Document 2JXrvbE5wyLoXJ098NNb198Xp
7 v,
American-Standard
KEWANEE BOILER DIVISION
28728
w\
Lc-pyriyhl 1953. Amei
i St a i
28729
Today, steam or hot water for a plant or building of moderate size should be supplied by a unit that is designed to meet today's exacting requirements. Labor costs are high, so installation of the unit should be quick and uncomplicated. Once installed, the unit should operate automatically, with controls that keep performance smooth, safe and efficient without close adjustments and constant attention by skilled personnel. Con struction costs are high, so a stack should not be required--and the boiler room should consume as little floor space as possible, under a standard 8-foot ceiling. Fuel prices are high, so every usable Btu should be transferred from the fuel to the water.
With the Scottie Jr. series package units, Kewanee Boiler Division has perfected today's better way to fire oil and gas for today's better plants and buildings. These compact Kewanee packages are ready to serve wherever products are manufactured, materials are processed or people are working, shopping, learning or living.
28730
Kewanee's two-pass system takes hot gases through furnace (A) and back through all fire tubes (B) to smoke
outlet. (Low pressure unit features water back top with water above rear combustion chamber.)
Water surrounds furnace and fire tubes. All fire tubes are utilized equally--there are no baffles to burn out, no unequal temperatures to distort tube sheet. Large furnace and flue area keeps furnace pressures low.
28731
Kewanee Scottie Jr. Package Units are fully assembled at the factory. Burner and all con trols are in place and wired, Steel skid is attached ... all refractory is installed. When five simple service connections are made, the unit is ready to begin producing hot water or steam at the touch of a switch.
Both burner and boiler are engineered to per form as an integral unit--smoothly; quietly, efficiently. A fully-enclosed panel houses the automatic controls. Burner shuts down in stantly in the event of low water, flame failure, excessive steam pressure or water temperature.
Only periodic maintenance is required. Ratings for the units are computed conserva tively. Certified ratings are based on approx imately 5.5 square feet of heating surface per boiler horsepower.
Combustion air is provided by forced draft. A high speed (3450 rpm) ball-bearing motor drives the blower. Because Kewanee's two-pass system provides a large flue area, excessive blower speed and furnace pressure is not required. A simple vent carries off com bustion fumes--no stack is-needed.
Choose your burner; to meet local condi tions. The Kewanee oil burner is a twin nozzle, high pressure typeapproved.'for No. 1 or No. 2 oil. The Kewanee gas burner is equipped for either natural gas or LP gas, according to your specification. The combination gas-oil burners are particularly applicable to installations in
localities where gas is the main fuel but standby oil firing is necessary. Fast fuel changeover can be accomplished by the flick of a switch--or even by automatic controls,
The swirling flame created by forced-draft firing sweeps over the inside surface of the furnace tube. Initial heat transfer at this point is high. On the return pass through the 3" fire tubes, spinner blades in the tubes spiral the hot gases against tube surface. This action unlocks remaining Btu's for transfer to the water. Certified efficiency of the Kewanee unit is 80%--actual efficiency, under normal operating conditions, may be even higher.
Fire tubes in Kewanee units follow a vertical and horizontal layout as closely as possible. This permits more space between the main body of tubes for free, rapid circulation of water and unobstructed rise of steam bubbles. A low water line provides a large steam disengaging area, where these freely rising bubbles detach themselves without the extreme turbulance that can cause foaming and priming. Lower water line also increases the steam storage area at the top of the boiler, a further assurance of dry steam in ample amounts.
Kewanee Package Units will meet local and state requirements. Boiler construction meets or exceeds provisions of the-A.S.M.E.code. Burner and combustion controls are approved by Underwriters' Laboratories, Inc.
high temperature water above 250
28732
A glance at a Kewanee Scottie Jr. Package Unit reveals cleanness of design . . . quality of details, both in ma terials and workmanship. Welds are smooth--carefully executed. Swing open the cast iron flue doors and you will see that the ends of the fire tubes have been set into the tube sheet with a roller expander and expertly beaded. Burner controls bear nationally recognized names . . . boiler trim is of highest quality.
28733
Rapid, simple access for inspection and maintenance is an important advantage of Kewanee units. Sturdy flue doors and frames are cast iron, produced in the Kewanee Boiler Division foundry and machined to a precision fit. The doors are insulated to retain heat and gasketed to effectively prevent leakage of gases. Quick-opening locking clamps free the doors to swing out on hinges without interfering with firing equipment.
Access is also provided to the rear combus tion chamber as well as to all water surfaces. Adequate and ample handholes provide for in spection and cleaning of the tubes in all units of the Scottie Jr. series, with manholes in the larger sizes, 59 hp and above.
Boiler heads and furnaces in high pressure
units are of firebox quality steel. Ail other steel plate is of flange quality steel, in thicknesses that meet or exceed A.S.M.E. boiler code re quirements. On high pressure units, welds sub jected to tension are X-rayed and entire boiler is heated in a furnace to 1200F., to stressrelieve welds and formed sections.
A gas-tight welded steel smokebox is stand ard equipment on Kewanee units, fitted with a quadrant lock damper. On the rear combustion chamber a pyrex observation port allows ob servance of the flame.
When specified, Kewanee units are fire-tested at the factory. Heavily-insulated steel jackets are also available, at the option of the owner, as well as coils in low pressure units to provide an ample, steady supply of domestic hot water.
28734
The 68-office network of Kewanee men stretches through out every state for prompt attention to service calls. From your first contact with the Kewanee organization through out the long life of your Kewanee unit, there is always a Kewanee man ready to answer questions or provide skilled on-the-spot assistance with problems of maintenance or repair. Just pick up your telephone!
DIMENSIONS
unit number high pressure' low pressure
HM-18-W LM-18-W
HM-29-W LM-29-W
HM-39-W LM-39-W
HM-45-W LM-45-W
HM-59-W LM-59-W
HM-65-W LM-^65*W
HM-78-W HM-92-W LM-78-W . LM-92-W
BOILER HORSEPOWER
..18 29 39 45 59 65 78 92
STEAM PER HOUR-2120 F. lb
BTU PER HOUR
1000's
STEAM
sq ft
WATER
sq ft
624 606 2520 4040
996 967 4030 6450
1356 1316 5480 8770
1577 1530 6370 10200
2031 1971 6210 13140
2258 2191 9130 14610
~
2705 2625 10940 ' 17500
3185 3091 12880 20610
A--length overall**
8-9 11-3 11-6 12-7
13-3
.14-2 '
13-216
B--width overall
4-6 4-6
5-0 5-0
5-6 5-6 6-1
C--steam supply height
4-1116
4-11V6
5-516
5-516
6-0
6-0 '
7-0
D--smoke outlet height
5-6
5-6
5-11 <6
5-1116
,6-516
6-516
7-116
`certified output '^Includes oil burner. Gas burner extends additional 17 inches..
-
Above dimensions and drawings are for high pressure unit. Figures are also approximately correct for low pressure unit,..For complete specifications, see catalog bulletins 3314-3, 3315-3, 3316-3.
Form No. 1131 3-58 LPC
L/We RiCAN-^tandard
KEWANEE BOILER DIVISION 101 FRANKLIN ST., KEWANEE, ILLINOIS
28735
litho in u.s.a.