Circulair Heat Installed Under Window. Standard Outlet Grille
Circulair Heat is an improved convection heating unit of the concealed type for use with hot water, steam, vacuum or vapor systems in place of cast iron radiators.
The Circulair Heat Unit occupies only a fraction of the space required normally for room heating equipment and consists of a carefully designed seamless copper tube on which are pressed die-stamped fins evenly spaced. Circulair Units are avail able in various widths and lengths and may be concealed in walls or cabinets.
The Concealed Circulair Heater is usually plastered in the wall but a removable plaster wall panel is available where ready access to piping, valves and traps
is desired. This plaster panel is plastered
on the job when the wall is plastered and is
invisible when the wall is finished.
Circulair Heat Units are rated in equiva
lent square feet of cast iron radiation. All
ratings are based on 240 B.t.u. per square
foot and were established by actual con
densation tests. Capacities depend upon
(1) Type of heater, (2) Length of heater,
(3) Height of stack.
A wide variety of grilje designs
[ are available to harmonize with
II various types of architectural
ll treatment.
'
M For complete engineering and
installation data send for latest
Circulair catalog.
<<
Type D Grille
656
Mi Type C Grille
Heaters, Unit
The Dixie Blower Company
1351 West 37th Place, Chicago, 111.
Manufacturers of Dixie Unit Heaters
Dixie Unit Heater
The Dixie Unit Heater is adapted to any service for which a unit heater can be used, including the heating of ware houses, factories, offices, theatres, garages, churches, auditoriums, and many special applications for which a heater of high quality is required.
The Dixie Unit Heater is so constructed that it can be either suspended from the steam line or from an overhead support. The direction of the air is regulated by the adjustable shutters, at any angle from a horizontal direction straight down to the floor.
Dixie Unit Heaters are constructed and tested to operate continuously on any steam pressure up to 150 lb. Dixie cores have been tested at several times this pressure and found to be satisfactory. This is made possible by the use. of the highest grade material throughout andby the patented compression coupling, which eliminates the possibilities of. all leaks between the tubes and the headers. Each tube is inserted in its proper place and.the coupling tightened up by hand. Each core is a job in itself.
The tubes of which the Dixie core is con
structed are made of heavy weight % in.
seamless copper tubing upon which a spiral copper fin is securely fastened.
is guaranteed to be leak-proof. A further outstanding feature of this design is the ease with which a tube can be replaced in case of damage. It is only necessary to unscrew the coupling and lift out the tube. The hole in the header can be plugged with a in. pipe plug and the unit put back into operation. The Unit need not be
Cross Section of Compression Coupling Used in the Dixie Unit Heater
out of service more than a few.minutes, an incalculable advantage where-service is required.
In a test to determine the holding strength of this compression coupling,
11,000 lb. (2'A tons) pull was exerted try
ing to pull the headers apart. Although the tubes were stretched nearly one-half inch the compression couplings held per fectly and the unit remained intact.
Compression Coupling
An outstanding feature of the Dixie Unit Heater is the patented compression couplings employed between the tubes and the headers. These coup lings insure a connection which
Ratings at 5 lb. Steam Pressure
Air Air Entering Leaving Heater Heater
F. F.
B.t.u.
Con Eqtiiv. densate Sq.Ft.
Lbs. Direct per Hour Rad.
Cu. Ft. Air
per Minute
Ship ping Weight Lbs.
40
No. 50 1700 60
65
70
130 465240 484 1920 6400
550
136 436500 454 1816 6400
550
141 410680 428 1712 6400 ' 550
143 401000 416 1664 6400
550
144 387020 404
1616 6400
550
40 No.' 50
800 60 B 65
70
130 232620 136 218250
141 205340 143 200500
144 193510
242 227 214 208 202
960 3200 908 3200 856 3200 832 3200 808 3200
230 230
230
230 230
40
130 146880 155
612 i300
170
No. 50 135 138240 146 576 1300 170
500 60
143 128880 136
537 1300
170
65
145 124800 134
520 1300
170
70
147 121160
129
509 1300
170
40 No. 50 200 60
65
70
134 50880 53 212 920 1 120
138 45120 47 168 920 120
142 40320 42 168 920 120
143 38400 40 160 920 . 120
144 34520
37
148 ' . 920
120
Rear View Dixie Unit Heater
Dixie Unit Heater No. 800--Model A uses an 850 r.p.m. motor.- Ratings
on Model A are 25 per cent less than Model B. Three-speed alternatingcurrent motors operate at 500, 850 and 1150 r.pjn.
657