Document 15OJZ2J5paLnj6LB0OJ7J8opj
.1. ~1k
1
union carsio .c.9i'o.;;.r:nN
CHEMICALS AND PLAS"I* o OPERATIONS DIVISION
ENGJNEERINC f/EP^R TMENT
PLAINTIFFS EXHIBIT \
II 0C-P-131
PROJECT C--JNITION: INSTRUMENTATION DESIGN BASIS
ETHYLENE OXIDE SEADRIFT, TEXAS
(0 *?/<- V-*
APRIL. 2T. 1967
TECHNICAL. CENTER SOUTH CHARLESTON, WEST VIRGINIA
016568
UNION carbide; corporation CHEMICALS AND PLASTICS OPERATIONS DIVISION
ONGINEERING Dr.r-ARTiv'Ci'iT
PROJECT DEFINITION INSTRUMENTATION DESIGN BASIS
ETHYLENE OXIDE SEADRIFT, TEXAS
APRIL 21 , 1967
TECHNICAL CENTER SOUTH CHARLESTON, WEST VIRGINIA
016569
FFOJE.T lEFTELTIOn nSTHOMESBftllCK 27331(21 BASIS
. EEHTLEIE OXHC PIAITT SK7>RIFT, TEXAS
TABIF 1? COTCEBHgS
Gene.'*! Description ci Control System? . Sigineerli-^ ut.-ign Baxaaeters ELectrieal Instrument Power Supply System Instrument Air System Operator Communications System Electronic Instrumentation Specifications Pneumatic Instrumentation Specifications Instrument Console Specifications Control Valve Specifications Valve Positioner Specifications Temperature Element Specifications Plow Element Specifications Miscellaneous Instruments Wiring and Tubing Supports Wiring Requirements Instrument Piping and Tubing Instrument Drawings Instrument Electrical Connection Boxes _ Analyzer Specifications Instrument Safety Criteria Instrument Plow Plan Symbols
section
l.C'v> 2.000 3*>- SO 4.COO 5*000 6.000 7.000 8.000 9*000 10.000 11.000 12.000 13.0GC 14.000 15.000 16.000 17.000 18.000 19.000 20.000 21.000
016570
APPENDIX
k B C D E F
a
E I J K L
iROjKr 'iffmmos IBSIBUME.'TJATICN DESIGN BA.J\r
ETHYLETir. GXjDE PIANT SEADR J'.e, TEXAS
TABLE C APPENDICES
Functional Programming :*ne,_ifications Electronic Instrument Specifications Instrument Ifcnel Specifications Typical Instrument Specifications Sheet Process Analyzer Specifications Instrument Safety Criteria * Instrument Flow Plan Symbols Instrument Cable Specifications Cknitted Wire Numbering Method Wire Marking Method Instrument Electrical Connection Boxes
01657^
L.000
1.100 1.200
1.300 l.lKJC 1 -5-'0
PfvW 1 /.prll 21, 1?6
GEErVL DESCRIPTION 0/ CONTROL SYS'SS
TV-S unit will be ..wugelled and uui>e-. 1 >ed from a central cet-sr. All of tbe Central Control Kochs instruments will be o' tLt electronic t-'-pe. A small number of non-critical loops tun,, requi' .. only n-'.nor operator c.ttfcf,':ion will be locally ' vmtcd pix-'ivcic instrumentation.
A digit.1 process contri.' .r'mputer w. 11 function as an integral part of t`ie process control system. Vben the computer Is unavailable, the unit shall be safely operib from the central control center.
1.210 A computer system consisting of a "central" computer with facilities for receiving inforation from and transmitting data to the "block" (unit process control) computer will be provided. The block computer will perform functions per taining to data acquisition, unit control (set-point control and some direct digital control) and communication only. $je central computer will perform all major calculations such as equipment regulation, optimization and management information functions for the block computer.
1.220
The block computer will be located in the central control center. The central computer will be located in another area of the plant and will be shared by block computers for other process units.
1.230
When the block-central computer system is "on-line", all new program development will be accomplished on the central computer through the use of an "on-line" compiler or assembler. The central computer shall have the ability to compile and assemble programs for the block computers.
A stable and reliable source of a.empower will be provided for this unit and will permit all critical process variables to remain active even though the main source of unit power is interrupted. See Section 3*000.
All control systems shall be designed for fail-safe shutdown operation,
both on power failure, instrument air failure, and combinations of both.
Most electronic Instruments will be manufactured by the Foz'boro Company, xne majority of the control wives will be purchased from Famine1-Dahl or approved equal. All electro-pneumatic valve positionerr shall be manufactured by Mason Neilo-n. See Section 9.000 and Section ID.000 for details on control vi.lves and valve positioners.
016572
1.000 l.bOG
ftujf. 1 April *1, 1967
CEBMVL DESCRT^iOU OF OOHTROL Sl^JEMS (coni'd.)
Toe control center will be Vct.ted ox* the first floor s>f a cr rrtral operations bulli!^. Spacs to oe allocated in the contra1, center for the computer. 3he re-jaining area of the control cen ':<r will be i'-1 operat* ag area wher'.- 1 * instrument consoles i < r this ard exist ing operating units wi j1 be -Seated.
I.'IO
The cabling t_*om the 1* 'id to the instrument Connies and betveen tu -anscles and computer shall be rouv-o. overhead in cahl- wry?.
1.620
central control enter is air conditioned and heated.
The room will be classified "General Purpose" electrically.
016573
ftige 3 April 21. '967
2.000 USDEERIBS LZSICT PAP-AKETHi?
2.100
.VI important process var.Lab.' es shall be displayed in the cc -iral i^:rol center. The type display will be eicaer continuous ind-ca ters/ caaputer digital displays, console trend recorders, computer trend recorders, or type.~it*r cutput. PH variables i except con troller outputs) that are oou7.eited to 10-50 ma sigrj'-s 'Til be capable of trend recording -he instrument consol?s.
C 110 '
Ihch instrument conscJL* vl.ll be equipped r*ti- four 'uytwopen trend recorders. In ti e event that this ncr-nal number of trend recorder points is insufficient (during -"art-up, testing, system trouble-shoot* rue, etc.), additional trend recorder points will be provided on a "dolly". This dolly will be on rollers and vhen needed would be moved to ^ sition in front of the instrument consoles.
2.120 %
The light panels at the top of each instrument console will be used for trend recorder point identification as well as the alarm function. The engraving details and point description will accomplish the trend recorder point identification. Refer to appendix "D" for instrument equip ment panel arrangement.
2.200
The computer system will be used in the following manner. Appendix "A", "Functional Programming Specifications", describes the proce dures used within the computer system to accomplish these functions.
2.210
The computer will be used for all permanent logs in addition to flow integration and compensation. All flows will be calculated in units of pounds per hour. Ho arrangements to be made for recording any flows and planimetering of these flows as the computer will be used for this function.
2.211
The majority of -all alarm scans will be accomplished in the computer system. The computer system will be utilized for optimization work, equipment regulation, and management information functions.
2.212
Thermocouples that are not the primary device in analog control loops rhall be connected directly to the computer system for transformation into engirc-rirs oiii^o.
2.213
All c^namatograph outputs will be thrc"'<zh the computer system. Irctl recording shall be provided for mainten ance only.
, 2.220
Critical variables shall have analog ala.m txd annunciator systems independentt of computer operation. The process engi neers will denote on the instrument performance data sheets what loops are to bo provided with analog Claras. All other alarms will be accomplished by the compu ;er system.
016574
2-000 ?.3Cu
2.1*00 2.50
Pag* 4 Ap.-*1 21. 1967
EWGUHLJlMg TFoiar PARAMETERS (coat'd.)
A3I conbcxe'Counted control equipme.1 shall he electronic or electrical.
?. "'10
Ail field-mounted ,,`ansiri4 te~s that transmit to the ceutifj control center sha.- he jecvi'nic. lhe vast majority of ill field transmitters shs-.1 0^ the con-indicating type. Vibn a Jocci indication of a pr-ciss variable is required, an o'.-tput gnuge shall be Installed at tot transmitter.
2.311
2.312
Locally-mounted control loops may be employed for those loops that are relatively non-crltical and that require infrequent operator attention. These loops may be either pneumatic or electronic, as dictated by minimum Installed cost or as dictated by the process. Generally, these locally mounted loops shall be pneumatic.
A locally mounted pressure switch will be utilized whenever the instrument system requires an alarm indication in the control room.-
2.313
All field-mounted switches such as pressure switches, flow switches, level switches, etc., that are used to transmit on-off signals to either the computer or the instrument consoles shall be dry contacts - i.e., the power for these signals shall be a d.c. voltage from either the computer or the instrument consoles.
2.31^
All field-mounted switches shall be connected into the loop so that under normal conditions the contacts are closed. Therefore, the contacts will open on an abnormal condition.
2.320
Whenever operating requirements dictate, remote start and/or stop operation of pumps will be accomplished by installing pushbuttons on the instrument consoles. Fjmp running lights shall be Installed on the instrument console when required.
The necessary equipment will be installed to provide an oil-free,
filtered, reasonably dried, and egulated instrument
-- IT1/ vid
distribution system.
All controllers, regulators, relays, and/or devices necessary for safe control of the unit, including a?.l emergency shutdown systems, shall be powered from the same "primary a..~. power source" as the consoles.
016575
2.000 VNGI'TEFRING DESIGN PARAMETERS (cort'J.)
Paf 5 Auril 21, 1967
2.510
Whenever practical, the <*aergnr.jy shutdown systems sr.aj.3 be
designed tj permit checking their action without shutting
^down th s unit or equj vment. This checking may l-vt ntcsertrily
be accomplished by *.ne opevator without assistance, 'his
checking appliCi. .oecifictJly to the actuating device. By-
p?ss valves, venw and/or
valves, etc., shall be ia-*alled
to permit calibration checking of the actuating device
whenever practical.
2.600
All instrument scales and/or charts shall be as per the individual instrument specifications. However, *r* general, the scales shall be:
1) Liquid level: 2) Interface level: f) Flow:
4) Pressure: 5) Temperature: 6) All others:
0-10056 uniform 0-100% uniform
0-/0
In actual engineering units In actual engineering units In actual engineering units
a-
An exception to the above list regards trend recorders. As defined under the instrument specifications, all trend recorders shall have 0-100 uniform charts and scales.
2.700 Engineering units.for instrument scales, charts, computer readout, etc., shall be as follows:
1) Pressure:
Pounds per square inch gauge
2) Vacuum:
Inches of mercury
3) Absolute pressure:Millimeters of mercury or pounds per
square inch absolute if above atmospheric
4) Temperature:
Degrees centigrade
2.710
All indicating controllers shall be as per the individual instrument specifications. However, in general, the controllers will be specified with the following control modes and con troller range adjustments:
1) Modes
a) Tempera`.ure: b) All ethers:
Proportional plus r^net plus
derivative Proportional plus reset
2) Controller Range Adjustment Limits
016576
a) Flow - Proportional band:
Reset time
:
5-30Q1 0.01-3.3 minutes
b) All others -
Kcoortionaj. band Reset time Derivative time
5-300* 0.01-3.0 minutes 0.1-30 minutes
2.000 vNC-rmiNG DESIGN PARAMETERS (Con-'ij
Pn^e 6
April .'l, 1967
2.800 Fleeirical and electronic control equipment shall meet the electrical jodc established for the various area? of the plant, except:
1) Analyzers local/-J in 1 building within the prc.ee - uni u shall be f.v v s&ed vi.-h easketed cases and air ;.urg?d. This does no!: apply to- ,,L * sample system component ;hat are constructed ft** Clr.ss 1, Group D, Division I con struction.
%
2) The electronic transmitters will be furnished as a standard for Class 1, >i>.oup D, Division I construction.
2.900 All Instruments shall be accessible for maintenance in the field. Accessible is considered as one of the following:
1) Accessible from ground level; 2) Accessible from a fixed ladder; 3) Accessible from a fixed platform.
2.910
Whenever practical, all transmitting devices shall be installed in such a manner that they can be repaired and/or calibrated. This requires process shutoff valves, vent or drain taps, transmitter bypass vaive3, etc.
016577
3.000 v.100
3-200 3-3CO
Page *T April 21, 1967
-E--L-E--u--T-R---lC--A--L----IN--S--T--R--U--M---E-i-f-f--P--O--W--E-R----S-U--P--P--L-Y----S-Y--S--C--F-M-
1.'--c^.
A 3C'.bl.- and reliable source of a.c power viU be provided, Ter tV* in.tnuent control r., - .at.", incl'.uirv ^'-e computer. Biis scarce wj'1 pera.t all critical process variables cc remain active even though --hr main source 0* unit pover if interrupted. All controllers, -ill renalr wperable as will the eoavu* system, trend record'"s, cxrtieuous inr-i"i'.ors, and regulators coring a localized failure oi or'x power.
3.11A E.\*ctrical power 1:- required xl Central Control for the fc.1 lowing iter is:
- 3.111 I1TV a.c. "primary a t. power" for each instrument console at 20 amps. Tils source shall be used to power all components ir The console that are required for control, i.e., controllers, manual regulators, alarm trips, etc. A circuit breaker for this circuit shall be provided internally in each console by the console vendor. The wiring for thi3 circuit shall be
' adequate to handle 20 amps per console.
3.112
U7V a.c. "Secondary a.c. Power" for each instrument console at 5 amps. This source shall be used to power all components in the console that are not as critical, such as behind the panel illumination lights, horns, annunciator and service receptacles. Each of the consoles shall be connected to an external 5 amp circuit breaker.
3*113
208 a.c. cower at 23 amps is required for each of the two (2) Sorensen d.c. power supplies. Individual
external a.c. circuit breakers are required for the supplies. (The d.c. power supply system is described in mere detail under Section 3-300 and Appendix C, Section B).
The "Primary a.c. Power", the "Secondary a.c. Power", and the 65 volt d.c. power shall be connected to terminal strips in the instrument consoles. All other leads shall connect to the instrument consoles through the cables and cable connectors provided by the instrument console vendor.
' -3 volt d.c. power supply system i-> required for process control and shall be designed in the uaraer noted below.
3 3J0
Two (2) pieces of Sororseo Model OCR 80-30 d.c. power supplies are required and shr.ll he provided by Foxboro. Each of chese supplies shall opeiate in parallel and will be of sufficient
capacity to carry Ve total load for the unit. Xoraally, each supply will provide T./2 the load. Rated output of each supply is 30 c-^ps at 65 volts d.c.
016578
;.ooo
3-400 3*500
ELSCr^llM. INSTRUMENT *OWER SUPPLY SYS1* (cont *d )
ftge 8 April
19^7
3-3^0
"he output of the two supplies shall connect to e "d.c. rver Supply Switchover Unit" that will mom to** the outputof each power supply, fcr hath high and Ioj voltage in addition to high output turrey', and blr-j& a had supply from the line and transfe * t.v; total load to the reruin.'-:s.ruply. Ibis device to he iwvuisbed and mounted ii: cons:le hy r->ooio-
3*330
ihc power supplies shall operate i'roo 208V a.c. p?Ww- nv. 23 amps maximum current for each supply. The power suppl/es are arbitrarily assigned the deslguotiua as the 1 d.c. supply and the #2 d.c. power supply.
3-340
The #1 d.c. supply shall operate from the 208V a.c. power source called "Primary a.c. power". The #2 d.c. supply shall operate from the 208V a.c. power source called "secondary a.c* power".
An "AC Power Throwover System" shall also he required. Hie function shall he to normally power the "primary a.c. supply" from a circuit independant of local "unit power" hut automatically throwover to unit power upon failure of normal source.
A relay device shall he provided that will monitor the common outlet of the d.c. supplies and upon failure of this voltage, remove the a.c. power from the consoles. Both the "primary a.c. supply" and the "secondary a.c. supply" shall be removed from the console supply upon failure of the d.c. supply system.
016579
4.000 4.100
4.200 4.300
Atj 9 April 21, 1967
riPT: OMEtiT. AT? 1YST34
pY. L./C-^
A reliable source of instru.aen; air shall be provlded^for -He unit. Thit- supply shall be reduce* ir pressure, filtered and alated. Parallel filters and regulators to be used. Refer to UCC xn.rtrunent Piping Detail SK/1027 or Jr/l028.
4.110
A 100 pslg and a psig source of Instrument all v^ll be
provided. The 101 pslg source bhsll be taken lniai.Ia.ely downstream of the flitter** ahead of the reducing regulators.
4.120
The air supply source shall be shown on all Instrument
drawings. When I. A. supply is shown connected to an Instrument, it should be assumed to be 20 pslg. When 100 pslg supply Is required, the instalment sketch to show "100#I.A."
Most control valves will require 20 psig I.A. supply. 'Hie fol
lowing items will normally require 100 psig I. A. supply: on-off
ball valves with cylinder actuators, most valves with pneumatic piston actuators such as butterfly valves, gas turbine control systems.
The method of using Instrument Air manifolds, both for 100 psig and 20 psig,shall be used similar to those shown on Instrument Piping Detail SK-701, -702, or -703.
U_l--L /-
016580
4.100
A GENERAL - continued
Connections that will he blind flanged, Including small Instrument connections.
Number of expansion joints, approximate location, and detail number in applying specification (See Fig. 22-H-14, Insulation Specification No. 22-H).
Pressure rating of flanges.
Insulation requirements far supports.
Other information necessary to supplement standard specifications.
B. UNACCEPTABLE MATERIALS
Combustible insulating materials and weather barriers, as well as Insulations containing magnesia, are unacceptable.
C. SPECIFICATIONS
High temperature insulations suitable for Ethylene Oxide service are limited to Careytemp or Kaylo 20. Where broken joint construction is required use Standard Specification 32-HFP, 32-HFPSS, 32-IFP, or 32-UTSS. Where single layer application is suitable use Standard Specification 22-H or 22-HSS. (Kaylo 20 material may be substituted for Careytemp in these Specifications.)
Outside of the Ethylene Oxide contaminated area the specifications for hot lines and steam lines are 21-H, 22-H, and 23-H and the low temperature specification is 10-L.
016581
5.000 tflTJP COMMUNICATIONS SYSTEM
.'age 10 Apr* : 21, 1967
5.100 A viied communications system frr inside/outside operator cciwainications s will be provided for ;."ii? uiut.
5.200
A v/i.-id "audio intercom" cjmnunirations system will be int`ailed for oprrvt'onal communicate betwes.- the control center and the process areas within the battery limits.
5.210
This wired "audio intercta1' communications system will consist of multiple process area t'/o-way talk points using hand sets, and one central talk point within the control center. The system will be of the page or party mode type, allowing party line communication, conference type discussions, or battery paging coverage. Outside mounted hand sets and speakers shall be installed as required.
5.220
The system will utilize one power supply and one audio power amplifier. These items will be mounted within the control center where general purpose construction is adequate.
5.230
The handset pre-amplifiers shall be of the fully transistorized plug-in card type. The power supply and the audio power amplifier shall also be of solid state design.
5.240 The speaker output power is to be adjustable by changing audio transformer taps.
5.250
The handsets are to be of the noise cancelling type with con
tinuously variable input/output manual volume control. The
hook switch on each handset is to be supplied with the necessary
contacts to mute the speaker associated with that particular
system.
-
5.251 Each handset shall be equipped with a press-to-page switch.
5.252
The control center handset shall be mounted on one of the instru ment consoles. The coiled handset cable shall be expandable to twenty feet.
016582
'j.ooo VILuTKj'IIC INSTRUMENTATION SPECIE TCATloriS
Page 11 April 21, 1jo*
6.ioo
Art Pr.boro Company has been selected as the primarv supplier lectronic
imtru-cntation. All instrument covered by the
agrees at. shall
be purchased from Poxboro.
6.200
Ar;r ir.strument not covered by tri3 agreement may be purchf.sed .torn any
>ccepta,lc vendor. Vith the poss-**.. e exception of a/mr conso.e mounted
iarirumenta, there instrument izc5->t kill be purchased J.rectly
the
supplic".
6.300
All console mounted equipment not purchased from Poxboro shall l>e sent to Poxboro for installation in the couples.
6.1*00 Magnetic flow meters, turbine flow meters, liquid level alarms, pressure switches, etc. will be purchased from approved vendors. Fbxboro will not be Involved, unless they are the successful vendor, on these items except in regards to associated panel equipment.
6.500
Appendix B contains the specifications for the Poxboro electronic instruments.
016583
P.ge 12 A.'il 21, 196?
'.000 PFHHEEUUMMAAnnCC I5IWSSTTRBUUMMEEMHTT SSPPEECCIFIFICICAA-T-Tiri-ra-ai,i,
7.130
The J'or.bc.,*o Company has been *.?l'jct as the primary supplier rf pneumatic
listrumrns. A purchase agreem-*n* has been negotiated with foraero for -(.r.euoatlc instruments.
7.200 ftaevm&tic instruments shall c >t. ate on the standard 3 to 15 pelb -ange with a 20 csig supply.
7.300
*?1 pneumatic controllers shall be p.'owided with an automatic-manua..
tri-.~ler switch. A four-position transfer switch shall normally be provided.
- 7.310 All pneumatic controllers shall be of the indicating type.
016584
3.000
QONSQTJ SI>CIFTCATI0r.5
P*fT 13 April 21, 1967
Apueafixx C contains ths specific^Ac ns +or the instrument Cwnsnle? < - Taesconsoles shall oe purchased prefabricated and pre-wired .*roo
,or'*.oro.
016585
9.000 OOBIiO*, VALVES
par- n April 71, 19>-
9.100
ths Kemel-Dahl Division of ITT >aeral Control*; Trr. has been sel^ct^d at the principal supplier of ct.RT.dard diaphragm control val' er. (UCC Pu.-chase Agreement No. 100-373fO.)
V.^10 All diaphragm control v.O shall he purcK-sed vrom IlimmelDcr.i if listed in the iwtt Agreement.
9.120
Generally, control valves will te provided with tc^xc"-chevron packing without spring loading er standard. Whenever *i application requires a lubricator nl isolating valve, an Alemlte A-U86 buttonhead fitting will be provided.
9*130 2-1/2 inch and 5-inch valves will not be used.
9*200
Any application requiring a special valve, dictated by the process, is excepted,from the pricing agreement noted above and may be purchased from any approved valve manufacturer. Hasnel-Dahl will be requested to bid on these special valves.
9.210 Approved valve manufacturers include: Fisher, Foxboro, Annin, Mason-Neilan, and Hammel-Dahl.
9*220
All butterfly-type control valves shall be of the heavy pattern design and will be purchased from Fisher-Continental, Foxboro, Mason-Neilan, ** approved equal.
9*230
All flanged steel and stainless steel valves shall have a minimum flange rating of 300 pounds up to and including 6 inch. Control valves 10 inches and above shall conform to the pipe specifications.
9*300
All diaphragm operated control valves that are operated by an electric analog signal from the control room shall be supplied with an electropneumatic valve positioner. (This type positioner requires an instrument sir supply and converts the electric analog signal to an air pressure to set on the diaphragm.)
9.310
All throttling control valves that are actuated by a locally mounted pneumatic controller will be supplied with rncuastic type valve position*:-, whenever a positioner is ve-uiriu.
9.320 ,
Several types of concrol /alves such as large butterfly valves, large single-seated vuJ'.es, etc. will be supplied with a pneumatic cylinder or piston actuator; Fisher P.O.P. or equal* For throttling service, theee valve' will be need with ft currenA-to-pEeumai'
transducer such as the Moore 77-3 converter. This converter *111 .>e mounted adjacent to ~.h: valve. These v&l'-es wiU then be supplied with a pneumatic type valve positioner.
016586
Fag* 15
*pril 21, 1967 9.**00 Contr-.l valves shall be installed in horizontal rur.s of pip* with the top
works vertical. Exceptions t.-; ohif will be considered on an individual basic. 9-4.10 The control valve rhall be installed in the same horizontal plane
as the piping run vh?n bypasses are required. 9. Ur-:.'' Control valves shall bc-JpatalleC vita sufficient deara-ce to
ismove the inner valve while *he valve is "in the line.*' 9* **31 All control valves whose inner valve diameter is equal to or
leas than l/2 inch (Cv - approximately 4.0) shall be Installed with an in-line Y type strainer upstream of the valve.
016587
Page J.6 April 21, 1967
10.000 10.100
VALVE W.rflQHjSB
ft 'owSYin/iLL t
*L. ff<
All ^l^-trc-pneumatic valve po:ision':rs shall "be ttoijon-ITe llnr/l ad1..! 801S-.
These positioners will he purci-ared 'Ton Ifoaoa Nallam and sent. tr. the
control valve vendor, Hummel-Pal-1, for mountfng'ancl piping cn toe control
valve.
Z '
10.200
Pneimatic valve positioners t r ell uitrhra^an control valves :hull. - he Fox'ix'"^ Type "C". These positioners shiii be purchased from ssroie.' -Dehl
and will be mounted and piped on the. control valves by Bhmmel-Dahi piior tw shipment.
10.2'0
Whenever a diaphragm actuator Is impractical for a control valve, a pneumatic piston actuator shall be used. The preferred piston actuator is the Fisher P.O.P. vith valve positioner when required.
1
016588
13..000 Ti'Mi'Kiwnn.r:
,Th,cxr,iCATic:.z
Fugr 1.7
Apr .' I 21, 1K>7
11.100 Then3teuupJ.es will be used for the ;r ijority of the temperature jersureme.its.
11.200
IT'D's (Resistance Temperature Defectors) shall be used on these pyi lica-
ti--is where it is require: vh&t .he *emperature be converted to \ 10-50
MA signal for use on the lnsa *uunt console. Where applicable ., R.'D's
sha1! be used for all temperatures that c-e -n>.lcg controlled,
inently
Indicated, trena recorded, or analog alarmed on the instrument console.
11.300
u.Uoo
Most, thermocouples and DTD's shall be supplied with separable sockets.
.Cfbvivms exceptions, ouch as bearing -1enpp rntur ee-will -utili-so aheathad ,
type VmiWJuju^l'Ul.
------ --
~--rr= - - --
/
All thermocouples and resistance bulbs shall be furnished with the measuring tip in contact with the thermowell tip. All DTD's shall be spring loaded
11.500
Normally,, thermowells as per Instrument Piping Detail SK-1550, will be installed in pipe elbows facing the flow. On large I.D. pipe, the thermo wells may be installed in locations other than elbows when necessary if the installation is such that the thermowell.tip is in the approximate center of the pipe.
11.600
Thermowells in pipes normally will be 12" length. Thermowells that are to
be installed in columns, tanks, reactors, etc. normally will be 13" length.
11.700 Thermocouples shall be limited to the following types;
1. Cromel-Alumel (Type K) shall be used on applications from plus 350*C to plus 1110oC.
2. Copper-Constantan (Type T) shall be used on applications from minus 150*C to plus 350*C.
11.800 Spare thermowells shall be Installed as required and a 3/^" pipe plug installed to keep foreign objects out of the well interior.
11.900 All thermocouples for services 0#C and below shall be a sheathed type thermocouple and will be installed in a standard thermowell.
016589
i?.ooo flow
spkcifixations
Pag 18 Apri\ LI,
12.100 CrlTlce astars shall bs used wher-* practical. Whure permanent pr.sr .re drop must be minimized, where -ridi, rangeability \s required, where puxnnting flow is to be measured, or other unur.al circumst&.ioea o.-ist, flow tubes, turbine meters, .:., may be used.
12.110
%
12.120
Flo- eluent installation:. 3: all conform to Vi Gas Met. acrement Committee Report No. 3* and AGA Standards for approcrn
exit piping. Exceptions vo these standards must be con sidered on an individual basis.
Welding neck, slip-on, or screwed orifice flanges comply?ig with the appropriate piping specifications shall be used. Flange taps will be used.
12.130
Orifice plates shall be installed between 300 lb. (minimum) ASA flanged unions. Orifice plates shall be made from 316 stainless steel for all steel and stainless steel metering runs. Orifice plates shall ba fabricated as per Instrument Piping Detail SK-823.
12.140
Shop fabricated orifice runs, as per Instrument Installation
Specifications SK-815 shall be provided by an acceptable pipe
or orifice fabricating supplier. Nipples used on orifice
run connections shall be schedule 60
stainless steel
except for steam orifice measurements. All steam orifice
runs shall, be as per the Instrument Piping Detail Sketch for
steam orifice runs.
12.200 Volumetric displacement flow meters may be used for rate of flow or flow totalization where process requirements dictate their use. When used, no packing glands shall be permitted. The measuring element shall be magnetically coupled,.to the register. The output signal from these meters shall be electronic and compatible with other electronic instrumentation.
12.210
Rotameter indicators and/or transmitters used for pipeline flow metering shall be of all metal construction. Where rotameters are required, all metal construction rotameters shall be used for any hazardous fluid, high pressure, temperature or o,ner i.vro-.sul process conditions.
12.220 *
Magnetic flow meters m*y b* ussd for flow meaturem^n*. wnere process requirements dictate their use. However, thf.se flow meters shall not be uaei on streams whose average conductivity is less than one hundred micro MHO's. They shatl not be used
in process lines that a_*e steam or chemically claaned as a normal operating routine.
12.300 Liquid seals are required downst."&m of all liquid criVce runs. All
liquid orifice runs shall be either ir the horizontal oxcna vertical run with the flow "up".
016590
12.000 FjOV ELEMENT SPECIFICATIONS 'conn'd.)
Page . 9 April 2.\, 1967
IS:.310
The mounting of flow transmitters shall iollow good engineering practice. It is prefoned to close cf'uple the trsnrnr.tte.' to the process taps. Elevati _ is important and sh'xlx follow good engineering practice, : .a flow transmitter ,/iasuring liquid <iuv ?su',uld be mounted b.liv the process tx-i. , with stlf-vending leads into the process tap:*.
12.320 '
All orifice runs shall be installed with the flange Untation as per the appropriate instrument c'<etch. Normally, orfice taps will be as per SK-800, Figure x, with the shutoff valves and nipples straight into the process taps. Elbows shou*^ not be installed ahead of the -hutoff valves to facilitate cleaning or rodding the taps.
12-400
Where process conditions preclude the use of orifice metering runs (such as low permanent head loss), flow tubes with external piezometer rings for both taps shall be used. Manufacturer to be Foster or approved equal. Use of flow tubes shall be kept to a minimum.
12.500 Turbine meters shall be installed with a minimum of 15 diameters of straight pipe upstream run and 4 pipe diameters minimum downstream run.
12.510 A suitable strainer shall be installed upstream of all turbine meters in accordance with the following list:
1. 1/2" meter
2. 3/4", 1" meter 3. 1-1/2" and
larger
U.S. Sieve No. 120 (120 mesh/lin. inch) U.S. Sieve No. 45 (44-4 mesh/lin. inch)
U.S. Sieve No. 18 (17.1 mesh/lin. inch)
12.520 Upstream piping of magnetic_flow meters is not critical in regard to straight run.
016591
Page 20
Aixc:\ 21, 1967
l^.OOO MISCELL/1 '^CUS IWSTHl'MZNT ITEMS *
13 100 Gelf-ontairiod pressure reguluxurs ? '*11 "be installed in the fallowing mransr.
I3.U.O Self-regulating d-s/ices shall "be installed without bj-pas;-; valves and in aectriunc'e with Instrument Piping Detail 1016 or SK-1017.
'3.120
Pressure regulators on low prcC'ure make-up or vent service for tanks or other equipment shall be installed above the process connection with self draining leads to the vessel. Any exception to this standard must be considered on an Individual basis.
13.130
A l/2 inch tap with shutoff valve shall be installed near each regulator to facilitate control point adjustment with test gauges. To reduce the possibilities of incorrect installations, the piping drawings and/or flow sheets should clearly show that this tap is for a pressure gauge or test gauge and is not to be connected to the regulator housing. Regulators that require a separate process tap for operation should have a separate process tap and shutoff valve.
13.200 Radiation gauges shall be used where the process measurement dictates.
13.210
The purchase, receiving, installation, and checking of any radiation gauge shall be in strict accordance with procedures developed by UCC and shall meet all requirements of the appropriate federal and/or state agencies.
13.220 The Seadrift Plant Radiation Control Officer shall be involved as required in the purchase, receiving, and installation of these gauges.
13.300 Armored type rotameters shall be used"in preference to glass tube rotameters. Glass tube rotameters shall be used only where it is impractical to use the armored type such as for some purge applications.
13.^00 Pressure Gauges
" Pressure gauges should be installed on the following: Reaction, die Lille.-;.ion, conversion, or storage equipment that ii subject Lo -tir/ pressure other than atmospheric, pump discharge li; :-s, vacuum *--? suction and discharge linss; between stages of recipi.oc^u.Ltg compressors; steam inlet and exhaust lines to steam engines tad turbines; downstream of control!td valves controlling the flew of
steam; upstream and downstream of backpressure regulator or pressure reducing regulators; inlet and outlet lines of filters or la. ger water strainers; process vent headers, utility headers in buildings and structures.
016592
P< r.e il Aprl'1 cl, 1967
13.000 MISO^LIaHEOIS INSTRUMENT ITEMS (cont u.)
13.400 teor.t1J.)
In gen ral, pressure gauges shal1 be of the bourdon tub: 'ype.
All oral ges shall be Grade AAA with 0.5 percent accuracy anc. 4-1 1/oh phenolic caso... All-stt.<'-less steel rotary geared movnincr.ts shall be used. Treasure range of the gauge should be approxinu.tcly twice the normal f "ensure but greater than the maximum OApoeted pressure. Conner .Ion on gauge shall be l/l'-inch NPT.' Coll syphons arc to be used wr.ere hot condensible vapors (e.g., steam) are present.
13.500 Indicating Thermometers
Dial indicator bimetal-actuated thermometers are preferred. Glass stem thermometers shall not be used. A three-inch dial size should generally be used except where the thermometer mu3t be seer, from a distance greater than 10 feet where 5-iach size should be used. All thermometers should have the stem perpendicular to the dial. Scales should be in degrees centigrade with range approximately twice normal operating temperatures. Stainless steel separable sockets (with or without insulation extension) should be used on all indicating thermometers and shall be welded (or screwed and seal welded) into flanges or couplings so that they are not accidentally removed while unscrewing the thermometers from the socket.
13.600 Safety Valves
Safety valves shall be provided as required by the latest edition of the ASME Code, Section XIV, Paragraph UG-125 through -134. Safety valves shall be provided where abnormal operation, such as loss of power or cooling water, failure of regulator, motor valves, instruments, or other equipment which creates greater relief capacity than normally provided. They shall normally be provided on all pressure vessels, still columns, kettles, heat exchange equipment that can be "valved in," positive displacement pumps, compressors, and long pipe lines to relieve thermal expansion when "valved in."
Shutnif valves should be pr<-.jder unde: all safety valves. Th shutoff valves will be sealed oper. by the Seadrift Plant Proc.ess Safety Department. Shutoff ""Ives must be of full valve pert construction. The discharge of all safety valves shall be directed so as not to endanger personnel or equipment. All safety valves -three-inch and larger should have a filler flange installed bov.'een the ehutoff valve and the salety valve for inplace testing.
13.700 Gauge Glasses
Gauge glasses for obso;-. iug liquid levels in vessels shall not as a
rule le used. Where thv
r.-'i.c'sary the flat-glass high pressure
type shall be used.
016593
jH.OOO lU.100
<Jtn TUBINCr SU1V0RTS
Page 22 April J-,
Ir'-ivirual pairs of vires or multiple pairs of vires shall be rcu. ed aid sup^rted in the most econc^i?al manner provided tnat:
1. They are protected from excess!/* heat, mr^sture, mech-j'l'al daii^ge, and electrical interference.
2. They dc not Interfere with ec^ripic'nt access.
3* Ifeey &re not Installed underground.
*
0-1659^
15.000 15.100
15.200 15-<10
Ik'e 2j April 21, 1967
mUff tgtfHPfMEHTS
A? electrical instrument ratlt shall be as pe.* the Instrument Gables flp sclficr.tions, Appendix F,
15.310
Individual pairs v.f sires from the field Items shall be terminated in field Junction boxes and run in conviui jus multiple pa:'.-* cables tc the interface cabinets. Th< rxocouples, resist, m.? bulbs, analyzers, transmitters, /alve positioners, and ccnjuter digitc.*. inputs and ourj as shall be treated in this manner.
15.120
Splices between the field items and the Junction boxes sr.71 not be permitted. Splices in the multi-conductor cables between the field Junction boxes, interface cabinet and control center shall not be permitted.
15.130 s
All cables, including thermocouples and resistance bulbs, shall be routed from the field Junction boxes directly to an interface box in operating area. A separate interface box for all 115 VAC signal leads shall be provided. An additional Interface box for analyzer leads shall be provided.
15 .l1*
AH thermocouple and resistance bulb cables shall be routed from the interface cabinets directly to the computer room in central control. All resistance bulbs shall connect to "converter" cabinet. This cabinet will be located in the same area as the computer connection cabinets. The output leads from the converters shall be routed to the interface box and treated as any other 10-50 ma measurement signal.All thermocouples shall be routed directly to computer connection- cabinet.
Only one type of the following signal leads shall be installed in any one cable or junction box: Resistance bulb leadwire, AC power signals, and thermocouples. (Only one type thermocouple leadwire per Junction box.) DC signals, both measurement signals and valve positioner signals, and digital input signals to the control center may be Installed in the. same Junction box and cable if necessary. The digital signals will be such as flow switches, pressure switches, level switches, limit switches, etc., and will carry DC signals. All such devices shall have "dry" contacts only at the field.
Thermocouple terminations are to be made under one approved thermocouple terminal blocks so that contiuv'tv thermocouple material is aaintained.
or on
016595
15.300 15.1*00
15.500
ft**** 24 A; .11 21, 196:
DC signal vire, resistance bulb wire, aiii tfc*rr*ocouple vir*: sLnll not be installed in the same tray, coi duit.- or messenger, vita au rover JLring.
15 >310
The instrument cabj.e tra\ and the AC paver cable tray shall be sepp*.ated the ms'cis.uL' distance practical and shall be six feet aj ilmum spacing for "uy parallel run.
til analog signal cue* shall he terminated in an intericce box ir. the process area. Gables, with plugs provided by the console vendor, shall be ure.T to connect these "ignals iron the Interface box to the instrument consoles. All cables shall 1c. routed inside this interface box in a 'neat and Topical manner. Ihira shall be laced into bundles where possible and broken out for individual t-mination as required. Spare pairs shall be laced and colled out of the v&^. Each spare coil shall be clearly tagged to identify to which cable it belongs. Spares shall be of such length as to allow termination to any point in the interface cabinet.
15.^Ip Cables and wire in the control roam shall be routed overhead to the instrument consoles and to the computer.
15.1+20 Shields shall be electrically continuous from the primary element to the instrument console.
15*430
All incoming signals, transmitter, thermocouple, and computer wire shields shall be grounded at the instrument console only. All consoles shall be electrically connected together and then tied to an adequate earth ground. This ground shall be separate from the computer earth ground.
AH cables from, the field mounted junction boxes to the interface boxes shall be installed with a minimum amount of spare length. Ho spare length needs to be provided for relocation of the interface boxes.
15*510
All cables from the instrument consoles to the interface box shall be specified with 5-10 feet of extra length. The length
of these cables shall be determined by the Project Design Group after the console layout is finished.
15.520
Digital signals such as pressure switches, flow switches, level alarms, etc., that connect to either the computer or the instru ment consoles sl^li routed from-the field itev to a field located junction box. Then multi-pair cables shall be routed from the Juncti-'r oox to the interface box. die leads will then be routed to tht instrument consoles through cables and the plugs provided by the console vendor and shall connort to terminal strips inside the console. Those leads that are field contacts to the compute-.* shall be routed through the interface box, an instrument console, and then from the console to the computer.
016596
\}.&0Q
Page 2*
April 11, iy>
All re 3 shall be numbered in accorcancb vlth the .jrthod outlined ic Ayp'-ndl: "J"; wire numbering method.
15.700 All leads, where tagging Is requir'd, shall be tagged la accordance vlth tbr- *ethod outlined In Append!:: "I"; wire marking method.
15.8CO
'JBhe following analog signals tha\ x:or or exit the Instrument -casoles tbail be 10-50 I'A DC: a) transmitter outputs; b) co.vTM.*ter outru*s; c) controller outputs to valves
016597
Page 2 > April 21, 19^'T
16.000 1NSTHJMENT PIPING AND TUBING
16.100 i't carbon steel tubing or tu'-e Jit tings are peimitted.
16. MOO
Instrument installations shali be j.j shown In the Instrument. PLping Detail rbnuax- Special sketches, for lit* project only, shall be mal: as required. srd assigned c*etch numbers cr letters by the desi?.. froup. J!lctrical in3ii~mient installations shall be as per the SP-16Q1, 602, etc., set of instrument sketches.
16.300 Pipe or tubing shall not normally be supported from process and service piping or process equipment. Exceptions shall be made when it is most economical to support one or two lines from the piping or equipr^.t.
16.310 Groups of supported tubes shall be clear of insulation.
16.320 , All lines shall be supported as neatly and inconspicuously as possible utilizing the most economical approach.
16.330
Horizontal lines shall be grouped one above the other, i.e. side by side in a vertical plane, whenever possible. In order to provide proper access to all lines for maintenance, not over two such groups shall be placed "back-to-back." At tube connections, the lines being connected shall be offset (raised) from the group, and the connections staggered, to provide access for wrenches.
16.340 All bends in tubing lines shall be made with bending tools, and shall be free from kinks and flats.
16.350
All lines shall be free from cutting burrs and shall be thoroughly cleaned prior to installation. The ends of tubes cut in the field shall be reamed to the inside diameter of the tube. Teflon tape may be applied to male pipe threads as required. Particular care should be taken to see that excess tape is not applied or the tape is applied in a manner that would cause pieces of tape to shred and possibly plug small restrictions in the instrument leads.
016598
17.000 irCTPtmi-.-.T DRAWINGS
*8* 27 Apiil 21, 1967
a#.:?.00 The
and instructions :ercsiry to allow the control systems to
be installed, properly checked 'nd calibrated, operated and viol itnined
shall bo provided.
J7.JXX) An instrument specification iv c shall be prepared, (Gee Appc.vl '. D,) for oacH instrument system and shall conai.-.t uf the following m.rt:;. This sheet sj.'l be included in design reports and check books.
i7.2.'0
The instrument sketch shall be a functional diagram of the control system with adequate information shown to enable qualified personnel to functionally check the loop and set -11 adjustable devices. This sketch is not intended to be a detailed wiring diagram. The sketch will show:
17.211 All components in the loop.
if,212 17*213
Associated process equipment such as tanks, pumps, columns, reactors, etc. and shall be approximately to scale with approximate elevations. Sufficient infor mation such as flow direction, vent lines, etc. shall be to functionally describe the system.
t
Pertinent installation instructions as required such as SK-numbers and/or notes.
17.214 Which components require instrument air, (whether 100 psig or 20 psig) purge gas, plant air, case purge, etc.
17*215
The controller action (i.e. increase in input. Increase in output or vice versa), the valve positioner setting; pressure regulator, pressure switch, electronic alarm trips setting in addition to all other field adjustments that must be made prior to start-up.
17.216 Wire identification of each wire that leaves the instrument console.
17*217 The function of eich alarm or 6hutoff device shall be
denoted, i.e. high L.L. alarm at. 78 or lc;; I..u closes tails DM7 E-419C-1 at 18*.
1?.220 Specifications
17.221
The specification ^r^ion will consist of either six or twelve columns in either one or two rows. Oi.e column will be provided for each instrument item. A column will show the item nutber, type, manufacturer, and up to 15 lines of. detailed specifications on an individual item. In the event that the space for the detailed specifications proves
016599
r-e* April 21, 19
17.22u Specifications (Continued)
17.221
inc'i'*-uite, the notes yorUon on the bottom pac t cf sheet shall be used. 1;' twelve columns are inadequt^e to specify
of the itjrx i-i a loop, an additions! sheet, without a sketch, will be .-iced. Should the coluiu not be cyplicable to that -item and io-e detailed specificatio.it ere required., either - oarate a*-*,nchnent or the note space below a rix column shett .'ill be used.
17.22? Notes
17.223 The notes portion id required to provide space on the sheet for:
a. Special or excessive information required in an item's detailed specifications.
' b. Presenting a written description of the system's operation.
17.230
Except for the more involved loops, with computer computation, multi controllers, interlocks, shutdown systems, etc. the descriptive title found in the title block and the loop sketch will be sufficient to describe the system's function.
17.231 Title Block:
The title block to be located in the lover right corner of the sheet will provide the following information about the loop:
a. Descriptive title of the loop. b. Unit title c. Plant location d. 930 work order number e. Flow diagram number f. Control system engineer's initials g. Checker's initial h. Date of preparation i. Date of su^equent revisions J. Prefix fer iustru-ient item numbers
17.300
r^xooro will provide UCC with tievex al "block diagram" type instrument sketches that represent approximately 90-95^ of our expected loops. The instrument designer or draftsman sha1 \ complete this sketch by showing xtera numbers and correct wiring identification. This sketch shall then be forwaxiee to Foxboro
by the Control Systems Engineer. Foxboro shall use this sketch to prepare electrical drawings to prc-vAre the panel. Refer to Appendix "D" for examples or Mr.boro "flock diagram" type instrument sketches.
016600
Page 29 April .L, r.'6'i
27*400
fox-C'-o will provide lTCC a detailed, "* wired,panel drawing for rz.a. instrument loop showing the necessary derails to allow point-to-pc lut
eietckiig of the loop inside the co.isr.le. All wires that exist frts th'.eon::ole rball be tagged strictly :.n accordance wit* ths tagging requ .cted by UCC. These sketches will b*. provided to the plant personrei similar to Instrument check books.
17-410 drawing showing the "behind th; i+xjel" terminal strip lnyout *cr AC
newer and I*/
shall be provided -y Fbxboro.
17.420 17.430
It will nor. be necessary for the Engineering Contractor to pxcpar? eny interanal panel drawings except power corc^tion drawings as noxc! elsewhere
The normal sketches such S3 Instrument plan drawings. Junction box lay-out, tray routing, interface box layout, etc. shall be prepared and issued by the Engineering Contractor.
*
016601
18.000 18.IX
18.200 18.300
18.400
ftge ?J April 21, 1967
HTggg'KEtn? ZLTC^?IGAL COMHECTxOn EOKES
All dectricrJ. Instrument signal xerids shall be routed to the Interface boor through multipair cables a,d field mounted Junction boxes ^s shown in deta.,1 un Appendix L.
18.110 Only one multij?ir cable, either 12 pair or 24 pair, 3'an 1 be Installed In eny one Junction box.
16,All thermocouples and resistance temperature dectectcr.-> 'KED's) shall be routed with 12 uai1** cables through electrical Junction boxes as shown In Appendix L. The electronic sisnals shall be routed In a similar manner.
All a.'ltipair cables shall be in accordance with the cable specifications in Appendix H.
These standard field Junction boxes shall be used for the following functions.
% 18.310 Specifications for the purchase and prefabrication of the
Junction boxes.
18.320 18.330
Instructions on the tagging of terminal strips by the Junction box fabricator.
*
Issued to the field for detailed instructions on the methods of connecting all shields and drain wires. The methods of shield connections shall be strictly followed.
An Interface box shall be Installed in the process areas. All multlpalr cables from field Junction boxes to the instrument consoles shall be routed through the interface box.
18.410 The Interface box will be used as an "unscrambling" point for wiring from the field cables to the Instrument consoles.
18.420 The Interface box shall be a mirHTmim of four (4) feet wide and. will be expanded in two (2) foot increments.
18.430
A separate interface box is required for the 115 VAC signals and another interface box for the process analyzer lead-*. This means that a total of -aree interface boxes is requir*>u.
016602
Pac* ^1 l.jrll 21, 19Cr
j.8.500 All jui.eticr boxes shall have a phone jack, accessible tram tii* v.utside, umi'able for sound powered phone crxainlcation with the control rx.
18.600 A Bi.leuo of four
spare pairs shall be nade available for all 12
pttli thermocouple 5uid resistance temperature detectors junctiur boxes.
l85z ' A minimum of five (;) spare pairs shall be made anr 'l '.ble for all 12 pair 1 metrical Junction boxes and eight (8} ^pare pairs for *1124 pair electrical Junction boxes.
18.620 -
The interface box shall designed and sized to connect all *hc instrument signal leads, including all spares, with space and terminal strips for an additional 30 number of wires.
016603
9.000 A3ALY7&? SEECIFICATUi.'S
Page 32 April 21, J;6
Aa7Jend l\- "E".contains the general specifications for process analyzers-
*
016604
yc.ooo msTHUiiErr safliy criteria
Pu'- 33 Ajx 1 21, 1967
Append, jc "F" contains the basic, specifications for fire protection criteria lor the Instruments and control systems.
016605
2.1.000 mSTFUMOTV FLOW PLAN SYMBOLS
Pav 3U *pril 21, 1967
Appe'idJx "O'* contains the flow pli'i symbols that should be u?ad ov the . pz-oc*ss and instrut-iut vliagrams.
** '
*
016606
AFPEITjJX a JOTCTIONAL JB0A!LnKJ *EECIFICAT3tfS
April 2L 19d7
(To be Issued la;-,er)
016607
APPErOIX 2 8Pacinci"iras FOR XLKCTROIIC corm^ ROOM mSTRUKEirrS
fl{V?r i T'i rr. t,j Sheet 1 . 1' 7
April 21j 19^7
TIPI; ELECTRONIC IHDICATIHO COHTROLLER
SPBCIFICATIOHS:
MODEL.:
62HF-^V-P (Se Rotes under Auxiliary.) Tu-Line Type Controller
1RPUT:
DC current, 10-50 as
MotnrriHG:
Flush panel mounting, multiple unit mounting
OUTPUT:
DC current, 10-50 ns, vith output gauge
CASCADE DIPUT:
DC current, 10-50 na signal
COHTROL ACTI01:
Proportional plus reset
POWER SUPPLY:
115 volts AC, 60 cycles per second
CORSTHUCTIOE:
General purpose
AUXILIARY:
Renote-local switch to allow switching the controller set-point fron local to cascade. This switch to he accessible Fron the controller front. Provisions are to be incorporated in the controller to allow balancing between cascade and local set point. This Is also to be front accessible. All controller connections are to terminate on a terminal strip located behind the con troller. A flexible cable is to allow the controller to be withdrawn from the panel. This method of with drawal should permit withdrawal of all tL- electrical working pert;.
Provide an auxiliary contact on the resavte-local switch to close when the controller is in the cascade set position. TaIs contact is to be connected to the con troller terminal strip.
All controllers shall be supplied wltL the measurement
loop load pet nd fuse integrally mour.ted in the controller.
016608
SPECIFICATIONS FOR ELECTRONIC CONTROL ROuri INSTRUMENTS (CONTD) TOL: ElEGTECHC INDICATING CONTROTI-Ef {CCxZD)
Appendix 3 Specifications Sheet 2 of 7
April L, 19^7
The controller scale t.hall be completely witt v.'.ch . black figures. The so-.le as per individual -e:ificatians. The controlle; s&t point knob is to be black.
Engraved nameplates shall be furnished for each scntroller and shall be mounted on each controller front plate. Engraving details will be supplied at a later date.
NOTES:
Model 62HF-4V-P
This controller is supplied with Guard Plate on renotelocal switch to prevent the switch from being accidentlythrown to remote when controller is used as local set only. For use of both local and remote set positions, this guard plate must be removed.
Mcdel 62HF-5V-F
Same as above except three mode (proportional plus reset plus derivative).
Model 62HM-Z.V
Same as 62HF-4V-P except with motor driven set point for use with computer pulse output.
Model 62HM-55
Same as above except 3 mode (P + R t D) control. TYPE: VERTICAL SCALE INDICATOR
MODEL: ISPUT:
65 PV-u2T 10-50 ma D.J. (5 OHM input impedance)
Flush Panel
SCALE:
3-7/8 inchts long, black > vune-alo on white with fluorsecent red pointer.
CONNECTIONS:
Rear Terminal Studs
016609
SPECIFIC iT'-ONS FOR ELECTRONIC CONTROL ROOM INSTRUMENTS (CONTD)
TIPE: TE^'CAL SCAIE INDICATOR (OfJNTL)
ACCil?*C7:
2 percent
iFRO ADOJSTHENT: Front of instrumex-t
EIECTi.'ICAL CLASSIFICATION: General Purpose
Appendix B
Specifications Sheet 2A of 7
AprM 21, 1967
016610
Appen.Mx .. Specifications Sheet of 7
April kl, :,,6t
SPECI71CATICB--- FOB iSECTROHIC CONTROL RrOM INSTRUMENT: (COlfTL)
TYPE: P-g'TSTAKCE-BULB-VO-qjRRar- (OIT/EFIEPS
LMX.tFICATIV'':MCTfcL: RANGE: OUTPUT: CONSTRUCTION: MOUNTING: i POWER SUPPLY:
694AR-0A
To he specified later (adjustable vitnln Halts) DC current, 10-50 na General purpose Rack mounting 115 volts, 60 cycles per second
TYPE: KILLIVOLT-TO-CURRENT CONVERTER
SPECIFICATIONS: MODS.: RANGE: OUTPUT: CONSTRUCTION: MOUNTING: rO*iP GoFPLY:
693AR-X To be specified later (adjustable within Halts) DC current, 10-50 me General purpose Rack mounting 115 volts. 60 rycles per second
016611
A|>I*iiiI k ,.
at
.Mnt' * or 7
A/;ril Ll, 19t7
SPECIFICATIONS FOR ELECTRONIC CONTROL ROO. HS-y.'ttSHTS (CONTD)
Tmi airJTRONIC RECEIVER HECORSEBS
SPECIFICAT7 CV3:
MODEL:
RANGE:
DC voltage
derived by a suitable dropping
resistor In meesu"ement loop. 1-5 volts.
NO. OF PENS:
2 (Red and Green)
CONSTRUCTION:
General purpose
MOUNTING:
Flush panel mcxinting at 60* angle from vertical
CHART DRIVE:
3A iph
POWER SUPPLY:
115 volts AC, 60 cycles
CHART AND SCALE: 0-100 uniform divisions
AUXILIARY:
With rear-mounted terminal strip and scan-fold charts.
TYPE: MANUAL SET STATION
SPECIFICATIONS:
MODEL:
6UHTG-LP
OUTPUT:
DC current, 10-50 ma, with output gauge
CONSTRUCTION:
General purpose
MOUNTING:
Flush panel mounting, multiple unit mounting
rCVH; .xP'PLY:
115 volts, 60 eyries per second
JIi..`./RY: f
VE?.f)R:
All instrument connections are to terminate on a terminal stri;j located back of the in6truA>ct. Cord-set ivp. construction Manual output kkoc shall tc blnck.
Foxboro
016612
jp^ndix b Specification Sheet 5 or 7 April 21, 19^7
SPECIFICATION1. FOR ELECTRONIC CONT3QI. ROf M INSTRUMENTS (CONTD)
TYPE; RaTiO CONTROL STATION
SPSCi F"C.' TIONS
MODEL.
67HZG-1-LP
INPUT:
DC current, 10-50 ma
OUTPUT:
DC current, 10-50 an
CONSTRUCTION:
General purpose
MOUNTING:
Flush panel mounting, multiple unit mounting
POWER SUPPLY:
115 volts, 60 cycles per second
AUXILIARY: VENDOR:
Cord-set type construction. All instrument
connections shall terminate on a terminal strip
located in hack of the instrument. Process VARutacu t#/eAn>A r* 8a
srpr/oA/,
FOxboro
TYPE: ELECTRONIC PRESSURE TRANSMITTERS
SPECIFICATIONS:
MODEL:
61101 and 611GL
RANGE:
0-5 to 0-500 psig {range as per individual specifications)
MOUNTING:
Yoke mounting for Pipe Stand
BODY: CA::X:
Jl6 stainless vlth 316 stainless steel element
Explosion-
classification
Class T, Group D, Division I
CXmVT:
10-50 ma DC
AUX1 I .f i.MIY : VENDOR:
Vendor t.o ^trnlsh n Be:-; ty rrr.nluel atrip
inside th*. >.jco to lOmit'c . s.h."
signal leads.
Foxboro
<
.
016613
Appe^iiic h Specifics-Iona Sheet 6 of 7 April 71, 2567
SPECIFICATION *~t?R ZLItCTROWIC CONTROL ROOM I'lSTROHarTS (CCPTD)
TYPE: ELbTTHONiC DIFFERENTIAL PPFSSUK2 TrtANSKITTERS
.WIFI CATIONS: men.: RANGE:
MOUNTING:
BOOT:
>
CASE:
OUTPUT: AUXILIARY:
VENDOR:
613EM and 613DL
0-5 to 0-800 Inches of water will full elevation and suppression. (Range as per individual specification.)
Yoke nountlng for Pipe Stand
318 stainless steel with 316 stainless steel element
Bcploslon-proof classification Class 1, Group D, Division I
10-50 ma DC
Vendor to furnish a Barrier type terminal strip inside the case to connect the input signal leads.
Foxboro
016614
Apinrili it Specific*wXon
Sbeec 7^7 April 'c2 t 1967 SPECIFICATI0H3 FOR ELECTRONIC OOlfTBOL ROOM T^STHTOCyTS (OONZD)
016615
APPENDIT C
Sheet 1 of 10 Ayrll 21, 1967
INSTRUMENT PANEt-
CATIONS
Prt idr til 2rbor and materials as required to completely prefabricire and prewire an in*' Tvnent pcnel board as detailed telcv,
I. GENERA! CONSTRUCTION
The panel shall be 4' wide overall, approximately 7*9" high.A sketch showing the panel layout is attached.
3' deep.
. Each outer end of the panel shall be so constructed as to permit n identical panel to be "bolted on." Therefore, at each outer end, the ins truants should be mounted so as to provide a center line spacing as nearly equal to other spacing* as possible.
The panel'shall be smooth, scalefree, good quality steel, finished according to the vendor's standard method. The panel steel thickness, the panel support, and the instrument supports shall be specified by the vendor. The panel top and back shall be louvered in a manner determined by the panel vendor as required for ventilation. The panel top shall have a removable access plate. The panel shall have louvered rear doors.
%
Ventilation and cooling shall be provided as required assuming the panel to contain 48 controllers, 20 alarm trips, 20 annunciator alarm points, 4 trend recorders, 20 lights only. Ambient conditions -- normal; temperature 70-85*F, humidity 60-90%, maximum; temperature 95*?, humidity 95%.
The panel interior shall be primed and painted white. The panel exterior is to be primed and painted. The color to be light blue, similar to Foxboro chip BL-1.
The RTD (Resistance Temperature Detectors) converters and the millivolt-toeurrent converters are to be mounted in a separate area and shall be connected to the interface box through cables and cable connectors similar to those described under III, WIRING. The mounting arrangement and wiring for these converters will be specified separately.
AH holes for trend recorder plug-j^cka, pushbuttons, switches, etc. shall
be drilled. All cutouts and
not filled shall be prc.ided vith an
adequate plug or cover ?late painted to match the panel and maintain console
front continuity.
All vacant controller, verti:al indicator, and trend recorder slots shall be pro.ided with a cover plate printed to match the panel.
All pushbuttons, switches, bcllseye type lights, etc. viil have nameplates installed b- t.he panel vendc". , The annunciator test a_i acknowledge
pushbuttons shall be clearly tagged and lurnished by*the panel vendor.
016616
I. GENERA! JQKS7RUCTI0H (Continued)
Appendix C Sheet 2 of 1J
April 21, 1907
The panel vendor shall mount behind tht panel such Items as alarm -rips,
shutdown relays, etc. The alarm trips and any other rajor items will be
6ipulled by the Engineering Contractor, uie alarm crips will be A.1.3.
type 7If-2l4c and ET-215C surface motur.e-' units. They shall be jounce-' side
by side facing -the
of the panel azJ'te accessible frv" the pane.1, rear.
Space for 115 VAC power receptacles shall be provided in each ponel auu
mounting pxs.te'" provided for 20 alarm trips per panel.
Although the control room console layout may require the panels to be joined at certain points in SO* Joints, all the consoles- fronts will be Identical. Since the consoles have the trend recorders mounted on a sloping secti*> of the console, a filler panel Is required at each point where the panels are Joined at an angle. This panel Is to be painted to match the consoles and shall be supplied by the console vendor.
All relays thal are required for shutdown or automatic trip service shall
be 115 VAC potter Brumfield, DPDT contacts. These relays shall be mounted using Faxboro Socket No. B113KA. (These were furnished to UCC on Fbxboro Job No. k-273T5, Foxboro Order No. 64N-27375 Reference Drawing No. IV-1, Sheet U5.) Obvious exceptions shall be made for unusually high current switching, different voltage levels, etc.
II. FRONT OF PANEL LAYOUT
016617
The detailed Instrument layout for each panel with Instrument item numbers and panel locations shown will be as per Individual panel specifications and will be furnished later. For general console layout refer to Appendix "D".
The general layout of the panel is as follows from top downward.
Two (2) pieces of SCAM or Rochester Instrument Systems (RIS) light panels
with 6 wide by 10 high window spaces. The majority of the light panel points
are to be actuated by digital output signals from a computer. Approximately
twenty (20) points per console, ten (10) points per light panel, are to be
actuated by a "remote mounted" annunciator system. This "remote mounted"
annunciator shall be in a 2t" relay rack mounted inside the console behind
the light panel box. Both the light panel and the annunciator are to be
supplied by Engineering Contractor but snail be mounted and wlrd by the
panel vendor. Certified drawings of
cutouts required will be furbished
later.
Two '`2) rows of twelve-rack vertierj. 3cale indicators. These indicators shall be mounted in a manner that will permit withdrawal of Individual meters or the complete twelve rack for maintenance and/or replacement.
Eight (8) rows of six-pack indicating controllers. The bottou two (2) rows may contain miscellaneous pushbuttons, electrical switches, and bullseye ` type lights.
Tour (k) pieces of trend recorders reqcji'ing four (k) cut ouur per *nel shall be provided as part of the panel package. These two pen trend recorac-s c-re specified under the "panel instrui'ent specifications" section. Trend recorder
rr. IBOHT OF PAKrlL A1?TH` (untinued)
Appendix C Sheet 3 of 10
April 21: 1967
plug-Jacks, 96 'per instrument const. Lj, ire to he mounted on the slcpjd section of tk.. console above the trend r-corders. The plug-Jacks siall be aoi'.n^ed lu sections of 6 vide by 2 high, eight such sections per instru ment console. These sections rhali be designed and constructed jo t*-it these plu^-Jt/'ks and the associated virlntf cae he withdrawn, thus exposing Ijth th. wiring and plug-Jacks for rep*.'l. or replacement. The plug-Jac.-o 3vail i tagged in a predetermined manner to identity which point Is ccnn*cted to each plug-Jack. The required desigaatter will he shown on a typical panel layonw dx swing furnished by UCC.
One controller location In each console to contain a Ibxboro Model 6TEF manual by-^ass station. This by-pass station will permit any controller In- the console to he removed from service while the process variable is --"nny controlled from the by-pass station. Jack receptacles are to be located under each controller or manual station in each console. The Engineering Contractor to Indicate on the panel arrangment drawing the locations not,requiring a receptacle so that a plastic insert may be Installed in the receptacle hole by the panel vendor.
m. WIRING
Wiring;
All wiring to he installed In accordance with the applicable provisions of the National Electric code.
Classification: Open wiring. Wiring to be neatly bundled and/or plastic troughs. Enough spare space is to be provided In troughs or space provided
to run bundles for complete wiring of every available Instrument space in the console.
Connections;
All wiring for the electronic console Instruments shall be through multiconductor cables with a molded plug at one end for plugging Into the Instrument
All controllers and vertical scale Indicators are to have a marked terminal block located directly behind that respective Instrument. This one (1) terminal block is to contain the connections for the entire Instrument loop, l.e.. This block is to be the Junction point for all leads In the control loop > acl-Jirc, controller input, output, cascade set-point. power surrjly, and the open-closed contacts to tbe computer, analog Input signal to the com'"'ter, wires to trend recorder jacks and other devices sue* as rjarm units, reliys, etc. As shown on the pare! board drawings, space is provided for a maximum of 48 controllers and a maximum of 2k vertical scale indicators per poriel. All controllers and vertical se?le indicators shall be capable of trend recording. An additional 24 (maximum) analog variables per panel, capable of trend recording, also exist. Terminal blocks are to be provided for all these items and the spate items are to be pre-wired including trend recorder connections and dropping resistor, d.c. power supply for measurement loop,115 VAC power where required, wiring to connection plugs, DC distribution pcnelr, computer input dropping resistor, etc.
016618
Append'1'' Ifcge 4 of 10 Ay* J. 21, 1967
HI. WHL.TG (Continued)
Connect.Ion-: (Continued)
. Shoe' analog variables tnat are neither controlled nor Indicated on the jectl shall be connected to a ranted terminal block located 1? the irstrsv .at console. Uhls teririn-2 block shall be a mini sum cf 8 points, Jore* iio. 140 or equal.
All i-cnn.-ctions betveen '..e panel w':ruments and the field and computer are to be >rlred by the pane- vendor to suitable cable connectors. (These connectors .ire to be specified r.rvl furnished by the panel vendor subject to approval o> UCC.) The following is an outline of the wiring scheme:
All controller input-output leads re to be wired by the panel
vendor to cable connectors securely fastened to the Instrument
panel. The input-output leads for a controller are to be
connected to the same cable connector.
algo wlre-the~mating-oabTe-g<annert,or anti-tag-thc-qther-end-of- *
J~n irf Wsj
ft-wdy TO. 1-V-T-gr
-S-- L <iT
All analog measurement signals to the computer shall be treated in a similar manner. Only analog measurement signals are to be tied to a particular connector.
All contact closure signals from the controllers to the computer and the output signals from the RED converters and MV converters are to be treated likewise. BSD converters and MV converters output signals .may be connected to the same cable connector.
An additional cable, six (6) pairs. Is to be used for any mis cellaneous signals carrying 125 VAC, such as solenoid valves. 115 VAC leads shall not be connected to the same connector as other leads.
The panel vendor will use 24 pair ^cables. Reliability and long service life- are to be prime considerations in the selection of the cable connectors and cable.
The signal cable used for all connections except 115 VAC to the instru ment consoles shall be as specified below and furnished by Foxboro:
Conductors: 20 guage 7-strnd copper, 24 pairs per cable
xx-imazy Insulation: 15 mils ^0C rVC or high-density polyethylene
Humber of Conductors per Croup: 2, twisted
Color Code: Black aid White
Bair Identification: xhch jair numbered
lay of Twist: 1-1/2" *0 2.1/2"
e Overall Shield: 100^ jor.'erage 2-3 1 *3 imri
a -r tape with
* 20 gense 7-strand copper drain wire
Overall Jacket: Black ^G*C P/C, 65 mils nominal
Communication Ihir: To be included in addition to specified
number of pairs
Manufacturer: Dekoron or ntroved equal
016619
III. WPINJ (Continued)
ppendlT C, Page 5 '->f 10
April 21, 196T
ConneecJoiu.: (Continued)
Tht cable for the miscellaneous 115 VAC signals snail be as specified h.ciev and furnished by Foxboro *
Contactors: l6-gauge 7-6trajd cjyper, 6 pairs per cable Primary Insulation: 15 nils ro-ii.al 90*C PVC or pick.' density
polyethylene
Kemper of Conductors per Croup: d, twisted
Color Code: Black and White Lay of Twist: 1-1/2" to 2-1/2" Shield: 100% coverage 1 mil aluminum x 1 ail mylar tape with
18 gauge 7-strand copper drain wire Overall Jacket: 30 mils black 80*C PVC Manufacturer: Dekoron or approved equal
Listed below is the minimum amount of wiring that shall be done by Fbxboro on each instrument console for the respective items listed. This list will be updated by UCC as required.
Analog Signal to the Computer: (maximum capacity of 96 per console) Four {U) pcs. of 2k pair cables per console completely wired at
the console side including computer input dropping resistor. The other end of all cables shall be clearly tagged with the appropriate
Item number. All spares shall be clearly tagged so that identifi cation as to console, cable no., polarity, and specific terminal strip can be easily made.
Controller Cascade Setpoint Signal from Computer: (maximum capacity of 1*8 per console) Using 2k pair cables, a minimum amount of 50% spare capacity is to be the designed basis for these points. A minimum of one (l) 2k pair cable is required per console with an "average" use of one (l) per console.
Digital Signal from the Controller to Computer: (maximum capacity of U8 per console.) Using 2k pair cables, a minimum amount of 50% spare capacity is to be the desi&i basis for these points. A minimum of one (l) 2k pair cable is required per console with an "average" use of one (l) per console.
Miscellaneous 115 VAC Signal(maximum capacity is untfprinedl
Using six (6) pair curies, ttic number of cables per console will be
determined leaving 50%
as a ,'jinimum. Each consol., chill have
one (l) 115 VAC cable as a minimum.
Digital Output Signals from the Computer to the Cenacler (maximum
capacity approximately per console) Using 24 pair cp.oles, a minimum amount of Uo% spau capacity is to be the design basis for these points. A minimum amount of one fi) 2k pair,cibie is required per console with an "average" esc of three (3) per console.
016620
III. WIRING (fcnclnucd; Connections: 'fontiiiv.ed).
<
Apv*TiXX C Pr.'.e 6 of 10 April 21, 1967
F.-I, MV-T, and TC-I Converter Ouiput to the Interface Box (m'xiDfd capacity undefined) 2- >air cables. These requirement* a:-.c to be defined scpara;-2y.
Uni'a* specifically exceptea. all annunciator points shall be actuav.1 by external dry contacts. The output signal of alam triju ("IS model ET-214C and ET-21>T) '-ill be dry contacts. Th" voltage output signal from the alarm trips~Shall not be used to actuate the annunciator points.
Poxbo.*'* shall provide as a part of each console, a/gfo) volt DC power supply to provide power for a minimum of 120 light pnnel points at 3 watts per point. This power is required to power tith the light panel points that are actuated by the computer digits' output points and the annunciator system. This power supply will be resolved by Foxboro and UCC but a simple and reliable supply, with little filtering, is anticipated.
Wire Type:
All instruments such as transmitters that connect only to the trend recorder points and the computer shall be terminated in the terminal area with terminal strips so that the output signal from the field transmitters and any associated panel board devices can be connected to the terminal strips completing the circuit.
All wiring in the Instrument panel, with the exception of the flexible cable for controllers, etc., shall be JVC insulated wire and stranded TW copper whenever possible. The wire size is to be determined by the panel vender using good conservative engineering practice and sised for maximum possible panel load.
Industrial quality disconnect plugs shall be provided for all 115 VAC power to all devices, except those specifically mentioned, not using a flexible cable type construction. All cords to be No. 16-3 conductor, rubber covered. Approximately 30* spare power receptacles are to be provided and located behind the panel. The following items shall not require pov-.r disconnect plugs, annunciator, fans, illumination lights, eiinr. nor-., service receptacles, ;tc.
Joe* >,ur.cls shall be completely installed, 96 per panel, and wired in tha space shown on the panel layoct drawing. These jack panels shall b*; designed and constructed on a relcy rack or similar technique to permit withdrawal for checking nnd/or replacement.
016621
III. WIHinn (Continued)
Append!:. P Inge 7 of 10
April 21, 1967
Wire 'fipe: (Continued)
Kaa*.. 115 VAC power lends ore to c mnct to a reasonably isoleseu section o' the terminal area and be JVC inru-* >ted strs-.aed TW copper. Two (2) separate 115 VAC power sources 5ha?] be provided for each r<me.i , One source will pc*-c,` all control loop instruments such >s controllers, ratio units, manual regulators, alarm ui:its etc. This cii*. '.t shall have an individual circuit breaker for each panel. This souice snvll be 't 'erred to on all drawings and terminal strips as "primary AC power." CVe .econd 115'VAC source will power all other devices, such as trend rweerdors, annunciators, panel illumination lights, nc"*s, nnd service receptacles. Thic source shall be referred to os the "secondary AC power" circuit. A circuit breaker is not necessary for this circuit.
All wiring connected to screw terminals shall be tanged with spade lugs and all leads identified per wiring diagram with Brady marl.era or equal.
1
All measurement wiring to m/6420 trend recorders shall be through a "Cordomatic" reel with a round two conductor rubber coated cable, with the cords protruding through the console slope. The trend recorder connection plugs shall be color coded, red and green, tc identify pen color.
a
Each measurement analog signal shall have a dropping resistor in series with the loop to develop the proper analog voltage signal to the computer. This resistor, value to be determined later, shall be a noninductive, high quality, precision (+ 0.1%) resistor supplied by Foxboro but approved by UCC.
Terminal Area Miscellaneous:
The rear of the console area shall be supplied with protected lights mounted to,provide adequate illumination to both the terminul aret and the back of the panel. An on-off light switch shall be furnished for each panel.
All terminal blocks containing 115 VAC or ?30 VAC shall be covered.
Positive protection shall be provided to prevent accidental tripping of any power switches cipher by thtr location behind the twt.cI or bv. a guard.
One terminal block per c^'seir for tho following, clearly corked on both console and drawings shall be provided.
) 115 VAC primary power (?) 135 VAC secondary jv-vrr
(3) DC po^cr to measurement loop
All cables that connect tc ti><- instrument console shall be bottom entering. AC power connection .hkI DC town Conner'ion V.-uk nr.ll also bo bottom entering. All cables and <-. hTr connectors shall b olecr1*' lagged ns per the electrical wiring drawing:..
016622
Appendix C. ftU'.c H of I A^rll 21, 1967
H1SCEU ANKQUS
A Prating;
Approval drawings are required fov the panel structure. One transparency and 6 prints arc rcq .red of f-il drawings snowing the behind the panel terminal inp it-citput connections.
One transparency and four complete copies are requi-otl of all l"p drc.:nn^e. (These drawings include the input-output connection identification for each loop.) This includes electrical *T.:l;igs for any shutdown systems as required, tho annunciator system, electrical power, etc. All loop drawings for a particular panel shall be packaged in a separate book that includes all applicable drawings for that particular panel. This book and all associated drawings shall be clearly identified with the proper instrinent panel.
Ttv- prnlrl vendor shall maintain close communication with the enr.I neerin contractor rej^arding the type of drawings to be made and the proposed layout or the behind the panel terminals.
The panel vendor shall provide a parts list of all items not specified by UCC but furnished as a part of the instrument panel. Examples of these items are plug-jacks, circuit breakers, terminal
blocks, cordamatic reels, cable connectors, etc. Adequate infor mation such as detailed description, part no., manufacturer, or Foxboro part no. shall be provided to allow UCC to purchase duplicate replacement parts later.
B. D.C. Bower
A common D.C. power distribution system will be used to provide the
required 65 volt DC power for all measurement loops in some pre determined number of instrument consoles. These DC power supplies and the associated DC switchover system will be remote mounted from the instrument consoles. A DC power distribution system will consist of the following:
Two (2) pcs. of Sorensen model DCR 80-30 DC Power Supplies Input: 187-229 VAC Output: 0-80 VDC, C 30 rrp?, - 0.1^ line and load re^ilarion
These two DC power sup,li zz vill cerate in parallel -1 :h -ch unit providing approximately half the load. A "DC switchover unit" shall monitor the ui'lput of each power supply ud remove * cower supply that is out-of-limits from service vni transfer the total load to the remaining power supply.
The D.C. switchover unit will be provide-'! by FcAboro a.id shall conform to the following specifications:
Input: Two (2) 65 V.D.C. sigctlo, 0-30 amps
(output of two DCR 80-30 supplies) Output: 65 V.D.C., 0-60 ucp
016623
.'vr-'aaix C fage 9 of 1C
April 21, 1S6?
IV. KTSCETJJa-FUUS fContinued)
B. 1). 1. Fger (Continued)
function: Continuously monitor the output voltage of the two Sorensen DC. yover supplies; check agaiur-t pre-set .*ijh end low Units. Normally, both
supplies wii" '-e in service. If either power
supply output exceeds ti*.
Units, eiths*
high or low, that particular unit is to be re-
noved from the load. The remaining supply will
then carry the total load.
a
.tuxillary: A red signal light shall be provided for local Indication of a power supply failure. Additional dry contacts shall be provided to actuate a renote
annunciator. The D.C. switchover unit shall be designed and packaged to permit the physical removal, for maintenance or checking, of each switchover unit, ' l.e. the unit will be packaged with the electrical parte separated such that the monitoring and switchover elements for either the No. 1 power supply or the No. 2 power supply esn physically be removed and still have either of the power supplies supply the load. A bypass switch, with local indication, shall be provided for each switchover unit.
Review drawings are required for the electrical design and packaging of the D.C. switchover system.
C. Recorders
Four (U) 2-pen, 115 VAC chart drive, 0-100 uniform divisions chart and scale recorders with standard general purpose housing shall be mounted and supplied with this panel. These recorders are to he voltage input type recorders. The voltage input to these recorders is to be derived by placing a resistor of suitable value in series with the current measurement loop. The recorder range is to be 1-5 volt DC with a 3/4 HH chart speed. The ink colors shall be red and green.
D. Checkout
The panel vendor shall havt' che responsibility for the pr^p-- operation or all equipment, including any item supplied by th.' Engineerinc C-ntractor that is purch&jed from other manufacturers, mat In n.ountcd and wired os u portion of che panel package. Several er;-upics of items covered are the light panels, annunciator system, snutdown system relays, alarm units, d.e. power supply system, c4. o. Proper
operation of items supplied by the Engineering Contracts,! ^rom manu facturers other than Ftxboro means correct action, correct wiring into loop, etc. This dees not mean checking tnc accuracy limits and drift on the items not supplied by the panel vendor.
*
016624
IV. msCTLl^-lFcUS (Continued,
Appendix C. Page 10 of 10
April 21, 1967
D. CkecWut (Continued)
T .* panel vendor shall complete! / check out operationally all ".cnscles, electrical viring, etc. ** ;h additj jxis aade to specifically to our particular paid design and loop wir.'ig, `hi
"PANEL Ih^PECTTON AMD CHECXOUT1' procedure as described on Foxfciro
form U395, dated 4/65 is adequate. Certain obvious ' tTS, such
as the trend recorder jack panel, vertical scale indicators, etc. shall also be checked.
The DC power supply system, including bock *ne switchover unit and the Sorensen DC supplies, shall be operationally checked. The exact procedure will be defined later. However, as a minimum, the system shall be checked for proper operation at 10%, 25%, 50% and 75% of rated output. The DC power supply system shall be run at a load of 29% - 50% rated output for a two (2) weeks' period prior to shipment.
Vendor: ?oxboro
0i6625
t'.'- /
AFPEFDTY E
PROCESP /KALYZER 'PECHTCAT3DHS (To be Issue' jater)
016627
APPIXjIX 7 INSTRUMENT SAfiOT CRITERIA
(To be issue.i ? ater)
016628