeve and Adj ustable Con trolling Fresh Air Damper with dustproof and non-corroding hinges.
(2) D-I Adjustable Controlling Fresh Air Damper.
(3) 2 x 4-inch Wood Frame around ends, top and bottom of Sleeve, room side --Edge to set flush with finished plastering.-
(4) D-I Sanitary Ventilating Box Base.
(5) Recirculating Air Damper and Cleanout Door.
(6) D-I Adjustable Air Diffusers with Removable Rolls.
(7) D-I Adjustable Fresh Air Damper Indicator.
(8) D-I Automatic Fresh Air Damper Control.
(9) Bottom of Wall Box Sleeve to set not less than 8 in. from finished floor.
(10) 38-in. Five Tube Ventilating Legless Radiator--Bracketed from wall.
(11) Back of radiator to set 2} in. from
finished wall.
(12) From center of lower tapping to extreme top of radiator--33H in.
(13) From finished floor to center of lower radiator, tapping--11in.