Air Conditioning
W. L. Fleisher & Co., Inc.
31 Union Square West
New York, N. Y.
*
Chicago, 111., 530 South Clinton St.
Philadelphia, Pa., 135 North 3rd St.
Consulting and Contracting Industrial Engineers for Air Conditioning and Drying
Slurlevaril --FTeisher
AIR CONDITIONING SYSTEMS
Slurtcvanl-Fleisher Equipment
The Sturtevant-Fleisher air conditioning systems are designed to Overcome the .
handicaps imposed on industry by variations in, or adverse climactic, weather or atmos
pheric conditions. They insure to the manufacturer that effect on materials and pro
cesses which can only be produced by ideal air characteristics, making his plant entirely
independent of the seasons or the weather.
^
Whether the cure for such difficulties involves the creation of high or low tempera ture, and high or low humidities in any combination, dependable apparatus, a careful design and a broad basis of experience, is offered by the combined Sturtevant and . Fleisher organizations.
All apparatus used is manufactured by the B. F. Sturtevant Co., the oldest, largest and one of the most experienced fan and air apparatus builders in this country. The highest type of service, both from the engineering and contracting viewpoints, is assured by W. L. Fleisher & Co., Inc.
Catalogs are ready for distribution, giving both the general details of the apparatus used, and also, for each specific industry, giving the particular advantages of such in
stallations to that industry.
Sales Engineers are located in practically every principal city. Upon request they ,
will call on manufacturers for consideration of their problems and to collect data for
recommendations, estimates, and guarantees of results.
1
182
Air Washers
The Cooling Tower Co., Inc.
17 John Street, New York
AIR WASHERS COOLING TOWERS SPRAY NOZZLE SYSTEMS
Representatives in Principal Cities
The air washers tabulated below embody all the good features of the best modern practice and have been designed to meet the specifications of Architects and Engineers for public buildings. Some exclusive features are the special clog-proof' nozzles, the duplex spray heads with scale arrester, and automatic hu midity control devices.
For information on washers for generators, ask for Bulletin K.
AIR WASHERS FOR PUBLIC BUILDINGS
Length T O'. Air Vei. gross area 480' per min. Resistance 0.2' water gage.
Washer Num
ber
Total Width
B- 5
B- 7 B- 9 B-l 1
3'-9" y-9* y-9* y-9*
C- 7
C- 9 C-ll
C-13 C-15
5'-6' 5'-6'
5'-6' 5'-6' 5'-6'
D- 9 D-11 D-13
D-15 D-17 D-19
7'-3' 7'-3' 7'-3' 7'-3' 7'-3'
7'-3'
E- 9
E-l 1 E-13
E-l 5 E-l 7
E-19
vjs
9'-0' vw 9'-' 9'-0' 9'-O'
F--11 F-13
F--15
F-17 F-19
IO'-9' 1(Y-9* W-9* W-9* 10'-9*
G-l 1 G-13 G-l 5 G-l 7
G-19
ir-3' 12'-3,
1\?2'.-3y'
12'-3'
H-13 H-15 H-17 H-19
!4,-0' l4'-0'
l4'-0' M'-O*
1-15 1 y-9* I--17 \y-9* I--19 iy-9*
J-15
H/
J-19
l7'-6' !7'-6' !7'-6'
K-15 K-17 K-19
W-l* l9'-3'
w.y
L-17 2P-0' L-19 2l'-0'
Total Height
Ca pacity
Cubic Feet
per Min.
4'-0'A' S'-ffA' 6'-0Vi` r-O'A'
y-o'h' O'-0'A' T-O'/S
O9`-'-oO'A'/'f
b'-O'/f'
r-o'A'
O'-O'/f' 9,-0V2" 10,-0Vz" W-O'A'
6'-0VY r-O'A' O'-O'/S 9'JF/z* lO'-O'/i' 11'-0>/2'
4,500 6,000 8,000 10,000
9,200 12,000 15,000 17,200 20,000
15,800 20,000 22,800 26,400 30,000 33,400
20,000 24,200 28,600 33,000 37,500 42,000
r-O'A" 8'-O'A' r-O'A' lO'-OVz' H'-0/2'
30,000
35,000 40,000
45,000 50,200
r-O'A' 8'-0*/,'
m/z"
WJl'/S 1 r-0'A'
35,000 40,000 46,200 52,400 60,000
O'-O'/z'
lO'-O'/z' ivws
46,000 53,000
60,000
67,000
9'-QVz0- 60,000 \QfJ/S 67,200 IV-O'/S 75,200
9'-0>/2'
ww/s It'-0<A'
66,000 75,000 83,600
9'-Q'/S
WJS'/S If-O'A'
72,600 82,200 92,000
JO'-OVi' 1 90,000 1 1 \`4f/S j 100.200 1
CIRCULATING PUMP
Size
Ca pacity G. P. M.
Brake H. P.
R. P. M.
Motor H. P.
t'/z "
ww
I'A'
1\w'/i
w 1* 2'
22 30 40 48
46 60 73 86 100
LI 1,730 1.5 1,730
1.8 1,730 2.1 : .1,730 ;
2
2
2 3
2.0 1,730 3
2.5 1,730 3 3.0 1,720 5 2.7 1,720 5
3.2 1,720 5
IVY 2' 2' 2'
2" 2' I'A' 2'A' if/s
2'A'
2'A" 2<A' 2'A` 3' 3'
W' 3y'
3'
3' 3' y 4'
y 4' 4'
4' 4' 4'
4T 4' 4'
4' 4'
79
97 114
132 150
167
3.2
3.1 3.6 4.1 3.8 4.2
99 3.2 121 3.8
143 3.7
165 4.2 187 4.7 209 5.3
145 3.7 172 4.3 198 5.0 224 5.6
251 6.1
170 4.3 200 5.0
231 5.6 262 6.3
292 7.1
229 5.5 264 6.4 299 7.2
334 7.0
298 . 7.2 336 7.0 376 7.9
330 6.9
374 7.8 418 8.8
3o3 7.2 411 8.6 460 9.7
448 9.4 501 10.5
1,720
V.720 1,720
'1,720
1,720 1,720
5
5 5
5
5 5
1,720 1,720 1,720
1,720 1,720 1,750
5 5 5 5. 5
rA
1,720 1,720 1,750 1,750
1,750
5
5 r/z
li
1,720 1,750 1,750 1,750 1,750
5 7'/z
i
1,750
1,750 1,740 1,750
V/z V/z 10
2'A
1,740 1,750 1,740
10 7'A 10
1,750
1,740 1,740
V/z 10 40
1,740 1 10 l,740r 10 1,760 15
i1,760 15
1,760 IS
PIPE CONNECTIONS
Pump
Dis charge
Pump Suc tion
Fresh Water
Drain
\1vV2s0
2' 2'
Vw/z' T2*
vVsS
2' 2'
VS Y
VS 2'
w 2" 2* 2'
VvSs
2* V
2` 2' vs 2"
2' 2".
iv'/AS"
vvss
2* 2'
2" 2' VS 2r
2r
2'/S 2VS 2x/z 3'
V/S V/S V/S 3' 3'
Vvvss," vvss
2* 2' 2'
2' 2'
2*
V/S
w y
2VS 2 VS 3' 3'
vvvsss vs
2' 2' 2' 2'
y y
y y
vvss
2' 2'
V/S 3' 3' y 3' y
3' 4' 3' 4'
y y
y 3'
y 4'
4' 4'
4' 4'
VS
vvss vvss
2' 2" 22'
2'
r
i'.
r t-
r V 2'A'
y 4' 4' 4' 4' 4'
4' 4'
\* r
r
4' 4* 4' 4'
4' 5'
1' 1'
r
4' 4'
4' 5' 4' 5'
\* 2/S
r -2VS i' 2'A"
4* 5' 1 VS 3' 4' 5' tvs 3' 5' 5' tvs y
4' 5'
ly
1 5'
t \
v/s t'/S
|1
y
3"
183