Document 7O16y5ye9kR5VezxEoNLO2Qk8
I
HEATING VENTILATING AIR CONDITIONING CUIDE 1944
CHAPTER 16. HOT WATER HEATINC SYSTEMS AND PIPINC
atmosphere. The minimum contents of an open tank should be 0.06 of the volume of the water in the system including that in the boiler, heat transmitters, pipes, etc. This capacity is 50 per cent in excess of the actual increase in volume of water due to increase in temperature from 40 F to 200 F. The tank should be located at least 3 ft above the highest radiator. Provision must be made to prevent freezing of the water in the tank as well as in the pipe leading to the tank.
In a thermally circulating hot water heating system, the pipe to the open expansion tank should be connected to the supply riser from the boiler, so that the air liberated from the water in the boiler will enter the expansion tank.
In a forced circulating hot water heating system, the pipe to the open expansion tank should be connected on the suction side of the circulating pump, so that the pressure head on the suction side of the pump will remain practically constant.
A closed expansion tank is sealed against free venting to the atmos phere. The tank may be above the highest radiator or heat transmitter, or may be below the lowest one. The minimum contents of a closed expansion tank must be such that the expansion of the water due to increase in temperature will be cushioned against a reservoir of compressed air above the water level in the expansion tank. The tank must providespace not only for the change in water volume, but also for variations in air volume within the tank due to changes in air pressure. If the closed expansion tank is below the heat transmitters, the tank should be larger than if it is above-them, and the higher the building, under such circum stances, the larger should be the air capacity within the tank in excess of that required merely for increase in water volume due to temperature increase..
The size of a basement-located closed expansion tank should be at least equal to the following:
One story buildings: x = 0.10 V
Two story buildings: *.= 0:-13-K_
Three story buildings: * = 0.17 V
Six story buildings: x = 0.28 V
where
X = expansion tank size in gallons.
V = water volume in heating system in gallons.
Table 4.
Friction Heads (in Milinches) of Central Circular Diaphragm Orifices in Unions
(iOne.mUinch equals 0.001 in.)
Dukbteb
Veloott or Waxes in Pxfb in Feet pea Minute
or
Orifices
20 j 30 j 40 | 50 j 60 j 90
(Inches)
10
IS
%-in. Pipe
120 | 180
0 0TM 0" 35
0.55
0 3s 0 0 4S
0^65
1300 650 330 170
2900 1450
740
380 185
5000 2500 1300
660 330
155 75
11,300
5700 2900 1500
740 350 170
20,800 32,000 10,400 16,000
5200 8000 2600 4000 1300 2000
620 970
300 480
45,000 23,000 57,000 12,000 26,000
6800 13,000 2900 6500
1400 3200
700 1600
,1)00 24,000 53,(XX) 12,000 27,000
5700 13,000
2800 6400
900 2000 3500 460 1000 1800 77ft 570 1000 160 330 580
190 330 200
120
1-in. Pipe
7800 4000
2300 1400 '750 440 260
14,000 . 7200
4100 2300 1300
800 460
22,000 12,000
6400 3700 2200 1300
720
32,000 17,000
9300 5400 3000 1800
1100
37,000 21,000 12,000
7000
4200 2400
65,IXX) 37,000 22,000 50,000 13,000 28,000
7400 17,000 4300 10,000
0.45 0.50 n ss n
0 6* 0.70 0.75
1000 660 430 TAft
190
2250 4000 1450 . 2600 950 1700 630 1100
420 750 285 510
190 330
1/4-in. Pipe
. 8900 5800 3800
2500 1700
1150 750
16,000 10,400
6800 4400
3000 2000
1300
25,000 16,400 10,500
6900 4700 3100
2100
36.000 23.000
15.000 10,000
6700 4500 3000
53.000 34.000 22,000
15,000 10,000
6700
60,000
40,000 27,000 60,000 18,000 40,000 12,000 26,000
0.55 ft.rift ft.ris
ft 7ft ft 75 nan
0.85
850 1900 3300 600 1300 2300 400 850 1500 260 600 1100 180 400 760
300 540 200 380
1 Vrin, Pipe
7400 5400 3600
2600 1800 1200 860
13,000
8600 7200 4400 3000 2200 1600
21,000 16,800 10,400
7000 5000
3200 2300
30.000 21.000
14,000 10,000
7000 5000 3000
50,000 30,000
21,000 14,000 10,200
7800
53,000
39,000
28,000 19,000 45,000 13,000 30,000
This condition favors, especially in tall buildings, the placing of the closed expansion tank above the highest heat transmitter.
Any closed expansion tank located above the heat transmitters of a hot water heating system should be connected by a direct pipe with the flow main leaving the boiler, iri order to enable the air to pass easily to the expansion tank. In a closed hot water heating system the water under pressure tends to absorb air at a rate increasing with pressure increase and decreasing with temperature increase.
0.70 0.80 0.90
1.00 1.10
1.20 1.30
890 1850 3500 470 975 1800 255 560 1000 160 340 610
214 375 195
S-in. Pipe
7400 3900 2200 1320
850 460 275
14,000 7400
4200 2520 1600
950 525
22,300 11,700
6500 4000 2500 1360
980
33,000 17,000
9500 5800 3700 1910 1375
37,000 20.500
12.500 7900 4200 3100
38.000 23.000 49.000 14.000 30.000
8100 16,800 4400 8850
: Means must be provided to adjust and to observe the proportion of air
within any closed expansion tank. This involves the provision of an air inlet valve, a water gage and a relief valve. A source of supply of com
dpuracctetidcablylytthreueTeinxathseEtnegsitnseteoridnegteErxmpienreimtneentloSsstaestio0n1 ,naenadu amlsouuinultchsemtes7t4s-uto*..determine the losses of h--ead
f
pressed air for renewing the air cushion is highly desirable, especially in
in orifices in 4-in., 6-in., and 12-in. pipe, conducted by the Engineering Experiment Station of the University of Illinois, (Bulletin.10Q, Table 6, p. 38. Davis and Jordan).
310 311