Document k6zj3m9146X0d6OYEjqO92VLy

EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL July 25, 1984 Revised Steve C. Hillman Process Engineer Approved By: R. A. Frohreich 1 Chief Process Engineer VAB.0001134982 I EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL I. INTRODUCTION The Emission Recovery System was installed as a part of the Aberdeen Chemical Plant*s overall program to achieve compliance with the promul gated regulations of the Environmental Protection Agency regarding emissions of vinyl chloride monomer. These regulations require that fugitive emissions be collected and contained and that any vent to the atmosphere be less than 10 ppm vinyl chloride. Various waste water and vapor vent streams in the Aberdeen Chemical Plant contain high concentrations of VCM. The waste water from the process is being collected and steam stripped to remove VCM. EPA regu lations currently require that this water to contain 10 ppm or less VCM. Also EPA regulations require that the VCM railcar unloading lines con tain less than 0.13 ft. VCM vapor at 20C and 29.92 in. Hg. To do this requires pulling a vacuum of 10 in. Hg. on these unloading lines after the car has been unloaded. The EPA regulations which limit VCM emissions to 10 ppm or less in exhaust gas vents and in process waste water have required that all VCM/ PVC plants collect and contain these various sources. The Emission Recovery System is a combination vacuum/compression unit which collects VCM vapors from the following sources in the Aberdeen Chemical Plant: 1. Batch Water Strippers 2. VCM Tank Farm 3. VCM Railcar Unloading Lines 4. Vessel Purge System The vapors are subsequently condensed in the Emission Recovery System recovery condenser and liquid VCM is transferred to the old module recovered VCM receivers. ' y This operating manual will provide instructions to operate the Emission Recovery System in order to achieve emission levels within EPA limits. k 1 VAB.0001134983 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL * II. GENERAL DESCRIPTION Please refer to the P & I diagram (Drawing MS-9630-42-1D) in section VII of this manual for the following description. The Emission Recovery System is designed to collect VCM vapors from the following sources: 1. Batch Water Strippers 2. VCM Tank Farm Area 3. Vessel Purge System The VCM concentration in the discharge streams from these areas is required to be 10 ppm or below. Vapors from the vessel purge system and the batch water strippers first enter the Emission Recovery System through the inlet condenser EA-701. This heat exchanger is used to condense steam out of the vapor stream so that the vacuum pumps and compressors are not overloaded. The exchanger also cools the VCM gas stream and allows the vacuum pumps and compressors to operate at a lower temperature. The condensate exits EA-701 and gravity flows into T-701. With the drain pump, P-701, in auto, when the water level in T-701 reaches LS-701B, the middle level switch, CV-701 opens, the drain pump starts, and liquid is pumped from T-701 to the batch water strippers. CV-701 will close and stop the drain pump when the water level in T-701 decreases to the lower level switch LS-701A. The upper level switch LS-701C will trip an alarm on the local control panel, shutdown the ERS, and activate a shutdown alarm in the vinyl control room. VCM vapors from the tank farm area enter the Emission Recovery System through CV-1 and flow directly into T-701. Also the recycle VCM, which is used to control T-701 low pressure, enters T-701 at the same point. i PIC-701 is the low pressure controller for T-701 and is located on the local instrument panel. The setpoint should be 15 in. Hg. vacuum. When T-701 is pulled to 15 in Hg vacuum, PIC-701 allows VCM vapor from the old module large recovery system collect tank to bleed into T-701. Two new vacuum pumps, P-703 and P-704, and two new compressors, C-705 and C-706, have replaced the old vacuum pumps and compressors. One vacuum pump and one compressor will operate at all times. To insure sufficient vacuum in the emission recovery system, instrumentation is provided to automatically start/stop the second vacuum pump and com pressor as needed. Upon high system pressure (5 in. Hg. vacuum), high pressure switch, PSH-301, on tank T-701, will start the vacuum pump and compressor not on stream. As the system pressure is reduced to setpoint (10 in. Hg. vacuum), low pressure switch, PSL-301, will stop the vacuum pump and compressor that were started due to high system 2 VAB.0001134984 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL II. GENERAL DESCRIPTION (Cont.) Vapors exit T-701 and flow through pressure control valve, PCV-301, into vacuum pumps P-703 and P-704. Vapors from these vacuum pumps flow into T-702 where the seal water from the vacuum pumps is separated from the vapor stream. The seal water is filtered, cooled, and pumped back to the vacuum pumps and compressors. T-702 level control is set up to both drain and makeup water to T-701 as needed. Excess water is drained through the seal water pump and CV-311 and is pumped to the batch water strippers by drain pump P-701. With drain pump P-701 in auto, LS-702C will open CV-311, start the drain pump, and activate a time delay relay which will close CV-311 and stop the drain pump after approximately 20 seconds. If the time delay fails LC-702B will stop the drain pump and shut CV-311. LS-702D is the high level switch which will trip an alarm on the local control panel, shutdown the Emission Recovery System, and activate a shutdown alarm in the vinyl control room exactly as LS-701C did on T-701. When the level in T-702 drops below LS-702A an on/off water makeup valve, CV-702, will open to add HPSW to T-702. When the level rises to LS-702B, CV-702 will close. Liquid drained from either T-701, T-702, or T-703 will first pass through DST-301 to strain out any solids that might plug the drain pump. VCM vapors exit T-702 and flow into either C-705 or C-706. Vapors are compressed to approximately 80 PSIG and flow into T-703. Here seal water from the compressors is separated from the vapor stream. T-703 has a new level indicator controller, LIC-301, which controls the level in T-703 by draining excess liquid to T-702 through LCV-301. High level switch, LSH-703C, will trip an alarm on the local control panel, shutdown the Emission Recovery System, and activate a shutdown alarm in the vinyl control room just as LS-701C did. *t Two interstage control loops are provided in the system to control the interstage pressure between the vacuum pumps and compressors. The first control loop is a feed back control loop to prevent high pressure (greater than 5 psig) at the compressor(s) inlet. Pressure sensing element, PT--301, on tank T-702 senses the pressure and trans mits a signal to pressure indicating controller, PIC-301, to create a response to the high interstage pressure. As the pressure increases, the response of PIC-301 is to close PCV-301, therefore, restricting vapor flow from T-701 and creating a false vacuum at the vacuum pump inlet. This allows the compressors to essentially "catch up" and the pressure at the inlet of the compressors will go down. PT-301 will sense the pressure reduction and allow PCV-301 to open allowing normal flow through the system. h nmmmm MWfil T t*** PP VAB.0001134985 MISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL II. GENERAL DESCRIPTION (Cont.) The second control loop is also a feed back control loop to prevent low pressure at the compressor(s) inlet (pressures less than 1 psig). Pressure transmitter* PT-301, senses the low pressure and sends a signal to pressure indicating controller, PIC-302, which controls PCV-302 located in a pressure equalization line from T-703 to T-702. PCV-302 is normally closed, and the response to the signal from PT-301 is to open. As PCV-302 opens, vapor flows from the discharge of the compressors to the inlet of the compressors. The vapor flow from the compressor discharge to the compressor inlet will continue until an increase in pressure is sensed by PT-301. PT-301 will transmit a signal to PIC-302, and PCV-302 will close. The increase in interstage pressure indicates matched flow between the vacuum pumps and compres-- Pressure controller PIC-301 and PIC-302 are located on the local con trol panel. From T-703 the compressed VCM flows into the new Emission Recovery System VCM condenser EA-301, located on the roof of V-ll near inlet condenser EA-701. The vapor is condensed in EA-301 and transferred to the old module RVCM receivers. Vapor can also be transferred to the inlets of the old module large recovery system condensers, if needed. The seal water system provides compressant water to the vacuum pumps and compressors. The system consists of a seal water pump and , a filter and spare, and three heat exchangers to cool the seal water. It is designed to run on one seal water pump which will provide 60 GPM to the recovery system* Each vacuum pump requires 12 GPM and each compressor 18 GPM. The seal water will be transferred from T-702 by NP-707 or 708 and enter FD-301 where any trash or resin will be filtered out. Pressure entering .the filter will be approximately 135 PSIG, and normally the pressure will drop 2-3 PSI at the outlet. The filter cartridges should be changed when the pressure drop exceeds 5 PSI. In addition to the regular compressant seal water provided by the Emission Recovery System seal water system, compensated seal water is added to the Emission Recovery System compressors when running to increase the discharge pressure that the compressors are able to attain to 100 PSIG. As the compressor discharge pressure increases the seal water flows from T-703 through a restriction orifice and on/off control valve to the compressor. The existing three seal water coolers have been repiped so that they can be operated in parallel as needed to provide sufficient cooling. The seal water temperature control will be maintained by the existing temperature controller on the cooling water return line. 4 VAB.0001134986 p EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL II. GENERAL DESCRIPTION (Cont.) The V-ll hydroquinone system is tied into the Emission Recovery System seal water system at tank T-702. Hydroquinone is continuously injected into the Emission Recovery System seal water by the V-ll hydroquinone system diaphram pump. The injection rate should be set at 0.17 GPH and should be checked once per shift. The plant HPSW system provides the mechanical seal purge water for the vacuum pump and compressors. This water enters the Emission Recovery System in a header at about 220 PSIG and enters individual pressure regulators for each vacuum pump and compressor where the pressure is dropped to 125 PSIG. Pressure on the seals and flow through them are controlled by manual valves on the seal outlets. Fresh air stations and utilities stations are located on the north side of the old blast wall on the first and second floor of V-ll. The utilities stations consist of 150 PSIG steam and 220 PSIG HPSW. The electrical circuit breakers for the Emission Recovery System are in the breaker room located on the second floor of the chiller build ing. All breakers are labeled. * 5 VAB.0001134987 * EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL III. INTERLOCK DESCRIPTION Vacuum Pumps and Compressors 1. Vacuum Pumps- The valve(s) on the inlet manifold(s), and the valve(s) on the compressant seal water line(s) will not open until the vacuum pumps, P-703 and P-704, are started as follows: Valve CV-302 will open one second after P-703 has started and CV-301 will open 5 seconds after P-703 started. When P-703 stops running, CV-301 and CV-302 will close. Valves CV-304 will open one second after P-704 has started and CV-303 opens 5 seconds after P-704 started. When P-704 stops run ning, CV-303 and CV-304 will close. The vacuum pumps cannot start until the compressors are running. 2. Compressors- The valve(s) on the inlet manifold(s), and the valve(s) on the compressant seal water line(s), and the valve(s) on the compensated seal water lines will not open until the compressors, C-705 and C-706, are started as follows: Valve CV-306 will open one second after CV-705 has started and CV-305 & CV-309 open 5 seconds after C-705 starts. When C-705 stops running, CV-305, CV-306, and CV-309 will close. Valve CV-308 will open one second after C-706 has started and CV-307 & CV-310 open 5 seconds after C-706 starts. When C-706 stops running, CV-307, CV-308, and CV-310 will close. 3. Normally one vacuum pump>and compressor will run at all times. When placed in auto the second vacuum pump and compressor will start/stop as needed according to PSH-301 and PSL-301 located on T-701. 4. The vacuum pumps and compressors will not start unless one of the seal water pumps, P-707 or P-708, is running. 5. Drain pump P-701 must be in auto before T-701 and T-702 will auto matically drain on high level. * ifWMV Pip VAB.0001134988 flPPPM if EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL IV. EQUIPMENT LIST Item Conoco Number Service A. Compressors C-705 C-706 72-993 72-994 NASH 1253C Compresses VCM Vapors, 100 HP NASH 1253C Compresses VCM Vapors, 100 HP B. Filter FD-301 FD-301S 64-050 64-051 Commercial, Filters Seal Water Commercial, Filters Seal Water C. Heat Exchangers EA-701 EA-709A EA-709B EA-709C EA-301 55-002 55-004 55-311 55-376 Steam Condenser Doyle & Roth, Seal Water Cooler Doyle & Roth, Seal Water Cooler Doyle & Roth, Seal Water Cooler VCM Condenser D. Pumps P-701 72-209 Durco, T-701 Drain Pump P-707 P-708 E. Vacuum Pumps P-703 P-704 72-567 72-568 * fr 72-991 72-992 Gould, Seal Water Pump, 40 HP Gould, Seal Water Pump, 40 HP NASH CL-402, 40 HP NASH CL-402, 40 HP F. Vessels T-701 T-702 T-703 G. Strainer DST-301A DST-301B 45-026 45-308 45-342 * 77-078 77-079 Inlet K.0. Pot Vacuum Pump Seal Water Se Compressor Seal Water Sep Andale Strainer Andale Strainer 7 VAB.0001134989 EMISSION RECOVERY SYSTEM * ABERDEEN CHEMICAL PLANT V. INSTRUMENT LIST OPERATING MANUAL Item No* Description Service CV-301 CV-302 CV-303 CV-304 CV-305 CV-306 CV-307 CV-308 CV-309 CV-310 CV-311 CV-1 CV-601 CV-701 On/Off Control Valve Control Valve On/Off Control Valve Control Valve On/Off Control Valve Control Valve On/Off Control Valve Control Valve On/Off Control Valve On/Off Control Valve On/Off Control Valve On/Off Control Valve On/Off Control Valve On/Off Control Valve Vacuum Pump P-703 Process Inlet Vacuum Pump P-703 Compressant Seal Water Flow Control Vacuum Pump P-704 Process Inlet Vacuum Pump P-704 Compressant Seal Water Flow Control Compressor C-705 Process Inlet Compressor C-705 Compressant Seal Water Flow Control Compressor C-706 Process Inlet Compressor C-706 Compressant Seal Water Flow Control Compressor C-705 Compensated Seal Water Compressor C-706 Compensated Seal Water T-702 Drain To Batch Water Stripper Isolation Valve For VCM Tank Farm Isolation Valve For BWS T-701 Drain Valve FCV-301 FCV-302 FCV-303 FCV-304 Control Valve Control Valve Control Valve Control Valve Vacuum Pump P-703 Compressant Seal Water Vacuum Pump P-704 Compressant Seal Water Compressor C-705 Compressant Seal Water Compressor C-706 Compressant Seal Water FI-301 FI-302 FI-303 FI-304 FI-305 FI-306 FI-307 FI-308 FI-309 FI-310 Rotameter Rotameter Rotameter Rotameter Rotameter Rotameter Rotameter Rotameter Rotameter Rotameter Vacuum Pump P-703 Mech Seal Flush Vacuum Pump P-703 Mech Seal Flush Vacuum Pump P-704 Mech Seal Flush Vacuum Pump P-704 Mech Seal Flush Compressor C-705 Mech Seal Flush Compressor C-705 Mech Seal Flush Compressor C-706 Mech Seal Flush Compressor C-706 Mech Seal Flush Seal Water Pump P-707 Mech Seal Flush Seal Water Pump P-708 Mech Seal Flush FIC-301 FIC-302 FIC-303 FIC-304 Flowing Indicating Controller Flowing Indicating Controller Flow Indicating Controller Flow Indicating Controller 8 P-703 Compressant Seal Water P-704 Compressant Seal Water C-705 Compressant Seal Water I C-706 Compressant Seal Water VAB.0001134990 * w EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL fx 4 V. INSTRUMENT LIST (Cont.) Item No. Description Service LA-701 LA-702 LA-703 LCV-301 LCV-701 High Level Alarm High Level Alarm High Level Alarm Level Control Valve Level Control Valve T-701 High Level T-702 High Level T-703 High Level T-703 Level Control T-702 Low Level Makeup LG-701 LG-702 LG-703 LIC-301 LS-701A LS-701B LS-701C LS-702A LS-702B LS-702C LS-702D LS-703C PAH-301 PA-7 01 PA-702 PA-703 PCV-301 PCV-302 PCV-303 PCV-304 PCV-305 PCV-306 PCV-701 PG-301 PG-302 PG-303 PG-304 PG-305 PG-306 PG-307 Level Gauge Level Gauge Level Gauge T-701 T-702 T-703 Level Indicating Controller T-703 Level Control Level Switch Level Switch Level Switch Level Switch Level Switch Level Switch Level Switch Level Switch T-701 Low Level T-701 High Level T-701 High-High Level T-702 Low Level T-702 Middle Level T-702 High Level T-702 High-High Level T-703 High-High Level High Pressure Alarm High Pressure Alarm High Pressure Alarm High Pressure Alarm T-701 High Pressure T-701 T-702 T-703 Pressure Control Valve Pressure Control Valve Pressure Regulator Pressure Regulator Pressure Regulator Pressure Regulator Pressure Control Valve Interstage Pressure Control Valve Interstage Pressure Control Valve P-703 Mech Seal Water Pressure P-704 Mech Seal Water Pressure C-705 Mech Seal Water Pressure C-706 Mech Seal Water Pressure T-701 Low Pressure Control Valve Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge P-703 Process Inlet P-703 Process Outlet P-703 Mech Seal Flush Outlet P-703 Mech Seal Flush Outlet P-703 Mech Seal Flush Inlet P-704 Process Inlet P-704 Process Outlet 9 VAB.0001134991 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL V. INSTRUMENT LIST (Cont.) Item No. Description PG-308 PG-309 PG-310 PG-311 PG-312 PG-313 PG-314 PG-315 PG-316 PG-317 PG-318 Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge PG-319 PG-320 PG-321 PG-322 PG-323 PG-324 PG-325 Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge PG-326 Pressure Gauge PG-327 Pressure Gauge PG-328 Pressure Gauge PG-329 PG-330 PG-331 PG-701 PG-702 PG-703 Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge Pressure Gauge t1 PIC-301 PIC-302 PIC-701 Pressure Indicating Controller Pressure Indicating Controller Pressure Indicating PR-301 Pressure Recorder Service P-704 Mech. Seal Flush Outlet P-704 Mech. Seal Flush Outlet P-704 Mech. Seal Flush Inlet C-705 Process Inlet C-705 Process Outlet C-705 Mech. Seal Flush Outlet C-705 Mech. Seal Flush Outlet C-705 Mech. Seal Flush Inlet C-706 Process Inlet C--706 Process Outlet C-706 Mech Seal Flush Outlet C-706 Mech Seal Flush Outlet C-706 Mech Seal Flush Inlet P-703 Compressant Seal Water P-704 Compressant Seal Water C-705 Compressant Seal Water C-706 Compressant Seal Water Existing Mech Seal Water Filter Inlet Existing Mech Seal Water Filter Outlet Existing Mech Seal Water Filter Inlet Existing Mech Seal Water Filter Outlet P-707 Discharge P-708 Discharge FD-301 and FD-301S Outlet T-701 T-702 T-703 Interstage High Pressure Controller Interstage Low Pressure Controller T-701 Low Pressure Control Controller T-701 Pressure Recorder 10 VAB.0001134992 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL V. INSTRUMENT LIST (Cont.) Item No. Description Service PS-701 PS-702 PS-703 High Pressure Switch High Pressure Switch High Pressure Switch T-701 T-702 T-703 PT-301 Pressure Transmitter Secondary Vacuum Pump And Compressor Start/Stop RD-307 RD-703 RD-704 RD-705 RD-706 Rupture Disc Rupture Disc Rupture Disc Rupture Disc Rupture Disc EA-301 Process Outlet P-703 Process Outlet P-704 Process Outlet C-705 Process Outlet C-706 Process Outlet RO-301 RO-302 Restriction Orifice Restriction Orifice C-705 Compensating Seal Water C-706 Compensating Seal Water SV-301 SV-302 SV-303 SV-304 SV-305 SV-306 SV-307 SV-701 SV-702 SV-703 Relief Valve Relief Valve Relief Valve Relief Valve Relief Valve Relief Valve Relief Valve Relief Valve - 150 PSIG Relief Valve - 150 PSIG Relief Valve - 150 PSIG P-703 Process Outlet P-704 Process Outlet C-705 Process Outlet C-706 Process Outlet FD-301 Process Inlet FD-301S Process Inlet EA-301 Process Outlet T-701 T-702 T-703 SW-301 SW-302 SW-303 SW-304 SW-305 SW-306 SW-701 Hand/Off/Auto Switch > Hand/Off/Auto Switch Hand/Off/Auto Switch Hand/Off/Auto Switch On/Off Switch On/Off Switch Hand/Off/Auto Switch P-703 Start/Stop P-704 Start/Stop C-705 Start/Stop C-706 Start/Stop P-707 Start/Stop P-708 Start/Stop P-701 Start/Stop TA-70 2 TA-703 High Temperature Alarm T-702 High Temperature Alarm T-703 TCV-701 TCV-709 Temp. Control Valve Temp. Control Valve EA-701 Temperature Control EA-709 Temperature Control * * + # *mm m VAB.0001134993 mPMpiHPp EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL V. INSTRUMENT LIST (Cont.) Item No. Description Service TG-301 TG-302 TG-303 TG-304 TG-701 TG-702 TG-703 TG-709A TG-709B Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge Temperature Gauge EA-301 Process Inlet EA-301 Process Outlet EA-301 CWS Line EA-301 CWR Line T-701 T-702 T-703 EA-709A CWR Line EA-709B CWR Line TIC-701 TIC-709 Temperature Indicating Controller Temperature Indicating Controller EA-701 Temperature Control EA-709 Temperature Control TS-702 TS-703 High Temperature Switch T-702 High Temperature Switch T-703 * f 12 VAB.0001134994 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES A. General Information The Emission Recovery System is designed to continuously with a minimum of operator attention. The i lain controls for the system are located on a local instrument panel on the north wall of the second floor of V-ll. Secondary controls are located in the vinyl control room (See Section VI. C.). B. Local Panel and Switches The local control panel consists of the following items: 1. Explosion Proof Horn. 2. Explosion Proof Ronan Alarm Panel. 3. Explosion Proof "Killark" Control Panel. 4. PIC-701, Foxboro 43AP Pneumatic Pressure Indicating Controller For T-701 Low Pressure Control. 5. TIC-701, Foxboro 43AP Pneumatic Temperature Indicating Controller for EA-701 Cooling Water Flow Control. 6. TIC-709, Foxboro 43AP Pneumatic Temperature Indicating Controller For EA-709 A, B, and C Cooling Water Control. 7. PIC-301, Foxboro 43AP Pneumatic Pressure Indicating Controller For Interstage High Pressure Control. 8. PIC-302, Foxboro 43AP Pneumatic Pressure Indicating Controller for Interstage Low Pressure Control. 9. LIC-301, Foxboro 43AP Pneumatic Level Indicating Controller For T-703 Level Control. The "Killark" control panel consists of start/stop switches for P-707 and P-708 and an open/close switch for the batch water stripper and the new module blowdown tank. It also contains run and open/close lights for these items. . . ; t PIC-701 is used to control the vacuum in the inlet K.O. tank T-701. The normal set point is 15 in. Hg. vacuum. This controller sends a 3-15 PSI signal to PCV-701, the pressure control valve. A signal of 15 PSI will open PCV-701 completely and a 3 PSI signal will close PCV-701 completely. This controller and valve regulatesthe flow of RVCM which enters T-701 to maintain a minimum pressure of 15 inches Hg vacuum. TIC-709 is used to control the seal water temperature for the Emission Recovery System. The normal set point is 110F. This controller sends a 3-15 PSI signal to TCV-709 which is located in the cooling water return line of the seal water coolers EA-709A, B, and C. A 15 PSI signal closes TCV-709 and a 3 PSI signal opens it. This valve regulates the amount of cooling water flowing through the shell side of the seal water coolers in order to achieve the desired seal water temperature. 13 VAB.0001134995 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL OPERATING PROCEDURES (Cont.) TIC-701 is used to control the temperature of the vapor stream from EA-701. The normal set point is 110F. This controller sends a 3-15 PSI signal to TCV-701 which is located in the cooling water return line of the inlet steam condenser, EA-701. A 15 PSI signal closes TCV-701 and a 3 PSI signal opens it. PIC-301 is used to control high pressure in T-702 to prevent high inlet pressures to C-705 and C-706. The normal set point is 5 PSIG. The controller sends a 3-15 PSI signal to PCV-301 which is located on the process inlet to the vacuum pumps. High pressure in T-702 causes PCV--301 to close and throttle the vapor to the vacuum pumps and com-- PIC-302 is used to control low pressure in T-702 to prevent low inlet pressures to C-705 and C-706. The normal set point is 1 PSIG. The controller sends a 3-15 PSI signal to PCV-302 located on the vapor recirculation line between T-702 and T-703. Low pressure in T-702 causes PCV-302 to open and allow vapors from the discharge of C-705 and C-706 to recirculate to the inlet. I LIC-301 is used to control the level in T-703. The controller sends a 3-15 PSI signal to LCV-301 located on the drain line between T-703 and T--702. High level in T-703 causes TCV-301 to open allowing water to flow from T-703 to T-702. The reamaining items of the local control panel deal with system malfuntions and alarms. The alarms are as follows: Vessel T-701 Alarm F ? *r PAH-701, High Pressure LAH-701, High Level Setpoint 15 PSIG Element Pressure Switch Float T-702 PAH-702, High Pressure LAH-702, High Level TAH-702, High Temp. 25 PSIG - 175F Pressure Switch Probe Temperature Switch T-703 PAH-703, High Pressure LAH-703, High Level TAH-703, High Temp. 100 PSIG -- 175F Pressure Switch Float Temperature Switch VAB.0001134996 EMISSION RECOVERY SYSTEM h ABERDEEN CHEMICAL PLANT OPERATING MANUAL OPERATING PROCEDURES (Cont.) If any one of the above alarm setpoints is exceeded, then the element will trip the alarm on the local control panel and the following sequence of events occurs: 1. Local alarm light comes on. 2. Local alarm horn sounds. 3. The vacuum pumps and compressors shut down. 4. Emission Recovery Shutdown alarm sounds in the vinyl control room. Any upset must be corrected before the system can be restarted. If a seal water pump is on, the vacuum pump and compressor in the hand posi tion will automatically start back up when the alarm problem is cor rected. If there is any delay in restarting the system the seal water pump should be shut off. The next section will outline the procedure to clear each alarm. 1. T-701 High Pressure Alarm (PAH-701) This is set at 15 PSIG. a. Check the pressure gauge on T-701. b. Check the batch water stripper pressure. It must be lower than T-701 pressure. If it is not, pull the pressure off the batch water stripper with the large recovery system. c. Open the 2 inch manual drain valve on the bottom of T-701. This bleeds pressure to the batch water stripper. d. Make sure that one vacuum pump and one compressor are switched to hand and that the other vacuum pump and compressor are in auto. 2. T-701 High Level Alarm (LAH-701) S fr ' a. Check water level in the gauge glass on T-701. b. Check to see if drain pump P-701 is in the auto mode. c. Check CV-701 which is the automatic drain valve on T-701. It should be open already, but if it is not open the manual drain on the bottom of T-701 and proceed with the next step. d. Close both two inch ball valves on the level well on T-701. e. Open the one inch HPSW valve on the top of the level well and slowly fill the level well with water. f. CV-701 should open when the water level reaches the middle level switch. If CV-701 will not open, an instrument man must work on the middle level switch.' 15 VAB.0001134997 EMISSION RECOVERY SYSTEM h ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) 2. T-701 High Level Alarm (LAH-701) (Cont.) g. Check the pressure drop across DST-301 and check P-701 for cavitation (the discharge pressure gauge for P-701 would be jumping around erratically). If DST-301 is plugged, switch to the other side and clean strainer. 3. T-702 High Pressure Alarm (PAH-702) This is set at 25 PSIG. a. Check pressure gauge on T-702. b. Check batch water stripper pressure. It must be lower than T-702 pressure. If it is not, pull the pressure off the batch water stripper with the large reactor recovery system. Open the two inch manual drain valve on the bottom of T-702. This bleeds T-702 pressure to the batch water stripper. d. Make sure that one vacuum pump and one compressor are switched to hand and that the other units are in auto. 4. T-702 High Level Alarm (LAH-702) a. Check water level in the gauge glass on T-702 b Check to see if drain pump P-701 is in the auto mode. Check CV-311 which is used to automatically drain T-702 to T-701 discharge. This valve is located on the discharge side of the seal water pumps. It should be open. If it is not, an instrument man must work on the upper float level switch. d. If CV-311 is operating prpperly and T-702 will not'drain check for plugged strainer at the drain pump or a closed valve between the drain line and batch water stripper. % e. To manually drain T-702 open the 2 inch manual drain valve on the bottom. 5. T-702 High Temperature (TAH-702) This is set at 175F. a. Check temperature in T-702. If it is high proceed with the next step, if not have instrument man work on temperature switch. b. Add HPSW to T-702 to cool down the temperature. c. Check TIC-709 operation. Check that the seal water coolers are properly set up and that the cooling water valves are opened. VAB.0001134998 16 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL * VI. OPERATING PROCEDURES (Cont.) 5. T-702 High Temperature (TAH-702) (Cont.) d. Check TIC-701 temperature. If it is abnormally high, check TIC-701 operation and check that EA-701 is properly set up. maintenance damage f. Before operating system put all seal water coolers on line. 6. T-703 High Pressure Alarm (PAH-703) This is set at 100 PSIG. a. Check pressure gauge on T-703. If the pressure is still high check the valves between T-703 and the RVCM receiver and proceed with next step. b. Check pressure in the batch water stripper to which water is being drained. It must be lower than T-703 pressure. If it is not, pull the pressure off the batch water stripper with the large reactor recovery system. c. Open the two inch manual drain valve on the bottom of T-703. This bleeds T-703 pressure to the BWS. d. After the system is restarted check EA-301 for high differen tial pressure. 7. T-703 High Level Alarm (LAH-703) a. Check water level in the gauge glass on T-703. b. Check LCV-301 which is the automatic drain valve on T-703. It should be open already, but if it is not, open the bypass line around LCV-301. Check that LIC-301 set point is at 6 to 10 inches water. c. If LIC-301 is set right, have an instrument man look at LT-301. 8. T-703 High Temperature Alarm (TAH-703) This is set at 175F a. Check temperature in T-703. If it is high proceed with next step, if not have instrument man work on temperature switch. b. Add HPSW to T-703 to cool down the temperature. c. Check TIC-709 operation. Check that the seal water coolers are properly set up and that the cooling water valves are open. VAB.0001134999 EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) d. Check TIC-701 temperature. If it is abnormally high, check TIC-701 operation and check that EA-701 is properly set up. e. Have maintenance check the compressors for any damage. f. Before operating system put all seal water coolers on line. C. Control Room Panel and Switches The only controls for the Emission Recovery System that are installed in the vinyl control room are two valve switches and one alarm. The Emission Recovery System is designed to be controlled from a local panel in V-ll as described in Section VI. B. of this operating manual. The one alarm is a shutdown alarm that occurs when the Emission Recovery System has a malfunction and vacuum pumps and compressors are automatically shut down. When this alarm sounds, the panel operator will notify the "A" operator in the field. The ,,AM opera tor will go to the local control panel in V-ll and investigate the alarm. The valve switch labeled CV-1 controls a two inch plug valve in the line to the VCM tank farm. This switch and valve must be in the open position unless the Emission Recovery System is down for main tenance The other valve switch associated with the Emission Recovery System is labeled CV-601. This switch controls a three inch plug valve in the batch water stripper recovery line to the Emission Recovery System. It should be open except for the following circumstances. V * 1. The Emission Recovery System is down for maintenance. 2. The batch water strippers are down for maintenance. The pressure recorder for T-701, PR-301, is located on the old module vinyl control panel on the D-300 panel. This recorder is calibrated from 30" Hg vacuum to 150 PSIG. Also, located on the old module recovery panel, are run lights for the vacuum pumps, compressors, and seal water pumps and amp meters for the vacuum pumps and compressors. VAB.0001135000 TW EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) D. Pre-Startup Checks (See Drawing MS-9630-42-1-D) 1. Open the following valves (all others excluding safety relief valve isolation valves must be closed): a. EA-701 Inlet Condenser Two 2 Inch block valves at PICV-701 One 2 inch block valve at CV-1 One 3 inch plug valve for vaporinlet to EA-101 One 3 inch plug valve for vapor outlet from EA-101 Two 4 inch cooling water supply valves to EA-101 Two 4 inch cooling water return valves from EA-101 Two 3 inch block valves on TCV-701 valve manifold b. T-701 Inlet K.O. Drum One 3 inch ball valve for vapor inlet to T-701 One 3 inch ball valve for vapor outlet from T-701 One 3 Inch ball valve on T-701 liquid drain to DST-301 Two 3 inch ball valves on DST-301 inlet and outlet Two 2 inch ball valves on T-701 level well Two 3 inch valves between P-701 and the BWS c. P-703 Vacuum Pump One 3 inch ball valve for P-703 vapor outlet One 2 inch ball valve for seal water inlet to P-703 Three 1/2 inch ball valves for mechanical seal purge water inlets to P-703 Two 1/2 inch valves for mechanical seal purge water outlet on P-703 Two 3/4 inch ball valves on the inlet and outlet to the MSPW filter d. P-704 Vacuum Pump One 3 inch ball valve for P-704 vapor outlet One 2 inch ball valve for seal water inlet to P-704 Three 3/4 inch ball valves for mechanical seal puree water inlets to P-704 Two 1/2 inch valves for mechanical seal purge water outlet on P-704 Two 3/4 inch ball valves on the inlet and outlet to the MSPW filter 19 h VAB.0001135001 I EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) D. Pre-Startup Checks (Cont.) e. T-702 Vacuum Pump Seal Water Separator One 3 inch ball valve for vapor inlet to T-702 One 3 inch ball valve for vapor outlet from T-702 Two 2 inch valves in the drain line from T-703 to T-702 Two 1 inch valves at LCV-301 between T-703 and T-702 One 3 inch ball valve for seal water pump suction from T-702 Two 2 inch ball valves on T-702 level well f. C-705 VCM Compressor One 3 inch ball valve on discharge of C-705 One 2 inch ball valve for seal water inlet to C-705 Three 1/2 inch ball valves for mechanical seal purge water inlets to C-705 Two 1/2 inch valves for mechanical seal purge water outlet on C-705 One \\ inch ball valve on the compensating seal water line to C-705 g. C-706 VCM Compressor One 3 inch ball valve on discharge of C-706 One 2 inch ball valve for seal water inlet to C-706 Three 3/4 inch ball valves for mechanical seal purge water inlets to G-706 Two 1/2 inch valves for mechanical seal purge water outlet on C-706 One lh inch ball valve on the compensating seal water line to C-706 h. T-703 Compressor Seal Water Separator One 6" ball valve for vapor inlet to T-703 One 3" ball valve for vapor outlet from T-703 Two 2" ball valves on T-703 level well One 3" ball valve for vapor outlet to EA-301 * VAB.0001135002 I A EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) D. Pre-Startup Checks i. EA-301 VCM Condenser Two 3U valves on the process inlet to EA-301 One 3" plug valve on the process outlet from EA-301 Three 2" plug valves on the line to the old module RVCM receivers Two 4" gate valves on the cooling water supply to EA-301 Two 4" valves on the cooling water return from EA-301 j. Seal Water Pump NP-301, Filter FD-301 One 3" ball valve for suction to P--707 or P-708 One 2" ball valve for discharge from P-707 or P-708 One 2" ball valve upstream of filter FD-301 (FD-301S Spare) One 2" ball valve downstream of filter FD-301 (FD-301S Spare) k. Seal Water Coolers, EA-709A, B, C (Note: These are run in parallel) One 2" ball valve on seal water inlet to EA-709A One 2" ball valve on seal water outlet from EA-709A One 2" ball valve on seal water inlet to EA-709B One 2M ball valve on seal water outlet from EA-709B One 2" ball valve on seal water inlet to EA-709C One 2" ball valve on seal water outlet from EA-709C One 3" ballvalve for cooling water supply to EA-709A One 3M ballvalve for cooling water return from EA-709A One 3" ballvalve for cooling water supply to EA-709B One 3" ballvalve for cooling water return from EA-709B One 3" ballvalve for cooling water supply to EA-709C One 3M ballvalve for cooling water return from EA-709C One 3" ball valve upstream of TICV-709 One 3" ball valve downstream of TICV-709 Note: If while down the ERS system has been opened to atmos phere, oxygen needs to be removed from the system by filling the system completely with water and then breaking vacuum with steam or VCM and draining the excess water to the batch water strippers. Oxygen in the system at startup is a possible explosion hazard. 21 VAB.0001135003 I EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) 2. Fill T-702 and T-703 half full with water from the manual HPSW lines at the top of the level gauges. 3. Start the hydroquinone injection to T-702. Set the injection rate as described by the procedure sign at the hydroquinone tank. 4. The VCM tank farm inlet valve CV-1 and the batch water strip pers inlet valve CV-601 should be closed. 5. The vacuum pump high suction pressure controller PIC-301 should be set at 5 PSIG. 6. The compressor low suction pressure controller PIC-302 should be set at 1 PSIG. 7. T-701 low pressure controller PIC-701 should be set at 15 in Hg vacuum. 8. The inlet condenser temperature controller TIC-701 should be set on 110F. 9. The seal water cooler temperature controller TIC-709 should be set on 110F. 10. Seal water flow controller FIC--301 and FIC--302 on vacuum pumps P-703 and P-704 should be set on 12 GPM. 11. Seal water flow controller FIC-303 or FIC-304 on compressors C-705 and C-706 should be set on 18 GPM. L 12. T-703 level controller LlC-301 should be set at 6 to 10 inches water. E. Start-up Sequence: 1. Start one seal water pump P-707 or P-708 by depressing the start switch on the local control panel. Note: The vacuum pumps and compressors will not start unless the seal water pump is running. VAB.0001135004 T P *WV f t EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) 2. Start one compressor C-705 or C-706 by placing the local hand-off-auto switch in the hand position. Place the other compressor in auto so that it will start on demand. 3. Start vacuum pump P-703 or P-704 by placing the local hand-offauto switch in the hand position. Place the other vacuum pump in auto so that it will start on demand. 4. Place drain pump P-701 in the auto position. Note: Caution should be taken around the vacuum pumps and compres sors since the units in automatic can start up at any time. F. Post Start-up Checks 1. Verify that the pressure in T-701 decreases to the setpoint on PIC-701 and stabilizes. PIC-701 operates PCV-701 which allows VCM from the large recovery system VCM collect tank to enter T-701 to control the vacuum in T-701. 2. Verify that the seal water flow to the vacuum pumps and com pressors is at the setpoint on flow controllers. 3. Check the discharge pressure on the vacuum pump. It should be between 1 and 5 PSIG. 4. Check the discharge pressure of the compressor. It should be a few PSI above the pressure on the receiver to which VCM is being transferred. 5. Check the water level in T--703 and T--702. Adjust if necessary. 6. Check seal water pump discharge pressure. It should be 125 PSIG 10 PSIG. L V 7. Check seal water pressure downstream of the seal water filter FD-301. It should be 2 to 5 PSI less than the upstream pres- G. Systems Operation Once the Emission Recovery System has been successfully started up and all checks have been completed, the system can then be used for the following: 1. VCM Tank Farm Recovery. 2. VCM Railcar Unloading Line Recovery. 3. Steam Stripping of the Batch Water Strippers. 4. Vessel Purging. A VAB.0001135005 i EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) G. Systems Operation (Cont.) Each use will be outlined in the subsequent sections. 1. VCM Tank Farm Recovery This portion of the system collects VCM vents from the follow ing: a. Double Mechanical Seals on the VCM Pumps b. Corken Compressor Packing c. Corken Compressor Relief Valve Discharges d. Corken Compressor K.O. Pot Blowdown e. VCM Sphere and Bullet For these operations it is necessary that the Emission Recovery System be operating at 15 in Hg vacuum and that CV-1 is open. This allows the Emission Recovery System to pull VCM vapors from the tank farm through a 2 inch line. 2. VCM Railcar Unloading Line Recovery This operation is to begin when the yard operator determines that the VCM cars are empty and are ready to be disconnected from the unloading lines. The railcar pressure at this point will normally be about 10--20 PSIG. To perform this operation properly, the Emission Recovery System must be operating at 15 in. Hg vacuum and control valve CV-1 must be open. It is the responsibility of the vinyl department to maintain these condi tions at all times. Example for North unloading station: L 1. Shut off all Corken cdmpressors. 2. Close 6" block valve on liquid line and 4" block valve on vapor line. These lines and valves are located on the west side of the compressor shed. 3. Close the three valves on railcar. 4. Open switch SW-201 located at the North unloading station platform. Note: Switches SW--202, SW--303 are located at the other two platforms. Actuating this switch will open two 1 inch control valves (Bettis operators) which are tied into the two 3 inch unloading lines for the North unloading station. This will allow the Emission Recovery System to pull a vacuum on the unloading lines. * VAB.0001135006 *nf mW EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT k OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) G. Systems Operation (Cont.) 5. When the pressure on the unloading lines reaches 10 in Hg vacuum close the three valves on the unloading lines on the west side of the platform. Note: Pressure gauges are located at each unloading platform. At this point the stainless steel flex hoses are valved off at both ends and are at 10 in. Hg vacuum. 6. Disconnect the 2 unloading lines from the tank car and open the 1/2 inch vacuum breaker valves on each unloading line. 7. Reset switch SW-201. 8. Repeat steps 3 through 7 for all unloading stations. 3. Steam Stripping of the Batch Water Strippers Note: Open CV-601 and leave open. Close only when the Emission Recovery System is down. Refer to the batch water strippers operating manual for steam stripping procedures for that system. 4. Vessel and Equipment Purge System This system consists of a manifold system to purge vessels and equipment in VCM service prior to opening by evacuating the vapor with the Emission Recovery System and displacing the VCM with steam. i.' f The following general procedure is to be followed to purge VCM from vessels or equipment. In the old module, some of the ves sels may be evacuated directly into the Emission Recovery Sys tem while others will be evacuated by the Emission Recovery System through the batch water strippers. In the new module the vessels and equipment will be evacuated by the Emission Recovery System through the blowdown tank. 1. The following old module vessels can be evacuated directly into the Emission Recovery System tank T-701. When purging one of them, open the 3" ball valve in the vessel purge line which enters the Emission Recovery System on the second floor of V-ll. VAB.0001135007 Af EMISSION RECOVERY SYSTEM ABERDEEN CHEMICAL PLANT OPERATING MANUAL VI. OPERATING PROCEDURES (Cont.) G. Systems Operation (Cont.) a. The fresh and recovered VCM receivers. b. The RVCM collect tank. c. The recovered VCM condensers. d. The recovery seal water separators. e. The recovery K.O. pots. 2. Open the evacuation valve on the vessel or equipment. 3. Evacuate with the Emission Recovery System. 4. Connect a steam hose to the vessel or equipment and begin steam purging. 5. Purge the vessel or equipment for the amount of time speci fied in Tables I and II. 6. All VCM filters will be evacuated and purged through the batch water stripper or new module blowdown tank. 7. Close the steam and evacuation valves after the purge time is complete. 8. Before entering the vessel or equipment, check for VCM contamination with a portable hydrocarbon detector. If there is a reading, repeat the steaming and evacuation until the purge is complete. 9. Allow the vessel or equipment to cool down before entering. t* T m* Plfllipn w VAB.0001135008 CONOCO NO. 45-011 45-012 45-013 45-017 45-018 45-005 45-028 45-027 45-026 45-301 45-308 55-002 55-004 55-311 55-005 55-006 55-008 55-009 55-340 64-008 64-691 64-009 EPA COMPLIANCE OF VCM EMISSIONS VESSEL AND EQUIPMENT PURGING ABERDEEN CHEMICAL PLANT TABLE I; OLD MODULE VESSEL AND EQUIPMENT PURGING USE VOLUME GALLON PURGING TIME <3 35 SCFM, MIN. North VCM Receiver Middle VCM Receiver Fresh VCM Receiver Separator Separator RVCM Collect Tank South K.O. Pot North K.O. Pot K.O. Tank K.O. Tank K.O. Tank Seal Water Cooler Seal Water Cooler Seal Water Cooler Seal Water Cooler Seal Water Cooler Recovery Cond Recovery Cond Recovery Subcooler Fresh VCM Filter Rec. VCM Filter Fresh VCM Filter 7390 7390 7390 128 128 560 590 590 566 456 456 67 67 67(1) 42v ' 42(1) 124(1) 124(' 1)7 171u; -- -- -- 40 40 40 1 1 3 3 3 3 3 3 1 1 1 1 1 1 1 15<2) 15 (2> 15 K J (1) Tube volumes are given for exchangers. (2) Must be purged because filter is saturated with VCM. h VAB.0001135009 i EPA COMPLIANCE OF VCM EMISSIONS VESSEL AND EQUIPMENT PURGING ABERDEEN CHEMICAL PLANT TABLE II: AND CONOCO NO 45-317 89-520 45-745 45-762 45-763 45-760 45-761 55-335 55-336 55-337 55-338 55-334 64-718 64-719 64-742 USE VOLUME, GALLON West VCM Receiver Middle VCM Receiver Fresh VCM Receiver Separator Separator K.O. Pot K.O. Pot Seal Water Cooler Seal Water Cooler Recovery Cond Recovery Cond Recovery Subcooler Fresh VCM Filter Rec. VCM Filter Fresh VCM Filter * 7390 7390 9275 1380 1380 1520 1520 52 *^(1) 144, * 44(1) 171 C^ l')} ---- ---- PURGING TIME @ 35 SCFM, MIN 40 40 50 8 8 8 8 1 1 1 1 15 (2) 15 15(Z) (1) Tube volumes are given for exchangers. (2) Must be purged because filter is saturated with VCM. i VAB.0001135010 EMISSION RECOVERY SYSTEM DAILY WALK-AROUND INSPECTION REPORT Date Time Operator A Water level in T-702 (% of level sight glass) ............................ ..................................... Water level in T-703 (% of level sight glass) ............................ ..................................... Seal water pump running (P-707 or P-708) discharge pressure PSIG Seal water pressure downstream of filter.......................................... ...............................PSIG Hydroquinone being injected (Yes or No) .......................................... ..................................... Water level in T-701 (% of level sight glass) ............................ ..................................... T-701 inlet temperature and pressure (PSIG or in. Hg vac) . F CV-1 (Open or closed)................................................... ................................ ........................................ CV-601 (Open or closed) ............................................................................... ..................................... Vacuum pump P-703 switch position (hand, off, or auto) If in auto, is it running (Yes or No)........................................................................................ ................... ................ Mechanical seal purge water to vac pump P-703 (rotometer and discharge pressure readings)................... North seal % __________ PSIG South seal % PSIG Vacuum pump P-704 switch position (hand, off, or auto) If in auto, is it running (Yes or No)........................................................ ............................ Mechanical seal purge water to vac pump P-704 (Rotometer and discharge pressure readings)........................................................ North seal % ___________________ PSIG South seal % PSIG Compressor C-705 switch position (hand, off, or auto) If in auto, is it running (Yes or No).......................................... .... ........................................................... ................... MSPW to compressor C-705 (Rotometer and discharge pressure readings) North Seal% PSIG South Seal% PSIG Compressor C-706 switch position (hand, off, or auto) If is auto, is it running (Yes or no)............................................................................................................ MSPW to compressor C-706 (rotometer and discharge pressure readings) North Seal % ___________________PSIG South Seal % ___________________PSIG 29 VAB.0001135011 J Liquid ring seal water flow to vac pumps (P-703 and P-704) GPM Liquid ring seal water flow to compressors (C-705 and C-706) GPM Vac pumps and compressors rupture discs condition (all OK or indicate problem).................................................................................................................... T-701 low pressure controller PIC-701 pressure (PSIG or in. Hg Vac) Inlet condenser temp controller TIC-701 temperature Seal water cooler temp controller TIC-709 temperature. . . T-703 level controller LIC-301 reading . . Vac pump suction press, controller PIC-301 pressure Compressor suction pressure controller PIC-302 pressure. . . Describe any alarms/shutdowns (include alarm type, cause, and action taken to correct problem) GPM GPM FO FO PSIG PSIG A Were seal water filters changed today? TURN THIS FORM IN TO THE SHIFT SUPERVISOR WHO WILL TURN IN TO OPERATIONS SUPERVISOR (CHRIS TURNER) FOR REVIEW. 30 VAB.0001135012 V" p i i t i t < L r ......1 :|MMli --!MI'................... ................ ! " I i: I t I / i i i i i ii i VAB.0001135013