Document MoaRq6kJBjeR1vJKYgGOXb7Ea
1102
CHAPTER 49
1955 Guide
Table 3; Performance Requirements of Water Meters*
Sirs In.
*4 _____
a........ -I.-*-
Normal Test-Flow Limits GPM
1 to 2 to
3 to 5 to
20 34 53 100
S to 160 16 to 315 28 to 500 48 to 1.000
.
Minimum Test-Flow GPM
8 . . iS
2 4
12
* American Water Works Association Standards: Registration. The registration on the meter shall indicate the quantity recorded to be not Jess *Vp 93 percent jaor more than 103 percent of the water actually passed through the meter while it is being tested at rates of flow within the specified limits herein under normal test flow limits: There shall be not less 90 percent of the actual flow recorded when a test is made at the rate of flow set forth under minimum test
flow.
The water demand for hose bibbs or other large demand fixtures taken off the building main is frequently the cause of inadequate water supply to the upper floor of a building. This condition may be prevented by sizing the distribution system so that the pressure drops from the street main to all fixtures are the same. It is good practice to maintain the building main of ample size (not less than 1 in. where possible) until all branches to hose bibbs have been connected. Where the street main pressure is excessive and a pressure reducing valve is used to prevent water hammer or exces sive pressure at the fixtures, it is frequently desirable to connect hose
bibbs ahead of the reducing valve.
The principles involved in sizing either up-feed or' down-feed systems are the same. The principal difference in procedure is that in the downfeed system, the difference in elevation between the house tank and the
fixtures provides the pressure required to overcome pipe friction.
Procedure for Sizing Cold Water Systems The recommended procedure for sizing piping systems is outlined in fol
lowing paragraphs 1 to 6, inclusive. 1. Draw a sketch of the main lines, risers, and branches, and indicate the fixtures
to be served. Indicate the rate of flow of each fixture.
Table 4. Allowance in Equivalent Length of Pipe for Friction Loss i Valves and Threaded Fittings
Equivalent Length of Pipe for Various Fittings
Diameter
of Fitting In.
90 Deg
Standard Ell Ft
Ji- - 14-____ X
1 . ...
IX-
m
Z--
2X--
. ..
314---------
4 5
6_,---------------------
i
2
2.5 3 4 5 7
8
10
12
14 17
20
45 Deg Standard
Ell Ft
0.6 1.2
1.5 1.8 2.4 3 4 5
6
7
8 10 12
90 Deg Side Tee
Ft
Coupling or Straight
Run of Tee Ft
1.5 0.3 3 0.6 4 0.8 5 0.9 6 1.2 7 1.5 10 2 12 2.5 15 3 18 3.6 21 4.0 25 5 30 6
Gate Valve
Ft
0.2 0.4 0.5 0.6 0.8 1.0 1.3 1.6 2 2.4 2.7 3.3 4
Globe Valve
Ft
8 15 20 25 35 45 55 65 80 100 125 140 165
Angle Valve
Ft
4 8 12 15 18 22 28 34 40 50 55 70 80
Water Services
1103
2. Using Table 2, compute the demand weights of the fixtures in fixture units. 3. Determine the total demand in fixture units and, using Fig. 1 or Fig. 2, find the expected demand in gallons per minute.-
4. Determine the equivalent length of pipe in the main lines, risers, and branches. Since the sizes of the pipes are not known, the exact equivalent length for various fittings, etc., cannot be made. Add the equivalent lengths, starting at the street main and proceeding along the service line, the main line in the building, and up the riser to the top fixture of the group served.
5. Determine the average minimum pressure in the street main and the minimum pressure required for the operation of the topmost fixture. This latter pressure should be 8 to 15 psi.
. 6! Calculate, by means of Equation 1, the approximate design value of the average pressure drop per 100 ft of pipe in the equivalent length determined in paragraph 4.
p = [P - 0.4377 - 10] ^
where p = average pressure loss per 100 ft of equivalent length of pipe, psi. P = pressure in street main, psig.
(1;
Table 5. Equivalent Lengths of Iron Pipe to Give Same Loss as Special Fittings and Apparatus
Fitting Apparatus
Nominal Diameter of Pipe--Inches
Vs H 1 IM
11
30-ga| Vertical hot-water tank, % in. pipe. . . ' 4
30-gal Horizontal hot-water tank, *K in. pipe.. 1.2
Water meters (No valves included)
K in. with K in. connections.....................
67
% in. with % in. connections....................... 4.8
in. with % in. connections........... 1 n. with 1 in. connections . , , 1)4 m. with 1 in. connections........................................
34
_
'rater softener..
--
17
5
28. 20 14
9
44
50-200
56 16
90 64 45 30 14
--
115 54
laa ixiAAootj lutuic nuovc aureeu mam, ieet.
L = equivalent length determined in paragraph 4, feet.
If the system is of the down-feed supply from a gravity tank, the height of water
n the tank, converted to pounds per square inch by multiplying by 0.43, replaces the
t re?^ F?**11 pressure, and the term 0.43 H in Equation 1 is added instead of sub tracted in calculating the term p. In this case, H will be the vertical distance of the fixture below the bottom of the tank.
< From the expected rate.of flow, determined as in paragraph 3, and the value of V, calculated as in paragraph 6, choose the sizes of pipe from Figs. 3, 4 or 5.
Example ; Assume a minimum street main pressure of 55 psig; a height of topmost
xiure above street main of 50 ft; a developed pipe length from water main to highest
cl *e ^ ^ a ^*al lac* on the system of 50 fixture units; and that the water osets are flush-valve operated. Find the required size of supply main.
Tahl
Fig. 2 the estimated peak demand is found to be 51 gpm. From
Fci 6 f ^18 ev*dent that several sizes of meters would adequately measure this flow.
thrr>a k4* f^putetion choose the IK in: meter. From Fig. 6 the pressure drop ugn a IK in. disc-type meter for a flow of 51 gpm is found to be 6.5 psi.,
r* the pressure drop available for overcoming friction in pipes and fittings is 30 - 05 + 50 x 0.43 + 6.5) 12 psi.
of th lfi!s.point it is necessary to make some estimate of the equivalent pipe length
ex "Stings on the direct line from the street main to the highest fixture. The
pj equivalent length of the various fittings cannot now be determined since the
know1*68 * building main, riser, and branch leading to the highest fixture are not
select" a8
*ut a ^rst aPProximatin is necessary in order to make a tentative
fiiinin?k
s*zes- ^ the computed pipe sizes differ from those used in defcer-
fig the equivalent length of pipe fittings, a recalculation will be necessary, using