Document 061mvE2mo1YgxkbeGZ1B06oex

Healing and Ventilating Unit, Air G. C. Shipp & Company Indianapolis, Indiana, U. S. A. AUTOMATIC D-ITrade Mark Reg. U- S. Pat. Office SANITARY VENTILATING RADIATOR UNITS for SCHOOLS, HOSPITALS AND OTHER PUBLIC BUILDINGS Three vital and important factors are assured by the use of the Automatic D-I Sanitary Ventilating Radiator Units HEAT-___ l........... --Distributed properly and automatically to every comer of the room. MOISTURE............-In just the proper percentage assured automatically and without noise. VENTILATION__ ..Controlled automatically by the temperature within the room, without draughts and without the use of mechanical appliances of any kind, or the services of an expert operating engineer. Thus it will be seen that the D-I System is a natural, easy, simple, efficient and economical way of obtaining heat, ventilation and humidity for old and new buildings See Pages 653, 654, 655, 656. Copyright 19S7. 19SS. C. C. Shipp & Company C. C. Shipp & Company Healing and Ventilating Unit, Air CAPACITIES OF D-I SANITARY VENTILATING RADIATOR UNITS Series No. 1 2 3 4 5 6 Sire of D-I Wall Box In. 8 x 20 8 z 24 8 z 30 !<% 20 24 30 Cu. Ft. Air per Minute 180 240 300 270 330 420 Air per Pupil 30 30 30 30 30 30 in Radiator 12 14 16 14 16 18 Sections of Radiator Covered 8 10 12 10 12 14 (1) D-I Ventilating Wall Box with Storm Louvers, Insect Screen, Adjustable Extension Sleeve and Adj ustable Con trolling Fresh Air Damper with dustproof and non-corroding hinges. (2) D-I Adjustable Controlling Fresh Air Damper. (3) 2 x 4-inch Wood Frame around ends, top and bottom of Sleeve, room side --Edge to set flush with finished plastering.- (4) D-I Sanitary Ventilating Box Base. (5) Recirculating Air Damper and Cleanout Door. (6) D-I Adjustable Air Diffusers with Removable Rolls. (7) D-I Adjustable Fresh Air Damper Indicator. (8) D-I Automatic Fresh Air Damper Control. (9) Bottom of Wall Box Sleeve to set not less than 8 in. from finished floor. (10) 38-in. Five Tube Ventilating Legless Radiator--Bracketed from wall. (11) Back of radiator to set 2} in. from finished wall. (12) From center of lower tapping to extreme top of radiator--33H in. (13) From finished floor to center of lower radiator, tapping--11in. Copyright 1985,1986,1987.1988. C. C. Shipp & Company